Download Built Right BR100 S7 Specifications
Transcript
Chapter 6 Functional Parameter Detail VFD‐G7 Series Frequency Inverter Operation Manual 0: Direct‐on starting Start from the preset starting frequency (F1.01). 1: DC braking first, then start DC braking first, then start from starting frequency. It is suitable for small inertia load which may reverse at the start. 2: Speed tracking, then start Firstly, the frequency inverter calculates the motor’s running speed and direction, and move to setting frequency from tracking speed to achieve smooth no‐impact start to the rotating motor. The method is applicable the large inertia load to re‐start after the drive stops instantly. Notes: the machine type below 5.5kw is without speed tracking function. Decade: Reserve Hundred: Power on terminal running protection selection When the running instruction channel is terminal control, in the process of power on of the frequency inverter, the system will detect the running terminal’s state automatically, and conduct corresponding control according to the multi‐function input terminal function. 0: terminal running command is invalid when power on Even though the running command terminal is detected valid in the process of power on, the frequency inverter will not run, the system will in the running protection state, until disconnecting the running command terminal, then to close the terminal, the frequency inverter will run. 1: Terminal running command is valid when power on If the running command terminal is detected valid in the process of power on, after the initialization, the system will start the running of frequency inverter automatically. This set could achieve the restart after power cut function under the control of terminal. Notes: this function may cause serious consequence, the user should select cautiously. Kbit: restart after power cut function under the keyboard control 0: Restart banned It indicates that the frequency inverter won’t start automatically when power on once again 104