Download Mitsubishi PCA-RP50KAQR Technical data

Transcript
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
October 2009
No. OCS03
REVISED EDITION-C
TECHNICAL DATA BOOK R410A INVERTER
<Indoor unit>
[Model names]
<Outdoor unit>
[Model names]
MFZ-KA·VA
SLZ-KA·VA(L)
SEZ-KC·VA
SEZ-KA·VA
SEZ-KD·VA(L)
PLA-RP·BA
PLA-RP·AA
PCA-RP·KA
PCA-RP·GA(2)
PEAD-RP·JA(L)
PEAD-RP·EA(2)
PEAD-RP·GA
PEA-RP·EA
Revision:
• PLA-RP71BA2, PCA-RP·KA, and
PEAD-RP·JA(L) are added, and
outdoor unit data has been modified in REVISED EDITION-C.
• Some descriptions have been
modified.
• Please void OCS03
REVISED EDITION-B.
SUZ-KA25/35/50/60/71VA
SUZ-KA25/35VAH
CONTENTS
1. REFERENCE SERVICE MANUAL ............................................. 2
2. SPECIFICATIONS....................................................................... 3
3. OUTLINES AND DIMENSIONS ................................................ 15
4. WIRING DIAGRAM ................................................................... 36
5. REFRIGERANT SYSTEM DIAGRAM ...................................... 54
6. PERFORMANCE CURVES ...................................................... 58
7. APPLICABLE EXTENSION PIPE FOR EACH MODEL .......... 62
8. AIR FLOW DATA ...................................................................... 64
9. NOISE CRITERION CURVES .................................................. 90
10. OPTIONAL PARTS ................................................................. 109
kW Model
1
REFERENCE SERVICE MANUAL
For information on service, please refer to the service manual as follows.
1-1. Indoor Unit
Model name
Service Ref.
Service
Manual No.
SLZ-KA25/35/50VA
SLZ-KA25/35/50VAL
SLZ-KA25/35/50VA(1).TH
SLZ-KA25/35/50VAL(1).TH
OC320
SEZ-KA35/50/60/71VA
SEZ-KA35/50/60/71VA.TH
OC321
SEZ-KC25VA
SEZ-KC25VA.W
MEE04K350
SEZ-KD25/35/50/60/71VA
SEZ-KD25/35/50/60/71VAL
SEZ-KD25/35/50/60/71VA.TH
SEZ-KD25/35/50/60/71VAL.TH
HWE07110
MFZ-KA25/35/50VA-E1
MFZ-KA25/35/50VA-E1
OB409
MFZ-KA25/35/50VA-A1
MFZ-KA25/35/50VA-A1
OB410
PLA-RP35/50/60/71BA(1).UK
PLA-RP71BA2.UK
OCH412
OCB412
PLA-RP35/50/60/71BA(1)
OCH416
OCB416
PLA-RP35/50/60/71BA
PLA-RP35/50/60/71AA.UK
OC335
PLA-RP35/50/60/71AA
OC327
PLA-RP35/50/60/71AA
OCH454
OCB454
PCA-RP50/60/71KA
PCA-RP50/60/71KA
PCA-RP50/60/71GA
PCA-RP50GA2
PCA-RP50/60/71GA (#1)
PCA-RP50GA2 (#1)
PEAD-RP35/50/60/71JA(L)
PEAD-RP35/50/60/71JA(L).UK
PEAD-RP35/50/60/71JA(L)R1.UK
HWE08130
BWE08240
BWE09220
PEAD-RP50/60/71EA
PEAD-RP35EA2
PEAD-RP50/60/71EA.UK
PEAD-RP35EA2.UK
HWE05210
PEAD-RP60/71GA
PEAD-RP60/71GA.UK
HWE05060
PEA-RP71EA
PEA-RP71EA.TH-A
OC328
OC326
1-2. Outdoor Unit
Model name
Service Ref.
Service
Manual No.
SUZ-KA25/35/50/60/71VA
SUZ-KA25/35VAH
SUZ-KA25/35VA(R1).TH
SUZ-KA25/35VAH(R1).TH
SUZ-KA50/60/71VA(1).TH
SUZ-KA50/60VAR2.TH
OC322
SUZ-KA25/35/50/60/71VA
SUZ-KA25/35VA(R1).TH-A
SUZ-KA50/60/71VA(1).TH-A
SUZ-KA50/60VAR2.TH-A
OC323
(Note)
When you connect P series indoor units with SUZ, always make sure to follow the piping size of SUZ.
Never use bigger sized pipings in order to ensure not only the system performance but also for your safety.
2
2
SPECIFICATIONS
2-1. FLOOR STANDING TYPE
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Model name
Power supply
Indoor unit
Outdoor unit
Refrigerant pipe size
Refrigerant pipe length
NOTE:
Btu/h
kW
kW
Btu/h
kW
kW
Total input
COP
Energy label class
Booster heater
kW
Phase
:
Cycle
Hz
Voltage
V
Breaker size
A
Air flow at cooling
CMM
(Low-Medium-High-Super High) CFM
Air flow at heating
CMM
(Low-Medium-High-Super High) CFM
External static pressure
Pa
Sound level at cooling
dB(A)
(Low-Medium-High-Super High)
Sound level at heating
dB(A)
(Low-Medium-High-Super High)
External finish (Panel)
Dimension
W : mm
Unit (Panel)
D : mm
H : mm
W : inch
D : inch
H : inch
Weight
kg
Unit (Panel)
lbs
Air flow at cooling
CMM
(Low - High)
CFM
Air flow at heating
CMM
(Low - High)
CFM
Sound level at cooling
dB(A)
(Low - High)
Sound level at heating
dB(A)
(Low - High)
External finish
Dimension
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight
kg
lbs
Gas side O.D.
mm
inch
Liquid side .
mm
inch
m
Height difference
Length
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Upper
Lower
Upper
Heating
Lower
Cooling
limit
limit
limit
limit
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
MFZ-KA25VA
SUZ-KA25VA(H)
8,500
2.5(0.9-3.4)
0.58
4.31
A
0.66
11,600
3.4(0.9-5.1)
0.835
4.07
A
—
1
50
230
10
4.8 - 5.8 - 7.1 - 8.7
170 - 205 - 250 - 310
5.0 - 6.2 - 7.6 - 9.1
180 - 220 - 270 - 320
0
22 - 27 - 32 - 37
MFZ-KA35VA
SUZ-KA35VA(H)
11,900
3.5(0.9-3.9)
1.09
3.21
A
0.65
13,600
4.0(0.9-6.2)
1.10
3.64
A
—
1
50
230
10
5.0 - 6.1 - 7.4 - 9.1
180 - 215 - 260 - 320
5.2 - 6.2 - 7.8 - 9.5
185 - 220 - 275 - 335
0
23 - 28 - 33 - 38
MFZ-KA50VA
SUZ-KA50VA
16,400
4.8(0.9-5.4)
1.55
3.1
B
0.63
20,500
6.0(0.9-7.9)
1.86
3.23
C
—
1
50
230
20
7.1 - 7.9 - 9.2 - 10.7
250 - 280 - 325 - 380
7.4 - 8.8 - 9.8 - 11.8
260 - 310 - 345 - 415
0
32 - 35 - 39 - 43
22 - 27 - 32 - 37
25 - 28 - 33 - 38
32 - 35 - 39 - 44
34.3
1,210
32.3
1,140
46
White Munsell 1.0Y 9.2/0.2
700
200
600
27 - 5/8
7 - 7/8
23 - 5/8
14
31
33.4
1,180
33.4
1,180
47
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
46
48
53 - 55
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
30
66
9.52
3/8
6.35
1/4
Max. 12
Max. 20
Ivory Munsell 3.0Y 7.8/1.1
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
33
73
9.52
3/8
6.35
1/4
Max. 12
Max. 20
840
330
850
33 - 1/16
13
33 - 7/16
53
117
12.7
1/2
6.35
1/4
Max. 30
Max. 30
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA25, KA35VA
KA50
KA25,KA35VAH
46°C D.B.
46°C D.B. 43°C D.B.
-10°C D.B. -15°C D.B.
-10°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B. -20°C D.B. ,-21°C W.B.
3
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
2-2. CEILING CASSETTE TYPE
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Model name
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low - Medium - High)
External static pressure
Sound level
(Low - Medium - High)
External finish (Panel)
Dimension
Unit(Panel)
Weight
Unit (Panel)
Field drain pipe O.D.
Outdoor unit
Air flow at cooling
(Low - High)
Air flow at heating
(Low - High)
Sound level at cooling
(Low - High)
Sound level at heating
(Low - High)
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
SLZ-KA25VA(L)
SUZ-KA25VA
8,500
2.5(0.9 - 3.2)
0.69
3.62
A
0.86
10,200
3.0(0.9 - 4.5)
0.83
3.61
A
—
1
50
230
10
8 - 9 - 10
280 - 320 - 355
0
28 - 31 - 37
SLZ-KA35VA(L)
SUZ-KA35VA
11,900
3.5(1.0 - 3.9)
1.06
3.30
A
0.77
13,600
4.0(0.9 - 5.0)
1.10
3.64
A
—
1
50
230
10
8 - 9 - 11
280 - 320 - 390
0
29 - 33 - 38
SLZ-KA50VA(L)
SUZ-KA50VA
15,700
4.6(1.1 - 5.2)
1.63
2.82
C
0.68
17,100
5.0(0.9 - 6.5)
1.55
3.23
C
—
1
50
230
20
8 - 9 - 11
280 - 320 - 390
0
30 - 34 - 39
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
CMM
CFM
dB(A)
34.3
1,210
32.3
1,140
46
White Munsell 6.4Y 8.9/0.4
570(650)
570(650)
208(20)
22 - 7/16(25 - 9/16)
22 - 7/16(25 - 9/16)
8-3/16(13/16)
16.5(3)
36(7)
32
1 - 1/4
33.4
1,180
33.4
1,180
47
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
dB(A)
46
48
53 - 55
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
30
66
9.52
3/8
6.35
1/4
Max. 12
Max. 20
Ivory Munsell 3.0Y 7.8/1.1
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
33
76
9.52
3/8
6.35
1/4
Max. 12
Max. 20
840
330
850
33 - 1/16
13
33 - 7/16
53
117
12.7
1/2
6.35
1/4
Max. 30
Max. 30
Btu/h
kW
kW
Btu/h
kW
kW
kW
:
Hz
V
A
CMM
CFM
Pa
dB(A)
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Upper
Lower
Upper
Heating
Lower
Cooling
limit
limit
limit
limit
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA25, KA35VA
KA50
46°C D.B.
43°C D.B.
-10°C D.B.
-15°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B.
4
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Outdoor unit
Refrigerant pipe size
Refrigerant pipe length
Btu/h
kW
kW
Btu/h
kW
kW
Total input
COP
Energy label class
Booster heater
kW
Phase
:
Cycle
Hz
Voltage
V
Breaker size
A
Air flow
CMM
(Low-Medium2-Medium1-High)
CFM
External static pressure
Pa
Sound level
dB(A)
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
W : mm
Unit (Panel)
D : mm
H : mm
W : inch
D : inch
H : inch
Weight
kg
Unit (Panel)
lbs
Field drain pipe O.D.
mm
inch
Air flow at cooling
CMM
(Low - High)
CFM
Air flow at heating
CMM
(Low - High)
CFM
Sound level at cooling
dB(A)
(Low - High)
Sound level at heating
dB(A)
(Low - High)
External finish
Dimension
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight
kg
lbs
Gas side O.D.
mm
inch
Liquid side O.D.
mm
inch
Height difference
m
Length
m
PLA-RP35BA
PLA-RP50BA
PLA-RP60BA
PLA-RP71BA(2)
SUZ-KA35VA
SUZ-KA50VA
SUZ-KA60VA
SUZ-KA71VA
11,900
17,100
19,400
24,200
3.5(1.0 - 3.9)
5.0(1.1 - 5.6)
5.7(1.1 - 6.3)
7.1(0.9 - 8.1)
1.09
1.78
1.94
2.53(2.47)
3.21
2.81
2.94
2.81(2.87)
A
C
C
C (—)
0.84
0.81
0.76
0.73
14,000
20,500
23,500
27,300
4.1(0.9 - 5.0)
6.0(0.9 - 7.2)
6.9(0.9 - 8.0)
8.0(0.9 - 10.2)
1.11
1.82
2.11
2.49(2.45)
3.69
3.30
3.27
3.21(3.27)
A
C
C
C (—)
—
—
—
—
1
1
1
1
50
50
50
50
230
230
230
230
10
20
20
20
11 - 12 - 13 - 15
12 - 14 - 16 - 18
12 - 14 - 16 - 18
14 - 16 - 18 - 21
390 - 425 - 460 - 530 425 - 495 - 565 - 635 425 - 495 - 565 - 635 495 - 565 - 635 - 740
0
0
0
0
27 - 28 - 29 - 31
28 - 29 - 31 - 32
28 - 29 - 31 - 32
28 - 30 - 32 - 34
White Munsell 6.4Y 8.9/0.4
840 (950)
840 (950)
258 (35)
33 - 1/16 (37 - 3/8)
33 - 1/16 (37 - 3/8)
10 - 3/16 (1 - 3/8)
22 (6)
49 (13)
23 (6)
51 (13)
32
1 - 1/4
33.4
1,180
33.4
1,180
47
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
48
53 - 55
53 - 55
53 - 55
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
33
76
9.52
3/8
6.35
1/4
Max. 12
Max. 20
Ivory Munsell 3.0Y 7.8/1.1
840
840
330
330
850
850
33 - 1/16
33 - 1/16
13
13
33 - 7/16
33 - 7/16
53
53
117
117
12.7
15.88
1/2
5/8
6.35
6.35
1/4
1/4
Max. 30
Max. 30
Max. 30
Max. 30
840
330
850
33 - 1/16
13
33 - 7/16
58
128
15.88
5/8
9.52
3/8
Max. 30
Max. 30
The values in the parentheses indicate the specification values for PLA-RP71BA2.
NOTE:
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Upper
Lower
Upper
Heating
Lower
Cooling
limit
limit
limit
limit
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA50, KA60, KA71
KA35VA
46°C D.B.
43°C D.B.
-10°C D.B.
-15°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B.
5
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Outdoor unit
Refrigerant pipe size
Refrigerant pipe length
NOTE:
Btu/h
kW
kW
Btu/h
kW
kW
Total input
COP
Energy label class
Booster heater
kW
Phase
:
Cycle
Hz
Voltage
V
Breaker size
A
Air flow
CMM
(Low-Medium2-Medium1-High) CFM
External static pressure
Pa
Sound level
dB(A)
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
W : mm
Unit (Panel)
D : mm
H : mm
W : inch
D : inch
H : inch
Weight
kg
Unit (Panel)
lbs
Field drain pipe O.D.
mm
inch
Air flow at cooling
CMM
(Low - High)
CFM
Air flow at heating
CMM
(Low - High)
CFM
Sound level at cooling
dB(A)
(Low - High)
Sound level at heating
dB(A)
(Low - High)
External finish
Dimension
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight
kg
lbs
Gas side O.D.
mm
inch
Liquid side O.D.
mm
inch
Height difference
m
Length
m
PLA-RP35AA
PLA-RP50AA
PLA-RP60AA
PLA-RP71AA
SUZ-KA35VA
SUZ-KA50VA
SUZ-KA60VA
SUZ-KA71VA
11,900
17,100
19,400
24,200
3.5(1.0 - 3.9)
5.0(1.1 - 5.6)
5.7(1.1 - 6.3)
7.1(0.9 - 8.1)
1.09
1.78
1.94
2.53
3.21
2.81
2.94
2.81
A
C
C
C
0.88
0.86
0.83
0.77
14,000
20,500
23,500
27,300
4.1(0.9 - 5.0)
6.0(0.9 - 7.2)
6.9(0.9 - 8.0)
8.0(0.9 - 10.2)
1.11
1.76
2.11
2.49
3.69
3.41
3.27
3.21
A
B
C
C
—
—
—
—
1
1
1
1
50
50
50
50
230
230
230
130
10
20
20
20
11 - 12 - 13 - 14
14 - 15 - 16 - 18
14 - 15 - 16 - 18
15 - 16 - 18 - 20
390 - 425 - 460 - 495 495 - 530 - 565 - 635 495 - 530 - 565 - 635 530 - 565 - 635 - 705
0
0
0
0
27 - 28 - 29 - 31
28 - 29 - 31 - 33
28 - 29 - 31 - 33
28 - 30 - 32 - 34
33.4
1,180
33.4
1,180
47
48
Upper
Lower
Upper
Heating
Lower
Cooling
limit
limit
limit
limit
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
53 - 55
53 - 55
Ivory Munsell 3.0Y 7.8/1.1
840
840
330
330
850
850
33 - 1/16
33 - 1/16
13
13
33 - 7/16
33 - 7/16
53
53
117
117
12.7
15.88
1/2
5/8
6.35
6.35
1/4
1/4
Max. 30
Max. 30
Max. 30
Max. 30
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
33
76
9.52
3/8
6.35
1/4
Max. 12
Max. 20
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
White Munsell 0.70Y 8.59/0.97
840 (950)
840 (950)
258 (30)
33 - 1/16 (37 - 3/8)
33 - 1/16 (37 - 3/8)
10 - 3/16 (1 - 3/16)
24 (5)
53 (11)
32
1 - 1/4
27.5 - 49
27.5 - 49
970 - 1,730
970 - 1,730
36.8 - 49
36.8 - 49
1,300 - 1,730
1,300 - 1,730
51 - 53
51 - 53
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
53 - 55
840
330
850
33 - 1/16
13
33 - 7/16
58
128
15.88
5/8
9.52
3/8
Max. 30
Max. 30
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA35VA
KA50, KA60, KA71
46°C D.B.
43°C D.B.
-10°C D.B.
-15°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B.
6
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
2-3. CEILING-SUSPENDED TYPE
Model name
Indoor unit
Outdoor unit
Capacity
Cooling
Total input
PCA-RP50KA
SUZ-KA50VA
17,100
5.0(1.1-5.6)
1.660
3.01
B
0.79
18,800
5.5(0.9-6.6)
1.710
3.22
C
—
1
50
230
20
10 - 11 - 13 - 15
355 - 390 - 460 - 530
0
32 - 34 - 37 - 40
PCA-RP60KA
SUZ-KA60VA
19,400
5.7(1.1-6.3)
1.770
3.22
A
0.81
23,500
6.9(0.9-8.0)
2.020
3.42
B
—
1
50
230
20
15 - 16 - 17 - 19
530 - 565 - 600 - 670
0
33 - 35 - 37 - 40
PCA-RP71KA
SUZ-KA71VA
24,200
7.1(0.9-8.1)
2.210
3.21
A
0.76
27,000
7.9(0.9-10.2)
2.320
3.41
B
—
1
50
230
20
16 - 17 - 18 - 20
565 - 600 - 635 - 705
0
35 - 37 - 39 - 41
lbs
mm
inch
CMM
CFM
CMM
CFM
dB(A)
960
680
230
37 - 13/16
26 - 3/4
9 - 1/16
25
55
26
1
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
White Munsell 6.4Y 8.9/0.4
1,280
680
230
50 - 3/8
26 - 34
9 - 1/16
32
71
26
1
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
1,280
680
230
50 - 3/8
26 - 3/4
9 - 1/16
32
71
26
1
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
dB(A)
53 - 55
53 - 55
53 - 55
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
840
330
850
33 - 1/16
13
33 - 7/16
53
117
12.7
1/2
6.35
1/4
Max. 30
Max. 30
Btu/h
kW
kW
EER
Energy label class
SHF
Capacity
Heating
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
Power supply
Indoor unit
External static pressure
Sound level
(Low-Medium2-Medium1-High)
External finish
Dimension
Weight
Field drain pipe O.D.
Outdoor unit
Air flow at cooling
(Low - High)
Air flow at heating
(Low - High)
Sound level at cooling
(Low - High)
Sound level at heating
(Low - High)
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
kW
:
Hz
V
A
CMM
CFM
Pa
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
Indoor
D.B. 32°C, W.B. 23°C
D.B. 21°C, W.B. 15°C
D.B. 27°C
D.B. 20°C
Ivory Munsell 3.0Y 7.8/1.1
840
330
850
33 - 1/16
13
33 - 7/16
53
117
15.88
5/8
6.35
1/4
Max. 30
Max. 30
840
330
850
33 - 1/16
13
33 - 7/16
58
128
15.88
5/8
9.52
3/8
Max. 30
Max. 30
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
D.B. 43°C
D.B. -15°C
D.B. 24°C, W.B. 18°C
D.B. -10°C, W.B. -11°C
7
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
Model name
Indoor unit
Outdoor unit
Capacity
Cooling
Total input
Btu/h
kW
kW
EER
Energy label class
SHF
Capacity
Heating
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
Power supply
Indoor unit
External static pressure
Sound level
(Low-Medium2-Medium1-High)
External finish
Dimension
Weight
Field drain pipe O.D.
Outdoor unit
Air flow at cooling
(Low - High)
Air flow at heating
(Low - High)
Sound level at cooling
(Low - High)
Sound level at heating
(Low - High)
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
kW
:
Hz
V
A
CMM
CFM
Pa
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
Upper limit
Lower limit
Upper limit
Heating
Lower limit
PCA-RP50GA2
SUZ-KA50VA
17,000
5.0(1.1 - 5.6)
1.78
2.81
C
0.81
20,500
6.0(0.9 - 7.2)
1.76
3.41
B
—
PCA-RP60GA
SUZ-KA60VA
18,800
5.5(1.1 - 6.3)
1.92
2.86
C
0.79
23,500
6.9(0.9 - 8.0)
2.05
3.37
C
—
PCA-RP71GA
SUZ-KA71VA
24,200
7.1(0.9 - 8.1)
2.53
2.81
C
0.71
27,300
8.0(0.9 - 10.2)
2.49
3.21
C
—
1
50
230
20
10 - 11 - 12 - 13
355 - 390 - 425 - 460
0
37 - 38 - 40 - 42
1000
39 - 3/8
27
60
14 - 15 - 16 - 18
495 - 530 - 565 - 635
0
37 - 39 - 41 - 43
White Munsell 0.70Y 8.59/0.97
1310
680
210
51 - 9/16
26 - 3/4
8 - 1/4
34
75
26
1
27.5 - 49
27.5 - 49
970 - 1,730
970 - 1,730
36.8 - 49
36.8 - 49
970 - 1,730
1,300 - 1,730
51 - 53
51 - 53
lbs
mm
inch
CMM
CFM
CMM
CFM
dB(A)
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
dB(A)
53 - 55
53 - 55
840
330
850
33 - 1/16
13
33 - 7/16
53
117
12.7
1/2
6.35
1/4
Max. 30
Max. 30
840
330
850
33 - 1/16
13
33 - 7/16
53
117
12.7
1/2
6.35
1/4
Max. 30
Max. 30
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
53 - 55
53 - 55
Ivory Munsell 3.0Y 7.8/1.1
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
PCA-RP50GA
SUZ-KA50VA
16,000
4.7(1.1 - 5.4)
1.80
2.61
D
0.70
18,800
5.5(0.9 - 6.6)
1.92
2.86
D
—
Indoor
D.B. 32°C, W.B. 23°C
D.B. 21°C, W.B. 15°C
D.B. 27°C
D.B. 20°C
840
330
850
33 - 1/16
13
33 - 7/16
53
117
15.88
5/8
6.35
1/4
Max. 30
Max. 30
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
D.B. 43°C
D.B. -15°C
D.B. 24°C, W.B. 18°C
D.B. -10°C, W.B. -11°C
8
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
840
330
850
33 - 1/16
13
33 - 7/16
58
128
15.88
5/8
9.52
3/8
Max. 30
Max. 30
2-4. CEILING-CONCEALED TYPE
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Btu/h
kW
kW
Btu/h
kW
kW
Total input
COP
Energy label class
Booster heater
kW
Power supply
Phase
:
Cycle
Hz
Voltage
V
Breaker size
A
Indoor unit
Air flow
CMM
(Low - Medium - High)
CFM
External static pressure
Pa
Sound level
dB(A)
(Low - Medium - High)
External finish
Dimension
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight
kg
lbs
mm
Field drain pipe O.D.
inch
Outdoor unit
Air flow at cooling
CMM
(Low - High)
CFM
Air flow at heating
CMM
(Low - High)
CFM
Sound level at cooling dB(A)
(Low - High)
Sound level at heating dB(A)
(Low - High)
External finish
Dimension
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight
kg
lbs
Refrigerant pipe size Gas side O.D.
mm
inch
Liquid side O.D.
mm
inch
Refrigerant pipe length Height difference
m
Length
m
NOTE:
SEZ-KD25VA(L)
SUZ-KA25VA
8,500
2.5(0.9 - 3.2)
0.778
3.21
A
0.80
10,200
3.0(0.9 - 4.5)
0.83
3.61
A
—
1
50
230
10
5.5 - 7.0 - 9.0
190 - 250 - 320
5 - 15 - 35 - 50
23 - 26 -30
SEZ-KD35VA(L)
SUZ-KA35VA
11,900
3.5(1.0 - 3.9)
1.09
3.21
A
0.78
13,600
4.0(0.9 - 5.0)
1.108
3.61
A
—
1
50
230
10
7.0 - 9.0 - 11.0
250 - 320 - 390
5 - 15 - 35 - 50
23 - 28 -33
700
700
200
27 - 9/16
27 - 9/16
7 - 7/8
18
40
900
700
200
35 - 7/16
27 - 9/16
7 - 7/8
21
47
34.3
1,210
32.3
1,140
46
Upper
Lower
Upper
Heating
Lower
Cooling
limit
limit
limit
limit
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
SEZ-KD60VA(L)
SUZ-KA60VA
18,800
5.5(1.1 - 6.3)
1.89
2.91
C
0.79
23,900
7.0(0.9 - 8.0)
2.05
3.41
B
—
1
50
230
20
12.0 - 15.0 - 18.0
420 - 530 - 640
5 - 15 - 35 - 50
30 - 34 -38
SEZ-KD71VA(L)
SUZ-KA71VA
24,200
7.1(0.9 - 8.3)
2.53
2.81
C
0.74
27,600
8.1(0.9 - 10.4)
2.37
3.42
B
—
1
50
230
20
12.0 - 16.0 - 20.0
420 - 570 - 710
5 - 15 - 35 - 50
30 - 35 -40
1100
700
200
43 - 5/16
27 - 9/16
7 - 7/8
27
60
1100
700
200
43 - 5/16
27 - 9/16
7 - 7/8
27
60
33.4
1,180
33.4
1,180
47
Galvanized sheets
900
700
200
35 - 7/16
27 - 9/16
7 - 7/8
23
51
32
1 - 9/32
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
27.5 - 49
970 - 1,730
36.8 - 49
1.300 - 1,730
51 - 53
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
46
48
53 - 55
53 - 55
53 - 55
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
30
66
9.52
3/8
6.35
1/4
Max. 12
Max. 20
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
33
76
9.52
3/8
6.35
1/4
Max. 12
Max. 20
Ivory Munsell 3.0Y 7.8/1.1
840
330
850
33 - 1/16
13
33 - 7/16
53
117
12.7
1/2
6.35
1/4
Max. 30
Max. 30
840
330
850
33 - 1/16
13
33 - 7/16
53
117
15.88
5/8
6.35
1/4
Max. 30
Max. 30
840
330
850
33 - 1/16
13
33 - 7/16
58
128
15.88
5/8
9.52
3/8
Max. 30
Max. 30
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
SEZ-KD50VA(L)
SUZ-KA50VA
17,100
5.0(1.1 - 5.6)
1.78
2.81
C
0.76
20,500
6.0(1.1 - 7.2)
1.87
3.21
C
—
1
50
230
20
10.0 - 12.5 - 15.0
350 - 440 - 530
5 - 15 - 35 - 50
30 - 34 -37
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA25, KA35VA
KA50, KA60, KA71
46°C D.B.
43°C D.B.
-15°C D.B.
-10°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B.
9
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Btu/h
kW
kW
Btu/h
kW
kW
Total input
COP
Energy label class
Booster heater
kW
Phase
:
Cycle
Hz
Voltage
V
Breaker size
A
Air flow
CMM
(Low - High)
CFM
External static pressure
Pa
Sound level
dB(A)
(Low - High)
External finish
Dimension
W : mm
790
D : mm
550
H : mm
225
W : inch
31 - 1/8
D : inch
21 - 5/8
H : inch
8 - 7/8
Weight
kg
19
lbs
42
Unit drain pipe
R1(External thread)
Power supply
Indoor unit
Outdoor unit
Air flow at cooling
CMM
(Low - High)
CFM
Air flow at heating
CMM
(Low - High)
CFM
Sound level at cooling dB(A)
(Low - High)
Sound level at heating dB(A)
(Low - High)
External finish
Dimension
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
Weight
kg
lbs
Refrigerant pipe size Gas side O.D.
mm
inch
Liquid side O.D.
mm
inch
Refrigerant pipe length Height difference
m
Length
m
NOTE:
SEZ-KC25VA
SUZ-KA25VA
8,500
2.5(0.9 - 3.2)
0.73
3.42
A
0.74
10,200
3.0(0.9 - 4.5)
0.83
3.61
A
—
1
50
230
10
4.8 - 7.9
170 - 280
Std:5 Max:5
25 - 36
Upper
Lower
Upper
Heating
Lower
Cooling
limit
limit
limit
limit
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
SEZ-KA50VA
SUZ-KA50VA
17,100
5.0(1.1 - 5.6)
1.78
2.81
C
0.75
20,100
5.9(1.1 - 7.2)
1.84
3.21
C
—
1
50
230
20
12 - 17
425 - 600
Std:30 Max:50
31 - 39
SEZ-KA60VA
SUZ-KA60VA
18,800
5.5(1.1 - 6.3)
1.96
2.81
C
0.75
23,500
6.9(0.9 - 8.0)
2.45
2.82
D
—
1
50
230
20
12 - 20
425 - 705
Std:30 Max:50
32 - 43
Galvanized sheets
1100
700
270
43 - 5/16
27 - 9/16
10 - 5/8
33.5
74
R1(External thread)
SEZ-KA71VA
SUZ-KA71VA
24,200
7.1(0.9 - 8.3)
2.46
2.89
C
0.74
27,600
8.1(0.9 - 10.4)
2.36
3.43
B
—
1
50
230
20
12 - 20
425 - 705
Std:30 Max:50
32 - 43
35
77
34.3
1,210
32.3
1,140
46
33.4
1,180
33.4
1,180
47
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
27.5 - 49
970 - 1,730
36.8 - 49
1.300 - 1,730
51 - 53
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
46
48
53 - 55
53 - 55
53 - 55
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
30
66
9.52
3/8
6.35
1/4
Max. 12
Max. 20
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
33
76
9.52
3/8
6.35
1/4
Max. 12
Max. 20
Ivory Munsell 3.0Y 7.8/1.1
840
330
850
33 - 1/16
13
33 - 7/16
53
117
12.7
1/2
6.35
1/4
Max. 30
Max. 30
840
330
850
33 - 1/16
13
33 - 7/16
53
117
15.88
5/8
6.35
1/4
Max. 30
Max. 30
840
330
850
33 - 1/16
13
33 - 7/16
58
128
15.88
5/8
9.52
3/8
Max. 30
Max. 30
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
SEZ-KA35VA
SUZ-KA35VA
11,900
3.5(1.0 - 3.9)
1.06
3.30
A
0.77
13,600
4.0(0.9 - 5.0)
1.10
3.64
A
—
1
50
230
10
10 - 13
355 - 460
Std:30 Max:50
30 - 35
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA25, KA35VA
KA50, KA60, KA71
46°C D.B.
43°C D.B.
-15°C D.B.
-10°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B.
10
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low - High)
External static pressure
Sound level
(Low - High)
External finish
Dimension
Power supply
Indoor unit
Weight
Field drain pipe O.D.
Outdoor unit
Air flow at cooling
(Low - High)
Air flow at heating
(Low - High)
Sound level at cooling
(Low - High)
Sound level at heating
(Low - High)
External finish
Dimension
Btu/h
kW
kW
Btu/h
kW
kW
kW
:
Hz
V
A
CMM
CFM
Pa
dB(A)
PEAD-RP35JA(L)
PEAD-RP50JA(L)
SUZ-KA35VA
SUZ-KA50VA
12,300
16,700
3.6 (1.0-3.9)
4.9 (1.1-5.6)
1.060 (1.040)
1.520 (1.500)
3.40 (3.46)
3.22 (3.27)
A
A
0.85
0.85
14,000
20,100
4.1 (0.9-5.0)
5.9 (0.9-7.2)
1.110
1.620
3.69
3.64
A
A
—
—
1
1
50
50
230
230
16
20
10 - 12 - 14
12 - 14.5 - 17
353 - 424 - 494
424 - 512 - 600
35/50/70/100/150
23 - 27 - 30
26 - 31 - 35
PEAD-RP60JA(L)
PEAD-RP71JA(L)
SUZ-KA71VA
SUZ-KA60VA
24,200
19,400
7.1 (0.9-8.1)
5.7 (1.1-6.3)
2.210 (2.190)
1.680 (1.660)
3.21 (3.24)
3.39 (3.43)
A
A
0.83
0.86
27,300
23,900
8.0 (0.9-10.2)
7.0 (0.9-8.0)
2.090
1.940
3.83
3.61
A
A
—
—
1
1
50
50
230
230
20
20
17.5 - 21 - 25
14.5 - 18 - 21
618 - 742 - 883
512 - 636 - 742
35/50/70/100/150
26 - 30 - 34
25 - 29 - 33
Galvanized sheets
900
732
250
35 - 7/16
28 - 7/8
9 - 7/8
26 (25)
28 (27)
58 (56)
62 (60)
Galvanized sheets
1,100
732
250
43 - 5/16
28 - 7/8
9 - 7/8
33 (32)
33 (32)
73 (71)
73 (71)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
CMM
CFM
dB(A)
32
1 - 1/4
dB(A)
33.4
1,180
33.4
1,180
47
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
48
53 - 55
53 - 55
53 - 55
W : mm
800
D : mm
285
H : mm
550
W : inch
31 - 1/2
D : inch
11 - 1/4
H : inch
21 - 5/8
Weight
kg
33
lbs
76
Refrigerant pipe size
Gas side O.D.
mm
9.52
inch
3/8
Liquid side O.D.
mm
6.35
inch
1/4
Refrigerant pipe length Height difference
m
Max. 12
Length
m
Max. 20
The values in the parentheses indicate the specification values for PEAD-RP·JAL.
NOTE:
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Upper
Lower
Upper
Heating
Lower
Cooling
limit
limit
limit
limit
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
Ivory Munsell 3.0Y 7.8/1.1
840
840
330
330
850
850
33 - 1/16
33 - 1/16
13
13
33 - 7/16
33 - 7/16
53
53
117
117
12.7
15.88
1/2
5/8
6.35
6.35
1/4
1/4
Max. 30
Max. 30
Max. 30
Max. 30
840
330
850
33 - 1/16
13
33 - 7/16
58
128
15.88
5/8
9.52
3/8
Max. 30
Max. 30
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA25, KA35VA
KA50, KA60, KA71
46°C D.B.
43°C D.B.
-15°C D.B.
-10°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B.
11
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low - High)
External static pressure
Sound level
(Low - High)
External finish
Dimension
Power supply
Indoor unit
Weight
Unit drain pipe
Air flow at cooling
(Low - High)
Air flow at heating
(Low - High)
Sound level at cooling
(Low - High)
Sound level at heating
(Low - High)
External finish
Dimension
Outdoor unit
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
:
Hz
V
A
CMM
CFM
Pa
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
CMM
CFM
CMM
CFM
dB(A)
PEAD-RP35EA2
PEAD-RP50EA
SUZ-KA35VA
SUZ-KA50VA
12,300
16,700
3.6(1.0 - 3.9)
4.9(1.1 - 5.6)
1.12
1.74
3.21
2.82
A
C
0.90
0.79
14,000
20,100
4.1(0.9 - 5.0)
5.9(0.9 - 7.2)
1.13
1.69
3.63
3.49
A
B
—
—
1
1
50
50
230
230
10
20
13.5 - 17
476 - 600
30(70)
36 - 40
(70Pa : 38 - 44)
Galvanized sheets
935
700
295
36 - 13/16
27 - 5/8
11 - 5/8
33
35
73
77
R1(External thread)
33.4
27.5 - 49
1,180
970 - 1,730
33.4
36.8 - 49
1,180
1,300 - 1,730
47
51 - 53
dB(A)
48
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
800
285
550
31 - 1/2
11 - 1/4
21 - 5/8
33
76
9.52
3/8
6.35
1/4
Max. 12
Max. 20
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Upper
Lower
Upper
Heating
Lower
Cooling
limit
limit
limit
limit
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
PEAD-RP60EA
PEAD-RP71EA
SUZ-KA60VA
SUZ-KA71VA
20,500
24,200
6.0(1.1 - 6.3)
7.1(0.9 - 8.1)
2.05
2.53
2.93
2.81
C
C
0.80
0.81
23,900
27,300
7.0(0.9 - 8.0)
8.0(0.9 - 10.2)
2.07
2.49
3.38
3.21
C
C
—
—
1
1
50
50
230
230
20
20
17 - 21
20 - 25
600 - 741
706 - 883
30(70)
70(130)
37 - 41
37 - 41
(70Pa : 39 - 46)
(130Pa : 40 - 45)
Galvanized sheets
1175
700
740
295
325
46 - 1/8
27 - 5/8
29 - 1/8
11 - 5/8
12 - 13/16
42
44
92
97
R1(External thread)
27.5 - 49
27.5 - 49
970 - 1,730
970 - 1,730
36.8 - 49
36.8 - 49
1,300 - 1,730
1,300 - 1,730
51 - 53
51 - 53
53 - 55
53 - 55
Ivory Munsell 3.0Y 7.8/1.1
840
840
330
330
850
850
33 - 1/16
33 - 1/16
13
13
33 - 7/16
33 - 7/16
53
53
117
117
12.7
15.88
1/2
5/8
6.35
6.35
1/4
1/4
Max. 30
Max. 30
Max. 30
Max. 30
53 - 55
840
330
850
33 - 1/16
13
33 - 7/16
58
128
15.88
5/8
9.52
3/8
Max. 30
Max. 30
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA25, KA35VA
KA50, KA60, KA71
46°C D.B.
43°C D.B.
-15°C D.B.
-10°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B.
12
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low - High)
External static pressure
Sound level
(Low - High)
External finish
Dimension
Power supply
Indoor unit
Weight
Unit drain pipe
Air flow at cooling
(Low - High)
Air flow at heating
(Low - High)
Sound level at cooling
(Low - High)
Sound level at heating
(Low - High)
External finish
Dimension
Outdoor unit
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
:
Hz
V
A
CMM
CFM
Pa
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
Indoor
Upper
Lower
Upper
Heating
Lower
limit
limit
limit
limit
PEAD-RP71GA
SUZ-KA71VA
24,200
7.1(0.9 - 8.1)
2.53
2.81
C
0.81
27,300
8.0(0.9 - 10.2)
2.49
3.21
C
—
1
50
230
20
16.5 - 21
582 - 741
20 - 25
706 - 883
10/50/70
33 - 37/35 - 40/36 - 42 35 - 38/37 - 41/37 - 43
(10/50/70Pa)
(10/50/70Pa)
Galvanized sheets
W : mm
1171
D : mm
740
H : mm
275
W : inch
46 - 1/8
D : inch
29 - 1/8
H : inch
10 - 13/16
kg
42
lbs
93
R1(External thread)
CMM
27.5 - 49
27.5 - 49
CFM
970 - 1,730
970 - 1,730
CMM
36.8 - 49
36.8 - 49
CFM
1,300 - 1,730
1,300 - 1,730
dB(A)
51 - 53
51 - 53
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
PEAD-RP60GA
SUZ-KA60VA
19,400
5.7(1.1 - 6.3)
2.03
2.81
C
0.82
23,900
7.0(0.9 - 8.0)
2.05
3.41
B
—
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
53 - 55
53 - 55
Ivory Munsell 3.0Y 7.8/1.1
840
840
330
330
850
850
33 - 1/16
33 - 1/16
13
13
33 - 7/16
33 - 7/16
53
58
117
128
15.88
15.88
5/8
5/8
6.35
9.52
1/4
3/8
Max. 30
Max. 30
Max. 30
Max. 30
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA60, KA71
43°C D.B.
-15°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B.
13
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
SHF
Capacity
Btu/h
kW
kW
Total input
COP
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low - High)
External static pressure
Sound level
(Low - High)
External finish
Dimension
Power supply
Indoor unit
Weight
Btu/h
kW
kW
kW
:
Hz
V
A
CMM
R/s
Pa
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
Galvanized sheets
785
690
428
31
27 - 1/16
16 - 7/8
46
101
R1(External thread)
CMM
CFM
CMM
CFM
dB(A)
27.5 - 49
970 - 1,730
36.8 - 49
1,300 - 1,730
51 - 53
dB(A)
53 - 55
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
Ivory Munsell 3.0Y 7.8/1.1
840
330
850
33 - 1/16
13
33 - 7/16
58
128
15.88
5/8
9.52
3/8
Max. 30
Max. 30
Unit drain pipe
Outdoor unit
Air flow at cooling
(Low - High)
Air flow at heating
(Low - High)
Sound level at cooling
(Low - High)
Sound level at heating
(Low - High)
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27 (80°F) W.B. 19 (66°F)
Heating
Indoor : D.B. 20 (68°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Upper
Lower
Upper
Heating
Lower
Cooling
limit
limit
limit
limit
PEA-RP71EA
SUZ-KA71VA
23,500
6.9
2.90
2.38
0.84
27,300
8.0
2.49
3.21
—
1
50
230
20
22 - 27
367 - 450
125
52 - 55
32°C D.B. , 23°C W.B.
21°C D.B. , 15°C W.B.
27°C D.B.
20°C D.B.
Outdoor : D.B. 35 (95°F) W.B. 24 (75°F)
Outdoor : D.B. 7 (45°F) W.B. 6 (43°F)
Outdoor
KA71
43°C D.B.
-15°C D.B.
24°C D.B. , 18°C W.B.
-10°C D.B. ,-11°C W.B.
14
3. Guaranteed voltage
198~264V, 50Hz
4. Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Outdoor unit
Single phase, 230V 50Hz
OUTLINES AND DIMENSIONS
Unit : mm
INDOOR UNIT
MFZ-KA25VA
MFZ-KA35VA
MFZ-KA50VA
700
607
46.5
More than
100mm
Air in
600
96
54
508
60
155
131
7
131
593
333
363
Installation plate
210
Indoor unit
337
337
15
60
60
60
80
454
12
128
45
35
72
110
4-:6 Hole
drain
137
147
12
60
Gas pipe
25, 35::9.52(flared)3/8"
50::12.7(flared)1/2"
Liquid pipe
:6.35(flared)1/4
11
123
125
60
Air out
19
118
125
More than
100mm
200
12
12
Air out
19
More than
100mm
46.5
165
205
3
W 100
25
W 73.4
Cut out hole
420
Suspension bolt pitch
Refrigerant pipe (liquid)
Refrigerant pipe (gas)
Emergency operation switch(cooling)
Receiver
Emergency operation switch(heating)
MITSUBISHI
ELECTRIC
DEFROST/STAND BY lamp
Operation lamp
(WIRELESS PANEL)
Ceiling surface
118
3- W 2.8 hole
Burring hole
66
121
Detail drawing of fresh air intake
12
0°
15~37
576~620 Ceiling hole
15~37
93
650
17
202
230
35 55
V/M
V/M
377
Air intake hole
Grille
Terminal block
(Case of Wired remote controller)Terminal block
650
301
Air outlet hole
15~37
199
352
335
576~620 Ceiling hole
570
530
Suspension bolt
pitch
V/M
V/M
Ceiling surface
335
15~37
193
570
Brand label
Vane motor
Air intake grille
Auto vane
Drain hole
Grille
SLZ-KA50VA(L)
W 12.7mm
flared connection
1/2"F
W 9.52mm
flared connection
3/8"F
W 6.35mm
SLZ-KA35VA(L) flared connection
1/4"F
W 6.35mm
flared connection
1/4"F
W 9.52mm
flared connection
3/8"F
W 6.35mm
flared connection
1/4"F
SLZ-KA25VA(L)
Refrigerant pipe
(gas)
Models
Refrigerant pipe
(liquid)
Wiring entry
Suspension bolt
M10 or 3/8
(procure locally)
Drain pipe
VP-25 connection
(O.D. W 32)
87
235
20
31
208
+5
27 0
57
56
38~58
55 35 Suspension bolt
lower edge
301
Air outlet hole
16
377
Air intake hole
182
0°
12
48
Fresh air
intake
SLZ-KA25VAL
SLZ-KA35VAL
SLZ-KA50VAL
SLZ-KA25VA
SLZ-KA35VA
SLZ-KA50VA
Unit : mm
SEZ-KD25VA(L)
SEZ-KD35VA(L)
SEZ-KD50VA(L)
SEZ-KD60VA(L)
SEZ-KD71VA(L)
Unit : mm
20
12
157.5
37 100
37
H
100XJ=K
23
20
12
57
625 (Suspension bolt pitch)
49
Terminal block
Terminal block (Indoor/outdoor connecting line)
(Remote controller transmission line)
70
270
1 Refrigerant piping
flare connection (gas)
Drain pipe(O.D.W32)(Spontaneous draining)
Access door
50
7
77
G
Note2
Knockout hole W27
(Indoor/outdoor connecting line)
200
102
23
25
116
2X2-W2.9
Knockout hole W27
(Remote controller transmission line)
Control box
100
150 (Duct)
700
677
23
10
Air filter
Suspension bolt hole
4-14X30 Slot
170
2 Refrigerant piping
flare connection (liquid)
L-W2.9
90
10
2XE-W2.9
More than 10mm
More than 20mm
25
20
30
88
100
100
Air
inlet
C
A
Air
outlet
B (Suspension bolt pitch)
D (Duct)
100X(E-1)=F
88
15
50
50
~1
50
0
00
45
n3
tha
e
r
Mo
45
0
Ceiling surface Access door
Make the access door at the appointed position properly
for service maintenance.
Required space for service and maintenance
Model
SEZ-KD25VA(L)
SEZ-KD35VA(L)
SEZ-KD50VA(L)
SEZ-KD60VA(L)
SEZ-KD71VA(L)
A
700
B
752
C
798
D
660
E
7
F
600
G
800
H
660
J
5
K
500
L
16
900
952
998
860
9
800
1000
860
7
700
20
1100 1152 1198 1060
11
1000 1200 1060
9
900
24
Note1.Use M10 screw for the suspension bolt (field supply).
2.Keep the service space for the maintenance at the bottom.
3.This chart indicates for SEZ-KD50VA(L) model,which has 3 fans.
SEZ-KD25,35VA(L) models have 2 fans.
SEZ-KD60,71VA(L) models have 4 fans.
4.In case an inlet duct is used,remove the air filter(supply with
the unit), then install the filter(field supply) at suction side.
17
1
Gas pipe
2
Liquid pipe
W9.52
W12.7
W15.88
W6.35
W9.52
Air filter
664(Lifting bolt pitch)
23
Terminal bed
(Power source)
Lifting plate
(4-14%30)
Bottom plate
550(+1)
510
459 (Lifting bolt pitch)
Control box
80
113
148
55
15
30
15
Air outlet
2X3- :3hole
14
610
150
50
16
14
127
13.5
50
50
Air inlet
582
710
2X12- : 3hole
50X11=550
204.5
(52)
42.5
56.5
301
301
450
(57)
50~
150
Make the access door at the appointed position properly
for service maintenance.
Ceiling surface
300
25
450
Required space for service and maintenance
Access door
5
6- :3hole
500
150
50~
Detailed chart around the air intake duct flange(+3)
(Duct and flange should be supplied in the field.)
5
Refrigerant piping flare connection
(gas :9.52 copper tube):LP
········
Refrigerant piping flare connection
(liquid :6.35 copper tube):HP
········
Drain piping connection R1 (External thread) ········
12
189
9
(When the air intake duct is used)
225(+2)
Note 1. Use M10 screw for the lifting bolt (field supply).
2. Keep the service space for the maintenance from the bottom
when the heat exchanger is cleaned.
3. The direction of air intake can be changed from the bottom to
the rear by attaching the bottom plate to the air intake side.
4. Drain Pan is changeable from right and left.
5. The dimension is changed, in case the optional long-life filter
is attached.
Rear Air-Intake spec. :Depth is increased by 30mm(+1)
Bottom Air-Intake spec. :Height is increased by 30mm(+2)
More than 20mm
18
More than 20mm
The part air intake duct is attached.(+3)
SEZ-KC25VA
Unit : mm
790
SEZ-KA35VA
SEZ-KA50VA
SEZ-KA60VA
SEZ-KA71VA
Unit : mm
42
In case of bottom side suction,
mount the PLATE (A) on the rear side.
930
After installation, remove the
transportation support PLATE (B).
215
120
7%100=700
955
PLATE (B)%2
24-W2.9 holes
27
50
1016
150
Select the either
back side or bottom side.
77
bolt pitch
Service space
(It is necessary to maintain a working
service area from the ceiling.)
40
50
(10)
680
700
Access door
60 38
350
50 Suspension
1000
600
50
+
450
Electrical parts box
Air inlet
(rear side)
150
77.5 100
29
25
12.5
240
(Inlet size)
(Inlet size)
Air inlet (rear side) dimensions
100
7%100=700
880
Air outlet duct flange
9 % 2-W2.9 holes
Air outlet
Refrigerant pipe (gas)
1070
Refrigerant pipe (liquid)
50
Wiring entry
20
25
32.5
(10)
Air inlet
(bottom side)
Access door
Air outlet duct flange
94
25
2%2-W2.9
holes
108
75
270
30
Electrical parts box
1100
+
100
Terminal block
170
(1070)
(Suspension bolt pitch)
20 or more
Suspension bolt pitch
Suspension bolt
M10 or 3/8
(procure locally)
80
350
Select the either back side or bottom side.
Electrical parts box
Drain plug R1 (male)
Air inlet (bottom side) dimensions
PLATE (A)
Models
SEZ-KA35VA
SEZ-KA50VA
7%100=700
120
215
930
(Inlet size)
25
12.5
240
51
39 77.5 100
(Inlet size)
SEZ-KA60VA
SEZ-KA71VA
955
24-W2.9 holes
19
Refrigerant pipe
(liquid)
Refrigerant pipe
(gas)
W6.35mm
W9.52mm
flared connection
1/4"F
W6.35mm
flared connection
1/4"F
W6.35mm
flared connection
1/4"F
W9.52mm
flared connection
3/8"F
flared connection
3/8"F
W12.7mm
flared connection
1/2"F
W15.88mm
flared connection
5/8"F
W15.88mm
flared connection
5/8"F
PLA-RP35BA
PLA-RP50BA
PLA-RP60BA
PLA-RP71BA
PLA-RP71BA2
Unit : mm
Ceiling hole
20~45
860~910
810
90
100
100
90
Cut out hole
620
860~910
Indoor power supply
terminal block(Option part)
Ceiling hole
167
+ +
605 +35
-5
840
Branch duct hole
Suspension bolt pitch
Remote controller
terminal block
Indoor unit/Outdoor unit
connecting terminal block
155
70°
160
(7.5)
100
Suspension bolt pitch
160
Detail connecting of branch duct(Both aspects)
20~45
Fresh air
intake hole
130
20~45
Branch duct hole
350
:175
14-:2.8
Burring hole
Burring hole pitch
:150
Detail drawing of fresh air intake hole
(7.5)
24
1
60
284
Drain pipe
connected to VP-25
377
B
A
+
190
156
105
140
+
Control wire entry
Ceiling
)
Cut out hole
:100
+
Ceiling
In case of standard grille : PLP-6BA / PLP-6BAMD
35
Power supply wire,
Indoor unit/Outdoor unit
connecting wire entry
17 +50
50~70
170
Connect the attached
drain socket.
+
+ +
+
Suspension bolt
lower edge
(
Keep approximately
10 to 15mm space
between unit ceiling
and ceiling slab.
2
+
Burring hole pitch
:125
120°
120°
840
3-:2.8
158
160
Suspension bolt
M10 or W3/8
Burring hole
20~45
187.5
160
D
C
90
150
Cut out hole
MITSUBISHI
ELECTRIC
Grille
597
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
597
Auto vane
(Air outlet)
switch<Cooling>and
Emergency Up/Down switch<Up>
Emergency operation
switch<Heating>and
Emergency Up/Down switch<Down>
Air intake hole
500
Air outlet hole
950
M
In case of Auto-Grille : PLP-6BAJ
In case of wireless remote controller : PLP-6BALM Auto Grille
Air intake grille up/down discharge
Emergency operation
Air intake grille
Receiver
M
83
M
36
500
83
36
Indoor unit
1500mm
or more
1000mm
or more
Indoor unit
3000mm or more
Obstacle
Air intake grille
Vane motor
950
Grille
DEFROST/STAND BY lamp
Operation lamp
Air outlet hole
Ceiling
Ceiling
L.L Filter
MITSUBISHI
ELECTRIC
1800mm or more
from floor
For high
attachment
Note : 1. Please choose the Grille from a standard grille, auto-grille.
2. As for drain pipe, please use VP-25(O.D. :32 PVC TUBE).
Drain pump is included.
Max. lifting height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional
casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions + marked on the figure.
3) The optional high efficiency filter must be used jointly with optional multi-functional
casement.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/water dew.)
8. As for necessary installation/service space, please refer to the left figure.
Models
Floor
PLA-RP35/50BA
PLA-RP60BA
PLA-RP71BA
PLA-RP71BA2
20
Refrigerant pipe
···:6.35
Flared connection
···1/4 inch
Refrigerant pipe
:6.35
Flared connection
1/4 inch
Refrigerant pipe
···:9.52
Flared connection
···3/8 inch
Refrigerant pipe
···:12.7
Flared connection
··1/2 inch
Refrigerant pipe
···:15.88
Flared connection
···5/8 inch
A
B
C
D
E
80
74
241 258 87
85 77
400
Max. 4.0m
Air intake hole
M
PLA-RP50AA
PLA-RP60AA
PLA-RP71AA
Ceiling hole
860 - 910
20 - 45
Fresh air intake
20 - 45
810
Suspension bolt pitch
159
197
W125
Burring hole pitch
158
120"
120"
20 - 45
3 - W2.8
Burring hole
159
16
C
89
Detail drawing of fresh air intake
98
192
W150
159
840
W100
(Cut out hole)
Suspension bolt M10
or W3/8
1
Ceiling surface
Feeding hole
(Drain pump)
286
374
60
860 - 910
Ceiling hole
14 - W2.8
Burring hole
Terminal block
840
W175
Branch duct hole
Suspension bolt pitch
605
350
167
155
159
130
70"
100
90 100 100 90
Branch duct hole
(Cut out hole)
Unit : mm
20 - 45
PLA-RP35AA
Drain pipe
VP-25connection
(O.D.W32)
+5
0
B
+5
0
30
135
Ceiling surface
17
Control wire entry
Power line entry
Suspension bolt lower edge
190
105
140
50 - 70
170
A
2
577
Air intake hole
Air intake grille
17
High efficiency filter
& Fresh air intake casement (option)
Grille
Drain hole
M
A
M
(WIRELESS PANEL)
950
Emergency operation switch (heating)
411
Air outlet hole
Emergency operation switch (cooling)
Auto vane
577
Air intake hole
A
DEFROST/STAND BY lamp
M
Receiver
77
Operation lamp
M
51
411
Air outlet hole
950
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
(Unit : mm)
LIQUID SIDE
GAS SIDE
RP35, 50
RP60
RP71
:6.35
:6.35
—
:9.52
:9.52
:9.52
:12.7
—
—
:15.88
:15.88
:15.88
(Unit : mm)
Models
PLA-RP35,50AA
PLA-RP60,71AA
: Initial flare nut size
21
A
B
C
241
258
80
Vane motor
77
51
Branch
duct hole
1
2
3
4
5
6
7
8
9
Ceiling
461
25
ø1
9
38
38
7
387
18
120°
85
260
2
8
48
233
246
When drain socket
is installed
(Drainage)
2
2
Drainage pipe connection(26mmI.D.)
Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for fresh air intake ø100
Knock out hole for wiring arrangement 2-ø22
Knock out hole for wiring arrangement 2-ø26
Air intake
Accessory···Drain socket (I.D. 26)
Electrical box
138
86
4
Air outlet
878
853
960
917(Suspension bolt pitch)
182
140
62
80
1
In case of the rear pipe arrangement, make sure to
remove the shaded portions from the independent piece.
Then put the independent piece back in initial position.
(The heat exchanger might be clogged because of dust)
75
3
When electrical box
is pulled down
121
24
5
126
2
190
46
76
124
(71)
8
169
37
1
190
Electrical box
84 88
2
85
254
320
195
57
6
680
230
680
22
476
150
18
[FRONT VIEW]
5
10
51
184
(liquid ø6.35)
(gas ø12.7)
When drain socket
is installed
(Drainage)
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the
drain pump (option parts),
refrigerant pipe will be only upward.
246
233
203
PCA-RP50KA
Unit : mm
121
37
190
46
1
2
3
4
5
6
7
8
9
461
25
ø1
9
38
7
387
18
120°
2
8
48
246
233
(Drainage)
When drain socket
is installed
138
85 86
260
2
4
2
Air outlet
1198
1173
1280
1237(Suspension bolt pitch)
182
140
62
80
1
Drainage pipe connection(26mmI.D.)
Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for fresh air intake ø100
Knock out hole for wiring arrangement 2-ø22
Knock out hole for wiring arrangement 2-ø26
Air intake
Accessory···Drain socket (I.D. 26)
Flare nut ø6.35 (RP60 only)
Electrical box
Ceiling
38
24
5
In case of the rear pipe arrangement, make sure to
remove the shaded portions from the independent piece.
Then put the independent piece back in initial position.
(The heat exchanger might be clogged because of dust)
When electrical box
is pulled down
75
169
3
124 76
(71)
2
8
126
1
190
Electrical box
84 88
2
85
254
320
195
57
680
230
680
23
476
150
[FRONT VIEW]
6
5
10
60
179
203
A
B
246
233
71
180
200
(gas ø15.88)
When drain socket
is installed
(Drainage)
(liquid )
236
4 GAS SIDE
ø15.88
:Initial flare nut size
ø9.52
5 LIQUID SIDE ø6.35
RP60
ø9.52
ø15.88
RP71
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the
drain pump (option parts),
refrigerant pipe will be only upward.
51
A
B
PCA-RP60KA
PCA-RP71KA
Unit : mm
18
PCA-RP50GA
Unit : mm
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain pump is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
17
933 (suspension bolt pitch)
85
983
226
157
15
81 76
Electrical box
180
210
70
904
182
1000
gas
241
(Drainage)
254
506
680
56
Air outlet
liquid
201
Air intake
161
90
918
1
2
3
4
5
6
7
8
38
131
46 175
1
38 79
32
Ceiling
161
6~7
42
179
Electrical box [Front view]
Use the current nuts meeting the pipe size of the outdoor unit.
86
138
171
263
352
525
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knockout hole for upper drain pipe arrangement
Knockout hole for left drain pipe arrangement
Knockout hole for wiring arrangement
Available pipe size
LIQUID SIDE
928
(Unit : mm)
RP50
:6.35
:9.52
When electrical
box is pulled
down
GAS SIDE
:12.7
:15.88
: Initial flare nut size
24
PCA-RP50GA2
PCA-RP60GA
PCA-RP71GA
Unit : mm
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain pump is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
17
1240 (suspension bolt pitch)
85
1290
Electrical box
15
226
210
180
81 76
157
70
1214
182
(liquid)
1310
201
(5/8F gas)
241
(Drainage)
254
506
680
56
Air outlet
Air intake
161
90
1228
38
131
161
525
46 175 1
Ceiling
3879
32
[ Front view ]
6~7
42
179
Electrical box
86
138
171
263
416
1
2
3
4
5
6
7
8
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knockout hole for upper drain pipe arrangement
Knockout hole for left drain pipe arrangement
Knockout hole for wiring arrangement
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP50
LIQUID SIDE :6.35
1235
:9.52
GAS SIDE :12.7
:15.88
When electrical
box is pulled
down
: Initial flare nut size
25
RP60
(Unit : mm)
RP71
:6.35
:9.52
:9.52
:15.88
:15.88
PEAD-RP35, 50, 60, 71JA
Unit : mm
2xE-:2.9
Suspension bolt hole
4-14x30 Slot
18
Air
inlet
210
G
Air
outlet
A
B(Suspension bolt pitch)
C
D (Duct)
100x(E-1)=F
15
643 (Suspension bolt pitch)
32
238
10
Terminal block
(Remote controller transmission line)
175±5mm
(Actual length)
217
250
Control box
2×2-:2.9
136
67
356
Drain pipe(O.D.:32)
Terminal block
(Spontaneous draining) (Indoor/Outdoor connecting line)
NOTE 1. Use M10 screw for the Suspension bolt (field supply).
2. Keep the service space for the maintenance at the bottom.
3. This chart indicates for PEAD-RP60•71JA models, which have 2 fans.
PEAD-RP35•50JA models have 1 fan.
4. In case that the inlet duct is used, remove the air filter (supplied with
the unit), then install the filter (field supply) at suction side.
Model
A
B
Gas pipe
D
E
F
G
PEAD-RP35,50JA
900
954 1000 860
9
800
858
PEAD-RP60JA
1100 1154 1200 1060
11
1000 1058
:15.88
PEAD-RP71JA
1100 1154 1200 1060
11
1000 1058
:15.88
Liquid pipe
:12.7
:6.35
Outdoor unit (SUZ): :6.35
Outdoor unit
: :9.52*
:9.52
* Setting at shipment
6
J
Kx(L-1)=M
J
K
More than 20mm
Ceiling surface
112
112
N-:2.9
More than 10mm
C
Drain hose (I.D.:32)
<accessory>
11
1 Refrigerant piping
Flare connection (gas)
Less than 300mm
Less than 700mm
732
700
Drain pipe Drain pump
(O.D.:32)
41
57
178 (Duct)
100
33
23
40
122
2 Refrigerant piping
Flare connection (liquid)
23
10
58
40
57
21
20
30
100
Air Filter
Access door
Q
Make the access door at the appointed position properly for service maintenance.
P
Qx(R-1)=S
Model
PEAD-RP35,50JA
PEAD-RP60,71JA
777
50
H
Note2
Access door
50
250
~30 45
0
0
450 0
30
han
re t
Mo
Required space for service and maintenance
26
H
1000
1200
J
54
49
K
260
330
L
4
4
M
780
990
N
10
10
P
40.5
40
Q
273
340
R
4
4
S
819
1020
PEAD-RP35, 50, 60, 71JAL
Unit : mm
2xE-:2.9
Suspension bolt hole
4-14x30 Slot
210
G
Air
inlet
C
Air
outlet
A
18
B(Suspension bolt pitch)
D (Duct)
100x(E-1)=F
15
21
Terminal block
(Remote controller transmission line)
732
700
32
175±5mm
(Actual length)
217
250
10
33
23
40
122
100
178 (Duct)
643 (Suspension bolt pitch)
57
2 Refrigerant piping
Flare connection (liquid)
23
10
58
40
57 20
30
100
Air Filter
2×2-:2.9
1 Refrigerant piping
Flare connection (gas)
Control box
136
67
356
NOTE 1. Use M10 screw for the Suspension bolt (field supply).
2. Keep the service space for the maintenance at the bottom.
3. This chart indicates for PEAD-RP60•71JAL models, which
have 2 fans. PEAD-RP35•50JAL models have 1 fan.
4. In case of the inlet duct is used,remove the air filter (supplied
with the unit), then install the filter (field supply) at suction side.
Drain pipe(O.D.:32)
Model
Drain hose (I.D.:32)
<accessory>
Terminal block
(Indoor/Outdoor connecting line)
A
B
C
Liquid pipe
Gas pipe
D
E
F
G
PEAD-RP35,50JAL
900
954 1000 860
9
800
858
PEAD-RP60JAL
1100 1154 1200 1060
11
1000 1058
:15.88
PEAD-RP71JAL
1100 1154 1200 1060
11
1000 1058
:15.88
:12.7
:6.35
Outdoor unit (SUZ): :6.35
Outdoor unit
: :9.52*
:9.52
* Setting at shipment
J
J
112
112
Ceiling surface
More than 20mm
More than 10mm
Kx(L-1)=M
K
11
6
N-:2.9
Access door
Q
P
Make the access door at the appointed position properly for service maintenance.
Qx(R-1)=S
Model
777
50
H
Note2
Access door
50
250
~30 45
0
0
re
Mo
450 0
0
n3
tha
Required space for service and maintenance
27
H
J
K
L
M
N
P
Q
R
S
PEAD-RP35,50JAL
1000
54
260
4
780
10
40.5
273
4
819
PEAD-RP60,71JAL
1200
49
330
4
990
10
40
340
4
1020
PEAD-RP35EA2
PEAD-RP50EA
PEAD-RP60EA
A
RP35,50 772
RP60
B
305
1012 280
+ Initial flare nut size
(Unit : mm)
F
G
R410A Outdoor unit : 6.35 + R410A Outdoor unit : 12.7 +
830 804
R407C Outdoor unit : 9.52 R407C Outdoor unit : 15.88
Outdoor unit (SUZ) : 6.35
15.88
290 1070 1044
R407C Outdoor unit : 9.52 +
C
D
E
Service space:500 or more
50~150 29
450
Refrigerant piping flare connection (liquid : F copper tube):HP
Refrigerant piping flare connection (gas :G copper tube):LP
Drain R1(External thread)
Electrical parts box
Drain Pump (Option)
Set
Drain Pipe (Option) ... Flexible joint VP-25(I.D. :32)
Filter
55
Access door
81
C
B
81
197
450
Lifting bolt hole
(14s22)
C
13
277
45 80
85
24
282
288
256
176
Air inlet
7
E
13
D
30
10- :3 (RP35,50)
12- :3 (RP60)
6
40
2
179
1
243
10
35
227
109
10
3.5
21
In case of rear inlet
30
61
4
81
A
44 75
640
30
B
10
18
56
355
365~465
159
1
2
3
4
5
6
7
10- :3 (RP35,50)
12- :3 (RP60)
A
10
Model
Unit : mm
5
Air outlet
3.5
3
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
In case of bottom inlet
10- :3 (RP35,50)
12- :3 (RP60)
Air outlet
40
15
176
256
10
3.5
10
7
81
C
B
81
A
Air inlet
PEAD-RP71EA
Service space:500 or more
F
15.88
55
2
35
1
Air inlet
375
12-:3
44
E
75
D
243
6
5
7
Air outlet
4
3
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
28
B
81
10
C
A
13
307
45 122
113
53
81
80
30
10
680
B
365~465
323
308
169
20
30
C
Lifting bolt hole
(14x22)
81
210
7
140
6
282
5
3.5
30
4
40
3
Refrigerant piping flare connection (liquid :9.52 copper tube):HP
Refrigerant piping flare connection (gas :F copper tube):LP
Drain R1 (External thread)
Electrical parts box
Drain Pump (Option)
Set
Drain Pipe (Option) ... Flexible joint VP25(I.D.:32)
Filter
319
261
181
2
3.5
1
12-:3
A
81
197
450
Access door
10
(Unit : mm)
A
B
C
D
E
Model
RP71 1012 280 290 1070 1044
+ Initial flare nut size
50~150 29
450
13
30
PEAD-RP60GA
PEAD-RP71GA
Unit : mm
(Unit : mm)
J
Model
A
B
C
D
E
F
G
H
RP60
1125
1090
1050
1012
7
840
8
Outdoor unit(SUZ) : 6.35
Other outdoor unit : 9.52 +
15.88
RP71
1125
1090
1050
1012
7
840
8
9.52
15.88
+ Initial flare nut size
29
PEA-RP71EA
Unit : mm
Refrigerant-pipe flared
connection :9.52(3/8)
Drainage pan connection R1
70 40
672 (Drainage pan)
11
Refrigerant-pipe flared
connection :15.88(5/8)
11
Wiring entry(2-:22holes)
Service panel
(Condenser/evaporator
temperature thermistor)
105
510
35
20
345
Electrical parts box
Room temperature thermistor
24.5
(130)
12-:2.9 holes
For air outlet
duct connection
530
690
200
200
Terminal
block
70
25
40
4-12 30
oblong
Suspension
bolt holes
125
125
15
35
Heat insulator t10
25
25
40
650
Air outlet duct flange Air outlet
730
Mounting plate
300
220
3.2
120
242
14
Heat insulator t10
600
Service space (opening) in the ceiling
Air intake
70
(530)
900
300
100
Air outlet
30
145
175
55
50
45
14-:2.9 holes
For air intake
duct connection
145
11
22.5
562 (Drainage pan)
155
90
155
(10)
339
21
155
22.5
20
20
15
265
690
15
20
250
75 60
418
Air intake
Air intake duct flange
15
Service panel
(Room temperature
thermistor)
85 85
25
381
(10)
Unit: mm
OUTDOOR UNIT
SUZ-KA25VA SUZ-KA25VAH
SUZ-KA35VA SUZ-KA35VAH
Drain hole :42 (SUZ-KA25/KA35VA)
Drain hole :33 (SUZ-KA25/KA35VAH)
Bolt pitch for
installation
304~325
44
17.5
40
2 holes 10X21
Service panel
Air out
22.3
23
Liquid refrigerant pipe joint
Refrigerant pipe (flared) :6.35
Handle
35
69
302.5
170.5
Service port
500 Bolt pitch for installation
800
REQUIRED SPACE
Basically open 100mm or more
without any obstruction in front
and on both sides of the unit.
ore
or m
m
m
100
100
mm
or m
ore
mm
200
Gas refrigerant pipe joint
Refrigerant pipe (flared) :9.52
99.5
10
164.5
280
150
ore
or m
350
mm
or m
ore
Open two sides of left,
right, or rear side.
31
43
285
Air in
550
344.5
400
Air in
SUZ-KA50VA
SUZ-KA60VA
SUZ-KA71VA
Unit: mm
Drain holes :33
515
299
40
360
330
51
34
66
500
840
121
80
Service panel
155
90
35
30
430
850
Liquid refrigerant
pipe joint
Refrigerant pipe(flared)
:6.35·····(SUZ-KA50/KA60VA)
:9.52·····(SUZ-KA71VA)
198
REQUIRED SPACE
Open as a rule
500mm or more if
the front and both
sides are open
100mm or more
Open as a rule
500mm or more if the back,
both sides and top are open
100mm or more
200mm or more if
there are obstacles
to both sides
350mm or more
32
Gas refrigerant
pipe joint
Refrigerant pipe(flared)
:12.7·····(SUZ-KA50VA)
:15.88···(SUZ-KA60/KA71VA)
Unit : mm
WIRED REMOTE CONTROLLER
19.5
43.5
120
130
33
Unit : mm
WIRELESS REMOTE CONTROLLER
SLZ-KA25/35/50VAL
SEZ-KC25,KA35/50/60/71VA(Option)
57
17.5
h
140
ON/OFF
AUTO COOL
HEAT DRY
TOO
WARM
TOO
COOL
FAN
SELECT
VANE
TIME
MODE
RESET
Installation area
• Area in which the remote controller is not exposed to direct sunshine
• Area in which there is no heating source nearby
• Area in which the remote controller is not exposed to cold (or warm) winds
• Area in which the remote controller can be operated easily
• Area in which the remote controller is beyond the reach of children
Installation method
Attach the remote controller holder to the desired location using two tapping screws.
Place the lower end of the controller into the holder.
Wireless remote controller (Accessory)
Wall
Remote controller holder (Accessory)
Fixing screw (Accessory)
• The signal can travel up to approximately 7 meters (in a straight line) within 45
degrees to both right and left of the center line of the receiver.
In addition, the signal may not be received if there are interferences of fluorescent
lights or strong sunlight.
34
Unit : mm
WIRELESS REMOTE CONTROLLER
159.3
58
19
55
35
4
WIRING DIAGRAM
MFZ-KA25VA
MFZ-KA35VA
MFZ-KA50VA
INDOOR UNIT
DISP REC
P.C.BOARD
MV1 ML1 MV2 ML2
2
1
CN
2
106
3 CN113
4
RT15
1
2
3
CN112
4
5
6
RT12
RT13
RT14
RT11
CN
111
LS1
CN
1X1
LS2
CN
1Y1
230V~
TB
TO OUTDOOR
UNIT
CONNECTING 12-24V
S1
S2
S3
BLK
WHT
WHT
RED
6
CN
125
5
5
5
CN
151
MF1
MF2
5
5
5
1
2
3
4
5
6
1
2
3
4
5
6
CN
152
CN211
CN212
F11
DB111
T11
NR11
3
2 CN201
1
3
2 CN202
1
LD103
INDOOR ELECTRONIC
CONTROL P.C. BOARD
GRN
[LEGEND]
SYMBOL
DB111
NAME
SYMBOL
NAME
SYMBOL
NAME
DIODE STACK
ML2
DAMPER LOCK MOTOR (LEFT)
RT14
INDOOR COIL THERMISTOR (MAIN 2)
TR15
INDOOR COIL THERMISTOR (MAIN 3)
F11
FUSE (T3.15AL250V)
MV1
HORIZONTAL VANE MOTOR
LS1
DAMPER LIMIT SWITCH (OPEN)
MV2
DAMPER MOTOR
NR11
VARISTOR
LS2
DAMPER LIMIT SWITCH (CLOSE)
MF1
UPPER INDOOR FAN MOTOR
RT11
ROOM TEMPERATURE THERMISTOR
MF2
LOWER INDOOR FAN MOTOR
RT12
INDOOR COIL THERMISTOR (MAIN 1)
ML1
DAMPER LOCK MOTOR (RIGHT)
RT13
INDOOR COIL THERMISTOR (SUB)
NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate :
/: Terminal block,
: Connector
36
T11
TRANSFORMER
SLZ-KA25VAL SLZ-KA25VA
SLZ-KA35VAL SLZ-KA35VA
SLZ-KA50VAL SLZ-KA50VA
GRILLE
TB4
S1
GRY
7
PINK
8
5
7
WHT
9 (FAN)
FAN
1
1
X1
ORN
3 (POWER)
CND
1
I.B
BLU
ORN
BLU
RED
WHT
RED
YLW
1
RED
3 (POWER
1
BOARD)
CNDK
FUSE
TRANS
3
BLU
(CONTROL)
CN3C
DC13.1V
1 2 CN2S(WHT)
X6 X5 X4
ZNR
X7
X6 X5 X4
X7
SW1
SW2
GRN
(VANE)
CN6V
5
4
5
6
VLT
3
7
8
9
1
2
BLK
RED
(2 PHASE) (INTAKE)
CN29
CN20
1
2
1
2
3
MODELS
LED2
WHT
(LIQUID)
CN21
1
2
SKYBLU
See fig:+1
2
WHT
(DRAIN)
CN31
GRY
1
BRN
REMOTE
CONTROLLER
CN90
(WIRELESS)
WHT
6
PINK
5
BLU
4
RED
3
YLW
2
ORN
1
RED
CN41
BLU
CN51
YLW
ORN
12345
CN32
W.R
<fig:+1>
LED1
CN2L
WHT
ON
OFF
RU
WHT
LED3
12345
SW2
BLK
WHT
(POWER 1
BOARD)
2
CN2D
X1
SW3
SWE
ON
ON
OFF
OFF
BLU
(REMOCON)
CN22
1
2
SW2
KA25
ON
OFF
KA35
ON
OFF
KA50
ON
OFF
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
BLU
LED1
BLU
SKY BLU
3
BLU
3 (D·U·M)
CNP
9
LED2
VLT
6
BZ
BLU
5
CNB
1
1 2 3 AC220-240V
CNSK(RED)
4
YLW
9
2 3
ORN
W.B
RED
3 (D·HEATER)
CNC
3
YLW
YLW
RED
1
RED
YLW
9
C1
BRN
BRN
H2
P.B
1
ORN
BLU
YLW
DP
WHT
YLW
5 10 8
5
MF
7 4
RED
6
ORN
5
5
BLK
5
TO OUTDOOR UNIT
S3
3
MV
YLW
2
MV
WHT
1
MV
S2
BLU
5
YLW
MV
* Case of wired model
9
TB15
1
2
DS
SYMBOL
SYMBOL
NAME
INDOOR POWER BOARD
W.B
TO MA-REMOTE
} CONTROLLER
DC8.7-13V
NAME
WIRELESS REMOTE CONTROLLER BOARD
INDOOR CONTROLLER BOARD
RU
RECEIVING UNIT
CN2L
CONNECTOR(LOSSNAY)
BZ
BUZZER
CN32
CONNECTOR(REMOTE SWITCH)
LED1
LED(RUN INDICATOR)
CN41
CONNECTOR(HA TERMINAL-A)
LED2
LED(HOT ADJUST)
CN51
CENTRALLY CONTROL
SW1
SWITCH(HEATING ON/OFF)
FUSE
FUSE(T6.3AL250V)
SW2
LED1
POWER SUPPLY(I.B)
C1
CAPACITOR(FAN MOTOR)
LED2
POWER SUPPLY(I.B)
DP
DRAIN PUMP
LED3
TRANSMISSION(INDOOR-OUTDOOR)
DS
DRAIN SENSOR
SW2
SWITCH(CAPACITY CODE)
H2
DEW PREVENTION HEATER
SW3
SWITCH(MODE SELECTION)
MF
FAN MOTOR
SWE
SWITCH(EMERGENCY OPERATION)
MV
VANE MOTOR
X1
DRAIN PUMP/DEW PREVENTION HEATER
X4
RELAY(FAN MOTOR LL)
X5
RELAY(FAN MOTOR Lo)
X6
RELAY(FAN MOTOR Hi)
X7
RELAY(FAN MOTOR Me)
ZNR
VARISTOR
I.B
TH2
* Case of wireless model
[LEGEND]
P.B
TH5
TH1
TB4
TB15
TH1
TH2
TH5
SWITCH(COOLING ON/OFF)
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP.THERMISTOR
(0/15kΩ, 25/5.4kΩ DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0/15kΩ, 25/5.4kΩ DETECT)
COND./EVA.TEMP.THERMISTOR
(0/15kΩ, 25/5.4kΩ DETECT)
Notes:
1. SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
+ For details on how to operate self-diagnosis, refer to the service manuals etc.
37
SEZ-KD25VA(L)
SEZ-KD35VA(L)
SEZ-KD50VA(L)
SEZ-KD60VA(L)
SEZ-KD71VA(L)
INSIDE SECTION OF CONTROL BOX
TB15
1
2
TO MA REMOTE
CONTROLLER
I.B.
;For SEZ-KD • VA
SW1
1
SW2
CN32
CN01
(Black)
3
CN3C (Blue)
CN41
CN51
DC310~340V
Rectify circuit
ZNR01
L1:only
SEZ-KD71VA(L)
FUSE
U
LED2
LED3
L1
LED1
CN90
5
U
CN22 (Blue)
ON OFF
SWE
3
ZNR02
12
CN2L
1
DSA
CN44
CN4F
123456789
34
123456789
1234
CN20 (Red)
1234
12
X1
CNMF
7654
1
3
1 CNP
(Blue)
W.B.
CN4F
TB4
S1
S2
CN1
S3
LED1
BZ1
RU
RECEIVER
SW1
SW2
;For SEZ-KD • VAL
t°
FS
t°
TH2
t°
TH5
M
1~
M
TH1
Fan motor
Optional Parts
Drainpump
Optional Parts
SYMBOL EXPLANATION
SYMBOL
I.B.
SYMBOL
NAME
INDOOR CONTROLLER BOARD
W.B.
NAME
WIRELESS REMOTE CONTROLLER BOARD
FUSE AC250V 6.3A
RU
RECEIVING UNIT
ZNR01,02
VARISTOR
BZ1
BUZZER
DSA
ARRESTER
LED1
LED (RUN INDICATOR)
X1
AUX. RELAY
SW1
SWITCH (HEATING ON/OFF)
CN2L
CONNECTOR (LOSSNAY)
SW2
CN32
CONNECTOR (REMOTE SWITCH)
TH1
INTAKE AIR TEMP. THERMISTOR
CN41
CONNECTOR (HA TERMINAL-A)
TH2
PIPE TEMP. THERMISTOR/LIQUID
CN51
CONNECTOR (CENTRALLY CONTROL)
TH5
COND. /EVA. TEMP. THERMISTOR
LED1
POWER SUPPLY(I.B.)
L1
AC REACTOR(POWER FACTOR IMPROVEMENT)
LED2
POWER SUPPLY(I.B.)
FS
FLOAT SWITCH
LED3
TRANSMISSION(INDOOR-OUTDOOR)
SW1
SWITCH (FOR MODE SELECTION)
TB4
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
SW2
SWITCH (FOR CAPACITY CODE)
SWE
CONNECTOR (EMERGENCY OPERATION)
TB15
TERMINAL BLOCK
(REMOTE CONTROLLER TRANSMISSION LINE)
FUSE
SWITCH (COOLING ON/OFF)
NOTE) 1. Since the outdoor side electric wiring may change,be sure to check the outdoor unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have polarities, make sure to match terminal numbers(S1,S2,S3) for correct wirings.
3. Symbols used in wiring diagram above are,
:Connector,
:Terminal Block.
38
TO
OUTDOOR
UNIT
39
INDOOR CONTROLLER BOARD
I.B.
RELAY (FAN MOTOR Lo)
RELAY (FAN MOTOR HI)
X5
X6
ZNR VARISTOR
RELAY (FAN MOTOR LL)
X4
SWE SWITCH (EMERGENCY OPERATION)
SW3 SWITCH (MODE SELECTION)
SW2 SWITCH (CAPACITY CODE)
LED3 TRANSMISSION (INDOOR-OUTDOOR)
LED2 POWER SUPPLY (I.B.)
LED1 POWER SUPPLY (I.B.)
FUSE FUSE (6.3A)
CN90 CONNECTOR (WIRELESS)
CN51 CENTRALLY CONTROL
CN41 CONNECTOR (HA TERMINAL-A)
TH5
TH2
TH1
TB15
X4
CN90
(0°C/15kΩ. 25°C/5.2kΩ DETECT)
COND./EVA. TEMP. THERMISTOR
(0°C/15kΩ. 25°C/5.2kΩ DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0°C/15kΩ. 25°C/5.2kΩ DETECT)
INTAKE AIR TEMP. THERMISTOR
TRANSMISSION LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TH1
RED
(INTAKE)
CN20
1 2
BLU
(REMOCON)
CN22
1 2
LED1
WHT
(POWER 1
BOARD) 2
CN2D
WHT
(LIQUID)
CN21
1 2
TH2
I.B.
1 3
BLU
(CONTROL)
CN3C
LED2
1 3 ORN
(POWER)
CND
TB15
1
2
TB4
S1
S2
S3
TO MA-REMOTE
CONTROLLER
DC8.7-13V
1 2 DC13.1V
CN2S(WHT)
TRANS
1 2 3 AC220-240V
CNSK(RED)
P.B.
TO OUTDOOR UNIT
NOTE:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
4. The wiring between MA-REMOTE CONTROLLER and TB15 is included in the package.
TH5
BLK
(2 PHASE)
CN29
1 2
ZNR
FUSE
LED3
RED
1 3
(POWER BOARD)
CNDK
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
FAN MOTOR
TB4
X4
X5
NAME
CN41
MF
CN51
X5
CAPACITOR (FAN MOTOR)
CN32
CN2L
X6
C
SYMBOL
12345
SW2
CN32 CONNECTOR (REMOTE SWITCH)
CN2L CONNECTOR (LOSSNAY)
INDOOR POWER BOARD
NAME
ON
OFF
SWE
SW3
ON
ON
OFF
OFF
1
12345
X6
WHT
1 2 3 4 5 6 7 (FAN)
FAN
7 6 5 4 3 2 1
7 6 5 4 3 2 1
INSERT
C
MF
BLU
7 6 5 4 3 2 1
P.B.
SYMBOL
[LEGEND]
The motor connector is
connected with 230V, 240V
power at factory shipment.
If 220V power is used,
Insert the attachment.
Color/Power source
WHT/230,240V
BLU/220V
SEZ-KC25VA
SEZ-KA35VA
SEZ-KA50VA
SEZ-KA60VA
SEZ-KA71VA
MF
TB4
BRN
3
4
5
6
7
8
1
2
3
4
5
6
7
8
BLU
2
YLW
TO OUTDOOR
UNIT
S3
1
ORN
C1
BLU
YLW
BLK
RED
ORN
WHT
S1
S2
RED
P.B
3
4
5
6
7
WHT
(FAN)
FAN
ORN
BLU
3
BLU
1
RED
WHT
2
RED
BRN
BLU
BLK
1
WHT
1 2 3 AC220-240V
CNSK(RED)
RED
1
(POWER
BOARD)
CNDK
FUSE
ORN
(POWER)
CND
3
1
I.B
TRANS
3
BLU
(CONTROL)
CN3C
1 2 DC13.1V
CN2S(WHT)
X6
X6
WHT
(POWER
BOARD)
CN2D
X4
SW3
1
2
BLK
WHT
LED3
12345
LED1
CN2L
BLK
RED
(2 PHASE) (INTAKE)
CN20
CN29
12345
CN32
CN51
CN41
CN90
1
2
1
2
See fig:+1.
LED2
WHT
(LIQUID)
CN21
1
2
BLU
(REMOCON)
CN22
1
2
BLU
ON
OFF
SW2
ON
OFF
X5
ZNR
X4
BLU
SWE
ON
OFF
X5
TB15
[LEGEND]
1
SYMBOL
SYMBOL
NAME
P.B
INDOOR POWER BOARD
C1
I.B
INDOOR CONTROLLER BOARD
MF
CN2L CONNECTOR(LOSSNAY)
TB4
CN32 CONNECTOR(REMOTE SWITCH)
TB15
CN41 CONNECTOR(HA TERMINAL-A)
CN51 CENTRALLY CONTROL
TH1
CN90 CONNECTOR(WIRELESS)
FUSE FUSE(T6.3AL250V)
TH2
LED1 POWER SUPPLY(I.B)
LED2 POWER SUPPLY(I.B)
TH5
LED3 TRANSMISSION(INDOOR-OUTDOOR)
SW2 SWITCH(CAPACITY CODE)
SW3 SWITCH(MODE SELECTION)
SWE SWITCH(EMERGENCY OPERATION)
RELAY(FAN MOTOR LL)
X4
RELAY(FAN MOTOR Lo)
X5
X6
RELAY(FAN MOTOR Hi)
ZNR VARISTOR
NAME
2
TH5
CAPACITOR(FAN MOTOR)
TH1
TH2
FAN MOTOR
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
<fig:+1>
MODELS
ROOM TEMP.THERMISTOR
(0/15kΩ,25/5.4kΩ DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0/15kΩ,25/5.4kΩ DETECT)
COND./EVA.TEMP.THERMISTOR
(0/15kΩ,25C/5.4kΩ DETECT)
SW2
KA35
ON
OFF
KA50
ON
OFF
KA60
ON
OFF
KA71
ON
OFF
12345
12345
12345
12345
Notes:
1. SymboIs used in wiring diagram above are,
: Connector,
: Terminal (block).
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4. Since the indoor fan motor(MF) is connected with 50Hz power, if 60Hz power is used, change the wiring connection shown in fig:+2.
<fig:+2>
Indoor Fan Motor(MF)
for 60Hz
BLUE
50
YELLOW
60
BLUE
+For details on how to operate self-diagnosis, refer to the service manuals etc.
40
}
TO MA-REMOTE
CONTROLLER
DC8.7-13V
PLA-RP35BA
PLA-RP50BA
PLA-RP60BA
PLA-RP71BA
PLA-RP71BA2
<Table 1> SW1 (MODEL SELECTION)
[LEGEND]
SYMBOL
I.B
CN2L
CN32
CN41
CN51
FUSE
LED1
LED2
LED3
SW1
SW2
SWE
X1
DCL
DP
FS
MF
MV
NAME
INDOOR CONTROLLER BOARD
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
FUSE (T6.3AL250V)
POWER SUPPLY (I.B)
POWER SUPPLY (R.B)
TRANSMISSION (INDOOR-OUTDOOR)
SWITCH (MODEL SELECTION) +See table 1
SWITCH (CAPACITY CODE) +See table 2
CONNECTOR (EMERGENCY OPERATION)
RELAY (DRAIN PUMP)
REACTOR
DRAIN PUMP
DRAIN FLOAT SWITCH
FAN MOTOR
VANE MOTOR
SYMBOL
TB4
NAME
TERMINAL BLOCK (INDOOR/OUTDOOR
CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP. THERMISTOR
(0 / 15k, 25 / 5. 4k DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0 / 15k, 25 / 5. 4k DETECT)
COND. / EVA. TEMP. THERMISTOR
(0 / 15k, 25 / 5. 4k DETECT)
TB5,TB6
TH1
TH2
TH5
OPTION PART
W.B
BZ
LED1
LED2
RU
SW1
SW2
SW1
SETTING
MODELS
PLA-RP·BA
1 2 3 4 5
PLA-RP71BA2
1 2 3 4 5
ON
OFF
ON
OFF
<Table 2> SW2 (CAPACITY CODE)
SW2
CAPACITY
SETTING
1 2 3 4 5
35
PCB FOR WIRELESS REMOTE CONTROLLER
BUZZER
LED (OPERATION INDICATION : GREEN)
LED (PREPARATION FOR HEATING : ORANGE)
RECEIVING UNIT
EMERGENCY OPERATION (HEAT / DOWN)
EMERGENCY OPERATION (COOL / UP)
1 2 3 4 5
50
1 2 3 4 5
60
1 2 3 4 5
71
ON
OFF
ON
OFF
ON
OFF
ON
OFF
The black square (■) indicates a switch position.
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
Refer to tables 1 and 2.
TRANSMISSION
WIRES
DC12V
2 1
TB6
VANE CNV(WHT)
SW1
20 18 16 14 12 10 8 6 4 2
J41 J42
SW2
19 17 15 13 11 9 7 5 3 1
CN32
(WHT) 1
CN51(WHT)
Pair No.
5
CN2L
LED3
3
1
3
AUTO GRILLE
CN3G 1
(BLK)
WIRELESS
CN90
(WHT)
9
5
5
M
M
M
M
MV
MV
MV
MV
GRILLE
LED2
1
4
4
CNB
LED1
2 1
OUTDOOR 1 3 5
CN01
3
INDOOR/OUTDOOR
COMMUNICATION
CN3C
1
CN41(WHT)
4
(BLU)
1 2
REMOCON
CN22
1
SWE
BZ
SW1
LED2
SW2
LED1
RU
I-SEE
SENSOR
1
6
MT
I-SEE SENSOR
CORNER PANEL
(OPTION PART)
1
4
4
1 2
t°
t°
TH2 TH5
t°
TH1
1
FUSE
DC325V
RECTIFICATION
(BLU)
7
FAN
CNMF
(WHT)
4
MS
3
5
M
3 1
(BLK)
1 3
ON OFF
AUTO GRILLE
I-SEE
FLOAT SW LIQUID/PIPE INTAKE
POWER
I-SEE SENSOR SENSOR MOTOR
CN4F
CN44
CN20
CNAC
CN4Y
CN6Y
(WHT)
(WHT)
(RED)
(WHT)
(WHT)
(RED)
9
5
YLW
R.B
I.B
5
DCL
TB5
2
1
FS
U.B
3
1
CN3G
5 3 1
CN3A
X1
1
1 D.U.M
3
CNP
(BLU)
YLW
ORN
TB4
YLW S1
ORN S2
S3
TO OUTDOOR
UNIT
ORN
BRN
M
3~
1~
MF
DP
+ Be sure to turn off the power source
and then disconnect fan motor connector.
(Failure to do so will cause trouble in fan motor.)
AUTOMATIC FILTER ELEVATION PANEL
(OPTION PART)
W.B
Notes:
1.SymboIs used in wiring diagram above are,
:Connector,
: Terminal (block).
2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed
system for power and signal.
+ :For power supply system of this unit, refer to the caution label located near this diagram.
41
PLA-RP35AA
[LEGEND]
SYMBOL
P.B
I.B
FUSE
ZNR
BCR
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
X1
X4
SW1
SW2
SWE
C
PLA-RP50AA
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE(T6.3AL250V)
VARISTOR
FAN CONTROL ELEMENT
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
POWER SUPPLY(I.B)
POWER SUPPLY(I.B)
TRANSMISSION(INDOOR-OUTDOOR)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
SWITCH(MODEL SELECTION) See table 1
SWITCH(CAPACITY CODE) See table 2
CONNECTOR(EMERGENCY OPERATION)
CAPACITOR(FAN MOTOR)
PLA-RP60AA
SYMBOL
MF
MV
H2
DP
DS
TB4
PLA-RP71AA
NAME
SYMBOL
NAME
FAN MOTOR
W.B
WIRELESS REMOTE CONTROLLER BOARD
VANE MOTOR
RU
RECEIVING UNIT
DEW PREVENTION HEATER
BZ
BUZZER
DRAIN PUMP
LED1 LED(RUN INDICATOR)
DRAIN SENSOR
LED2 LED(HOT ADJUST)
SW1
SWITCH(HEATING ON/OFF)
TERMINAL BLOCK (INDOOR/
OUTDOOR CONNECTING LINE)
SW2
SWITCH(COOLING ON/OFF)
TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
ROOM TEMP.THERMISTOR
Please set the voltage using the
(0°C/15kΩ,25°C/5.4kΩ DETECT)
remote controller.
For the setting method, please refer to
PIPE TEMP.THERMISTOR/LIQUID
the indoor unit Installation Manual.
(0°C/15kΩ,25°C/5.4kΩ DETECT)
COND./EVA. TEMP. THERMISTOR
(0°C/15kΩ,25°C/5.4kΩ DETECT)
WIRED REMOTE CONTROLLER BOARD
TB5, TB6
TH1
TH2
TH5
R.B
GRILLE
MV
MV
5
MV
5
MV
5
5
H2
5
MF
CN2S
(WHT)
2
1
1 2 3 6 7 4 8 9 5 10
1 2 3
CNSK
(RED)
P.B
3
2
1
DC
13.1V
TB4
YLW S1
ORN S2
ORN
S3
BRN
TO OUTDOOR
UNIT
5
1 2 3
DP
X4
BCR
X4 X1
D.HEATER 1 3
1 3
CNC(RED)
POWER
CNDK
(RED)
BRN
ORN
BLK
WHT
YLW
ORN
RED
WHT
D.U.M 1 3
CNP
(BLU)
YLW
YLW
YLW
YLW
FAN 1 3 5
(WHT)
I.B
VANE
1 3 POWER 1 2
1 3
CND POWER INDOOR/OUTDOOR CN6V
(GRN)
(ORN) CN2D
COMMUNICATION
(WHT)
CN3C
(BLU)
CN51
CN41 CN2L
ZNR
FUSE
RED
WHT
BLK
C
X1
CN32
SW2
SW1
DS
Refer to tables 1
and 2.
LIQUID
CN21
(WHT)
1 2
PIPE
CN29
(BLK)
1 2
TH1
2
1
BZ
9
REMOCON
CN22 WIRELESS
(BLU)
CN90
(WHT)
1 2
BLU
BLU
SWE
ON
OFF
LED3 LED2 LED1
HEATER D.SENSOR INTAKE
CN31
CN20
CN24
(WHT)
(RED)
(YLW)
1 2 3
1 2
W.B
LED2
LED1
SW1
SW2
CNB
R.B
TB5
1 2
TB6
TRANSMISSION WIRES
DC12V
TH2
RU
TH3
Table 1
Notes:
SW1
1. SymboIs used in wiring diagram above are,
: Connector,
MODELS
Service board
: Terminal (block).
1 2 3 4 5
ON
PLA-RP.
AA
2. Indoor and outdoor connecting wires have poIarities, make sure to match
OFF
terminal numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor
unit electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V),
adopting superimposed system of power and signal.
Table 2
MODELS
SW2
Service board
PLA-RP35AA
PLA-RP50AA
PLA-RP60AA
PLA-RP71AA
42
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
PCA-RP50KA
PCA-RP60KA
PCA-RP71KA
[ LEGEND]
SYMBOL
I.B
CN2L
CN32
CN41
CN51
FUSE
LED1
LED2
LED3
SW1
SW2
SWE
X1
R.B
DCL
MF
MV
NAME
INDOOR CONTROLLER BOARD
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
FUSE (T6.3AL250V)
POWER SUPPLY (I.B)
POWER SUPPLY (R.B)
TRANSMISSION (INDOOR-OUTDOOR)
SWITCH (MODEL SELECTION) + See table 1
SWITCH (CAPACITY CODE) + See table 2
CONNECTOR (EMERGENCY OPERATION)
RELAY (DRAIN PUMP)
WIRED REMOTE CONTROLLER BOARD
REACTOR
FAN MOTOR
VANE MOTOR
SYMBOL
TB4
TB5,TB6
NAME
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP. THERMISTOR
(0°C / 15kΩ, 25°C / 5. 4kΩ DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0°C / 15kΩ, 25°C / 5. 4kΩ DETECT)
COND. / EVA. TEMP. THERMISTOR
(0°C / 15kΩ, 25°C / 5. 4kΩ DETECT)
TH1
TH2
TH5
OPTIONAL PARTS
W.B
BZ
LED1
LED2
RU
SW1
SW2
DP
FS
PCB FOR WIRELESS REMOTE CONTROLLER
BUZZER
LED (OPERATION INDICATION : GREEN)
LED (PREPARATION FOR HEATING : ORANGE)
RECEIVING UNIT
EMERGENCY OPERATION (HEAT / DOWN)
EMERGENCY OPERATION (COOL / UP)
DRAIN PUMP
DRAIN FLOAT SWITCH
Refer to tables 1 and 2
DCL
TB5
2
1
TRANSMISSION
WIRES
DC12V
2 1
TB6
YLW
R.B
I.B
VANE CNV (WHT)
SW1
20 18 16 14 12 10 8 6 4 2
J41 J42
SW2
19 17 15 13 11 9 7 5 3 1
Pair No.
CN32
(WHT) 1
5
CN2L
LED3
LED2
2 1
LED1
3
1
CN41 (WHT)
4
1 2
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
REMOCON
CN22
(BLU)
1
SWE
OUTDOOR 1 3 5
CN01
(BLK)
1 3
CN51 (WHT)
DC311~339V
RECTIFICATION
ON OFF
1
WIRELESS
CN90
(WHT)
9
FLOAT SW
CN4F
(WHT)
1
LIQUID/PIPE INTAKE
CN44
CN20
(WHT)
(RED)
4
4
1 2
t°
t°
TH2 TH5
t°
TH1
1
FUSE
7
FAN
CNMF
(WHT)
4
MS
9
CNB
5
M
MV
BZ
SW1
LED2
SW2
LED1
RU
W.B
(OPTIONAL PARTS)
When attaching
drain pump
(optional parts),
remove the jumper
connector CN4F
and fit the drain
float switch (FS).
When attaching
drain pump
(optional parts)
FLOAT SW
CN4F
(WHT)
1
3~
YLW
ORN
X1
1
1 D.U.M
3
TB4
YLW S1
ORN S2
S3
TO OUTDOOR
UNIT
ORN
BRN
CNP
(BLU)
M
1~
DP
MF
(OPTIONAL PARTS)
+Be sure to turn off the source power
and then disconnect fan motor connector.
(Failure to do so will cause trouble in Fan motor)
4
FS
<Table 1> SW1
(MODEL SELECTION)
SW1
Service
1 2 3 4 5
<Table 2> SW2 (CAPACITY CODE)
SW2
MODELS
Service
PCA-RP50KA
ON
OFF
PCA-RP60KA
PCA-RP71KA
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
The black square (■) indicates a switch position.
Notes: 1.
2.
3.
4.
SymboIs used in wiring diagram above are,
:Connector,
:Terminal (block).
Indoor and outdoor connecting wires are made with poIarities, make wiring matching terminal numbers (S1, S2, S3).
Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system
for power and signal.
+ : For power supply system of this unit, refer to the caution label located near this diagram.
43
PCA-RP50GA
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
SWITCH (MODEL SELECTION) See Table 1.
SWITCH (CAPACITY CODE) See Table 2.
SWITCH(EMERGENCY OPERATION)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
FAN CONTROL ELEMENT
POWER SUPPLY(I.B)
POWER SUPPLY(R.B)
TRANSMISSION(INDOOR-OUTDOOR)
CAPACITOR(FAN MOTOR)
PCA-RP60GA
SYMBOL
MF
MV
DP
DS
TB4
TB5,TB6
TH1
TH2
TH5
R.B
P.B CNDK
(RED)
1 2 3
(OPTION)
C
THERMAL FUSE(98˚C10A:50GAH/117˚C16A:100GAH
110˚C16A:60,71,125,140GAH)
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
H1
26H
88H
1
2
BRN
ORN
YLW
ORN
RED
WHT
SW1
D.SENSOR INTAKE LIQUID PIPE
CN31
CN20 CN21
CN29
(WHT)
(RED) (WHT) (BLK)
1 2 3
BLK
BLK
Refer to tables 1
and 2 for service PCB.
When installing optional
drain pump, disconnect
the CN31 jumper connector
and replace it with the
drain sensor (DS).
CN31
DRAIN SENSOR
(WHT) 1 2 3
When installing drain pump
(Optional part).
DS
1 2
1 2
REMOCON
CN22
(BLU)
1 2
1 2
1 2
50~71 TYPE
6
6
6
TH2
100~140 TYPE
5
5
MV
9
CNB
RU
RECEIVER LED1 LED2 SW2 SW1
W.B
2
1
TRANSMISSION WIRES DC12V
TB5
TH1
MV
MV
BZ
1 2
BLU
BLU
SW2
D.U.M 1 3 POWER 1 3 POWER 1 3
1 2
1 3 VANE
CND
CNDK
CNP
6
INDOOR/OUTDOOR CN6V
POWER
(ORN)
(RED)
(BLU)
(
)
CN2D(WHT) COMMUNICATION GRN
CN3C(BLU)
X4
X1
CN41
CN2L WIRELESS
ZNR
CN90
CN51
CN32 (WHT)
X4
X1
LED3 LED2 LED1
BLK
BLK
BCR
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
FUSE
FAN 1 3 5
(WHT)
SWE
ON
OFF
NAME
WIRELESS REMOTE CONTROLLER BOARD(OPTION)
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR)
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
DP
RED
WHT
BLK
I.B
SYMBOL
W.B
RU
BZ
LED1
LED2
SW1
SW2
HEATER
FS1,2
Please set the voltage using the remote
controller.
For the setting method, please refer to
the indoor unit Installation Manual.
CN2S
(WHT)
1
2 DC13.1V
3
MF
PCA-RP71GA
NAME
FAN MOTOR
VANE MOTOR
DRAIN PUMP (OPTION)
DRAIN SENSOR (OPTION)
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )
ROOM TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
COND./EVA.TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
WIRED REMOTE CONTROLLER BOARD
BLK
WHT
[LEGEND]
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
SW1
SW2
SWE
X1
X4
BCR
LED1
LED2
LED3
C
PCA-RP50GA2
R.B
1 2
TB6
TH5
[Servicing]
Fasten terminal of the terminal board "TB4"equips lock system.
To remove the fastened terminal, pull it while pressing the protruding
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
Table 1
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor
unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match
terminal numbers (S1, S2, S3) for correct wirings.
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
MODELS
PCA-RP·GA
1 2 3 4 5
ON
OFF
Table 2
MODELS
PCA-RP50GA
PCA-RP50GA2
PCA-RP60GA
PCA-RP71GA
44
SW1
Service board
SW2
Service board
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
TO OUTDOOR
UNIT
t°
45
TH1
SYMBOL
I.B.
CN2A
CN2L
CN32
CN41
CN51
CN90
CN105
LED1
LED2
LED3
1
2
FS *1
1
2
3
4
CN4F
CNXB2
(Red) 1
CN2L 23
4
5
CN51
OFF
ON
LED2
1
2
CNXC2
SWE
LED1
4
3
2
1
CNXA2
(Blue)
CN22 2
(Blue) 1
(Black)
CN2A
(Red)
CN105
NAME
SYMBOL
NAME
I.B.
Indoor controller board
Indoor controller board
SW1 Switch (for mode selection)
Connector (0-10V Analog input)
SW2 Switch (for capacity code)
Connector (Lossnay)
SWE Connector (emergency operation)
Connector (Remote switch)
Connector (HA terminal-A)
Power supply board
P.B.
F01
Connector (Centrally control)
Fuse AC250V 6.3A
ZNR01, 02 Varistor
Connector (Wireless)
DSA Arrester
Connector (IT terminal)
X01
Aux. relay
LED(Power supply)
X10
Aux. relay
LED(Remote controller supply)
LED(Transmission indoor-outdoor)
SYMBOL EXPLANATION
t°
(Red)
CN20
CN41
CN32
TB15
SYMBOL
TH1
TH2
TH5
ACL
FS
TB4
M
1~
Drain pump
CNP
(Blue)
X01
1 2 3 4
(Blue)
X10
F01
CND
5 (Red)
CNXC1 CNXA1
1 2
U
ZNR01
3
Fan motor
M
7 6 5 4
CNMF
1
DC280~340V
Rectifier circuit
TO OUTDOOR UNIT
*1. Drain pump and float switch: only for PEAD-JA model
S3
TB4
NOTE: 1. Since the outdoor side electric wiring may change be sure to
NAME
Intake air temp. Thermistor
check the outdoor unit electric wiring for servicing.
Pipe temp. Thermistor/liquid
2. Indoor and outdoor connecting wires are made with polarities,
Cond./eva.temp. Thermistor
make wiring matching terminal numbers (S1,S2,S3).
AC reactor (Power factor improvement)
Float switch
3. Symbols used in wiring diagram above are, terminal block,
Terminal block
connector.
(Indoor/outdoor connecting line)
Terminal block
(Remote controller transmission line)
*1
1 2 3 4 5
CNXB1
3
1
DSA
ZNR02
U
1
P.B.
S1
S2
TO MA REMOTE
CONTROLLER
PEAD-RP60JA(L)
TH2 TH5
1
2
3
4
CN44
SW2
SW1
2
TB15
1
2
PEAD-RP50JA(L)
t°
LED3
CN90
1 CN3C
3 (Blue)
I.B.
1
2
1
ACL
INSIDE SECTION OF CONTROL BOX
PEAD-RP35JA(L)
PEAD-RP71JA(L)
PEAD-RP35EA2
PEAD-RP50EA
[LEGEND]
NAME
SYMBOL
I.B.
INDOOR CONTROLLER BOARD
FUSE FUSE(T6.3AL250V)
ZNR VARISTOR
CN2L CONNECTOR(LOSSNAY)
CN24 CONNECTOR(HEATER)
CN32 CONNECTOR(REMOTE SWITCH)
CN41 CONNECTOR(HA TERMINAL-A)
CN51 CONNECTOR(CENTRALLY CONTROL)
CN90 CONNECTOR(WIRELESS)
LED1 POWER SUPPLY(I.B.)
LED2 POWER SUPPLY(REMOTE CONTROLLER)
LED3 TRANSMISSION(INDOOR•OUTDOOR)
SW1 SWITCH(MODEL SELECTION)
SYMBOL
SW2
SWE
X1
X4
X5
X6
P.B.
DRAIN PUMP
PEAD-RP60EA
PEAD-RP71EA
NAME
SWITCH(CAPACITY CORD)
SWITCH(EMERGENCY OPERATION)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
INDOOR POWER BOARD
(OPTIONAL PARTS)
TB4
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER)
INTAKE AIR TEMP. THERMISTOR
(0 /15kΩ, 25/5.4kΩ DETECT)
TB5
TH1
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0 /15kΩ, 25/5.4kΩ DETECT)
TH5
COND./EVA. TEMP. THERMISTOR
(0 /15kΩ, 25/5.4kΩ DETECT)
DRAIN PUMP
DRAIN SENSOR
CAPACITOR(FAN MOTOR)
FAN MOTOR
DP
DS
C
MF
NAME
SYMBOL
INSIDE SECTION OF CONTROL BOX
DS
TH1
TH2
TH5
B B
L L
U U
1
3
CN31
1 2
1 2
CN22
(BLU)
CN20
(RED)
I.B.
1 2
1 2 3
1 2 3 4 5 6 7 8 9
1 2 3 4
1 2
1 2 3 45
1 2 3
CN21 CN29
(WHT) (BLK)
CN31
(WHT)
CN90
(WHT)
CN41
(WHT)
CN24
(YLW)
CN51
(WHT)
CN32
(WHT)
1 2
1 2
SW1
CN2L
(RED)
SW2
SWE
ON
OFF
LED1
LED2
LED3
2
1
WHT
BLK
X1
(BLU)
CN3C
O3B 1
R R
N N
ZNR
W3B1
H L
T K
O3Y 1
R L
N W
2 1
TO MA-REMOTE
CONTROLLER
DC8.7-13V
TB4
S3
S2
S1
TO OUTDOOR UNIT
2
1
B
L
K
W
H
T
CN2S
(WHT)
X4
X1
FUSE
(ORN)
CND
W B
H L
T K
TB5 BL
U B
2
L
1
U
X4 X5 X6
X5
CN2D
(WHT)
3
(RED)
CNDK
P.B.
1
CNSK
(RED)
3
1
(BLU)
CNP
DP
Optional parts
X6
7 5 3 1
W P P B
H N N L
T K K K
<PEAD-RP35•50•60EA, 35EA2>
External static
pressure 30Pa
<PEAD-RP71•100•125•140EA, 100EA2>
External static pressure 70Pa
<PEAD-RP35•50•60EA, 35EA2>
External static
pressure 70Pa
1 2 3 4 5 6
Optional parts
(RED)
(WHT)
BRN
ORN
YLW
MF
C
SW1
SW2
Model selection Capacity cord
switch
switch
12345
35EA2
50EA
60EA
71EA
12345
12345
ON
OFF
12345
12345
1 2 3 4 5 6
(RED)
1 2 3 4 5 6
MF
MODELS
(WHT)
FAN
ON
OFF
ON
OFF
ON
OFF
C
<PEAD-RP71•100•125•140EA, 100EA2>
External static
pressure 130Pa
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor
unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match
terminal numbers (S1, S2, S3) for correct wirings.
3. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
4. The wiring between MA-Remote controller and TB5 is included in the package.
ON
OFF
46
PEAD-RP60GA
PEAD-RP71GA
[LEGEND]
NAME
NAME
SYMBOL
SYMBOL
I.B.
INDOOR CONTROLLER BOARD
SW1 SWITCH(MODEL SELECTION)
FUSE FUSE(T6.3AL250V)
SW2 SWITCH(CAPACITY CODE)
ZNR VARISTOR
SWE SWITCH(EMERGENCY OPERATION)
CN2L CONNECTOR(LOSSNAY)
X1 RELAY(DRAIN PUMP)
X4 RELAY(FAN MOTOR)
CN24 CONNECTOR(HEATER)
CN32 CONNECTOR(REMOTE SWITCH)
X5 RELAY(FAN MOTOR)
CN41 CONNECTOR(HA TERMINAL-A)
X6 RELAY(FAN MOTOR)
CN51 CONNECTOR(CENTRALLY CONTROL) P.B. INDOOR POWER BOARD
C
CAPACITOR(FAN MOTOR)
CN90 CONNECTOR(WIRELESS)
MF
LED1 POWER SUPPLY(I.B.)
FAN MOTOR
LED2 POWER SUPPLY(REMOTE CONTROLLER) TB4 TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
LED3 TRANSMISSION(INDOOR•OUTDOOR)
NAME
SYMBOL
TERMINAL BLOCK(REMOTE CONTROLLER)
TB5
TH1
INTAKE AIR TEMP.THERMISTOR
(0 /15kΩ, 25/5.4kΩ DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0 /15kΩ, 25/5.4kΩ DETECT)
TH5
COND./EVA. TEMP. THERMISTOR
(0 /15kΩ, 25/5.4kΩ DETECT)
INSIDE SECTION OF CONTROL BOX
TH1
TH2
TH5
1 2
1 2
1 2
1 2
CN22
(BLU)
CN20
(RED)
CN21
(WHT)
CN29
(BLK)
B B
L L
U U
I.B.
1 2 3
1 2 3 4 5 6 7 8 9
1 2 3 4
CN90
(WHT)
CN41
(WHT)
CN31
(WHT)
1 2
CN24
(YLW)
1 2 3 4 5
1 2 3
CN51
(WHT)
CN32
(WHT)
1 2
SW1
CN2L
(RED)
SW2
SWE
ON
LED1
LED2
LED3
WHT
BLK
2
1
OFF
X1
(BLU)
CN3C
O3B1
R R
N N
ZNR
(ORN)
CND
TO MA-REMOTE
CONTROLLER
DC8.7-13V
W3B1
H L
T K
O3Y1
R L
N W
TB4
S3
S2
S1
TO OUTDOOR UNIT
MODELS
60GA
71GA
2 1
U B
L
U
2
1
X1
FUSE
W B
H L
T K
TB5 BL
X4 X5 X6
X5
CN2D
(WHT)
2
1
W
H
T
CN2S
(WHT)
B
L
K
3
(RED)
CNDK
3
P.B.
1
1
(BLU)
CNP
X4
X6
7 5 3 1
G Y Y B
R L L L
Y W W K
B B O
L L R
U K G
CNSK
(RED)
(WHT)
FAN
*External static pressure
CONNECTOR COLOR
220V
*
1 2 3 4 5 6
(WHT)
230V
240V
BLU
5Pa
10Pa
20Pa
WHT
35Pa
50Pa
60Pa
RED
50Pa
70Pa
75Pa
(FACTORY SHIPMENT)
BRN
ORN
YLW
MF
C
SW1
SW2
Model selection Capacity cord
switch
switch
12345
12345
ON
OFF
12345
ON
OFF
ON
OFF
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor
unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match
terminal numbers (S1, S2, S3) for correct wirings.
3. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
4. The wiring between MA-Remote controller and TB5 is included in the package.
47
PEA-RP71EA
[LEGEND]
SYMBOL
SYMBOL
NAME
P.B
INDOOR POWER BOARD
I.B SW1
I.B
INDOOR CONTROLLER BOARD
SW2
FUSE FUSE(T6.3AL250V)
SWE
ZNR VARISTOR
X4
CN2L CONNECTOR(LOSSNAY)
X5
CN32 CONNECTOR(REMOTE SWITCH))
X6
CN41 CONNECTOR(HA TERMINAL-A)
R.B
CN51 CONNECTOR(CENTRALLY CONTROL)
TB6
LED1 POWER SUPPLY(I.B)
C
LED2 POWER SUPPLY(R.B)
LED3 TRANSMISSION(INDOOR • OUTDOOR) MF
SYMBOL
NAME
SWITCH(MODEL SELECTION)+See table 1
SWITCH(CAPACITY CODE)+See table 2
SWITCH(EMERGENCY OPERATION)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
REMOTE CONTROLLER BOARD
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
TB2
TB4
CAPACITOR(FAN MOTOR)
FAN MOTOR
NAME
TERMINAL BLOCK(INDOOR UNIT POWER(OPTION))
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TB5
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
TH1
ROOM TEMPERATURE THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH2
PIPE TEMPERATURE THERMISTOR/LIQUID
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH5
COND./EVA. TEMPERATURE THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
INDOOR UNIT
P.B
CN2S
(WHT)
2
1
ORN
5
7
POWER 1
CNDK
(RED)
3
POWER 1
CND
(ORN)
3
ZNR
X6 X5 X4
X6 X5
X4
LED3 LED2 LED1
SWE
SW2
SW1
ON
OFF
CN24
Refer to tables
1 and 2.
1 2
1 3
POWER INDOOR/OUTDOOR
COMMUNICATION
CN2D
CN3C
(WHT)
(BLU)
WIRELESS
2 LIQUID
CN21
CN90
1 (WHT)
(WHT)
2 INTAKE
CN20
REMOCON 2
1 (RED)
CN22
1
(BLU)
2 PIPE
CN29
1 (BLK)
CN2L
CN41
CN32
TB5
1
2
BLU
2
TH5
PEA-RP·EA
BLU
BLU
1
TH1
MODELS
BLU
R.B
TH2
Table 1
ORN
YLW
3
BRN
WHT
1
WHT
RED
FAN
(WHT)
BLK
6
C
I.B
S3
2
FUSE
5
ORN
BLU
1
TO
OUTDOOR
UNIT
S2
1
WHT
RED
4
BRN
BLK
3
ORN
3
DC13.1V
MF
2
TB4
S1
YLW
CNSK
(RED)
TB6
TRANSMISSION
WIRE DC12V
Table 2
SW1
Manufacture/Service
MODELS
1 2 3 4 5
ON
OFF
PEA-RP71EA
SW2
Manufacture/Service
Please set the voltage using
the remote controller.
For the setting method, please
refer to the indoor unit
installation Manual.
1 2 3 4 5
ON
OFF
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings.
3. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
4. This diagram shows the wiring of Indoor and Outdoor connecting wires(specification of 230V), adopting superimposed
system of power and signal.
48
NOTES:1. About the indoor side electric wiring, refer to
the indoor unit electric wiring diagram for
servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
: Terminal block
SUZ-KA25VA
SUZ-KA35VA
49
NOTES:1. About the indoor side electric wiring, refer to
the indoor unit electric wiring diagram for
servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
: Terminal block
SUZ-KA25VAH
SUZ-KA35VAH
50
51
3~
MC U
BLK
WHT
RED
1
3
SYMBOL
CT
C61,62,63
DB61,DB65
DSA
F61
F701,F801,F901
HC930,IPM
IC802
L61
L62
W
MS V
RED
LDW
LDV
LDU
U
V
P
N
IPM
W
R825
TR821
1
R61
3
5
MF
MS
3~
CN932
3
5
F901
F801
R937A
1
T801
1
RT64
2 1
CN642
HC930
R937B
IC802
RT68
CN644
RT65
RT61 RT62
CN641
4 1
LEV
M
6
CN724
6
CT
LD61
U
F701
LD63
BRN
U
1
CN721
LD-E1
2
F61
LD62
U
LD-S
L62 DSA
PTC65
PTC64
X64
X63
21S4
BRN
BLU
RED
GRN/YLW
BLK
S1
S3
S2
TB2
L
N
TB1
230V~
12-24V
CIRCUIT
BREAKER
NOTES: 1. About the indoor side electric wiring,
NAME
refer to the indoor unit electric wiring
CURRENT-DETECTING RESISTOR
diagram for servicing.
CURRENT-DETECTING RESISTOR
CURRENT-DETECTING RESISTOR
2. Use copper conductors only (for field wiring).
TERMINAL BLOCK
3. Symbols below indicate.
SWITCHING POWER TRANSISTOR
:Terminal block
TRANSFORMER
RELAY
REVERSING VALVE COIL
2 1
SYMBOL
R61
R825
R937A, B
TB1,TB52
TR821
T801
X63,X64
21S4
3 1
CN643
INVERTER P.C. BOARD
NAME
EXPANSION VALVE COIL
COMPRESSOR
FAN MOTOR
CIRCUIT PROTECTION
DEFROST THERMISTOR
DISCHARGE TEMP. THERMISTOR
FIN TEMP. THERMISTOR
AMBIENT TEMP. THERMISTOR
RT68 OUTDOOR HEAT EXCHANGER
TEMP. THERMISTOR
SYMBOL
LEV
MC
MF
PTC64,PTC65
RT61
RT62
RT64
RT65
CN931
C63 C62 C61
LD66
NAME
CURRENT TRANSFORMER
SMOOTHING CAPACITOR
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL 250V)
FUSE (T3.15AL 250V)
INTELLIGENT POWER MODULE
INTELLIGENT POWER DEVICE
REACTOR
REACTOR
BLK
WHT
1
3
DB65
DB61
LD70
YLW
BLU
BRN
L61
POWER SUPPLY
~/N 230V 50Hz
TO INDOOR
UNIT
CONNECTING
ORN
SUZ-KA50VA
SYMBOL
CB1~3
CT1, 2
CT61
F64
F801
F911
HC930
HPS
IPM
L
NAME
SMOOTHING CAPACITOR
CURRENT TRANSFORMER
CURRENT TRANSFORMER
FUSE (T2AL 250V)
FUSE (T3.15AL 250V)
FUSE (T1AL 250V)
INTELLIGENT POWER MODULE
HIGH PRESSURE SWITCH
INTELLIGENT POWER MODULE
REACTOR
SYMBOL
LEV
MC
MF
NF
NR64
PFC
RS1~4
RT61
RT62
RT64
NAME
EXPANSION VALVE
COMPRESSOR
FAN MOTOR
NOISE FILTER
VARISTOR
POWER FACTOR CONTROLLER
RESISTOR
DEFROST THERMISTOR
DISCHARGE TEMP. THERMISTOR
FIN TEMP. THERMISTOR
SYMBOL
RT65
RT68
R64A,B
R937A, B
SSR61
TB1
TB2
T801
X64
21S4
NOTES: 1. About the indoor side electric wiring
NAME
refer to the indoor unit electric wiring
AMBIENT TEMP. THERMISTOR
diagram for servicing.
OUTDOOR HEAT EXCHANGER TEMP. THERMISTOR
RESISTOR
2. Use copper conductors only (for field wiring).
RESISTOR
3. Symbols below indicate.
SOLENOID COIL RELAY
:Terminal block
TERMINAL BLOCK
TERMINAL BLOCK
TRANSFORMER
RELAY
REVERSING VALVE COIL
SUZ-KA60VA
52
PE
NOISE
FILTER
P.C.BOARD
GRN/YLW
N
S3
RED
BLU
WHT
GRN
LDE1
CT61
1 2
RED
SYMBOL
MC
MF
NF
NR64
PFC
R64A,B
R937A, B
RS1~4
RT61
RT62
RT64
RT61 RT62
CN661
1 2 3 4
RED
BLK
BLK
BLK
4 YLW
1
RT68
7 8
LEV
6
CN795
5 6 7
CN702
3
2
S
R
CN4
1 2
RS2
RS1
T801
1
3
RS3
LD1
RS4
R937B
R937A
LD2
CB2
CT1 U
U
CN932
RED
WHT
BLK
GRN
MF
POWER RT64
BOARD
BLK
WHT
MC
W
RED
V
GRY
PNK
ORN
BLU
YLW
LD9
IPM
V
CT2 W
NOTES: 1.About the indoor electric wiring,
refer to the indoor unit electric wiring
diagram for servicing.
2.Use copper conductors only (for field wiring).
3.Symbols below indicate.
:Terminal block
:Connector
1 2
CN701
NAME
SYMBOL
NAME
COMPRESSOR
RT65 AMBIENT TEMPERATURE THERMISTOR
OUTDOOR FAN MOTOR
OUTDOOR HEAT EXCHANGER
RT68 TEMPERATURE THERMISTOR
NOISE FILTER
VARISTOR
SSR61 SOLENOID COIL RELAY
POWER FACTOR CONTROLLER
T801 TRANSFORMER
RESISTOR
TB1 TERMINAL BLOCK
TB2 TERMINAL BLOCK
RESISTOR
X64 RELAY
RESISTOR
21S4 R.V. COIL
DEFROST THERMISTOR
DISCHARGE TEMPERATURE THERMISTOR
FIN TEMPERATURE THERMISTOR
RT65
CN681 CN663
1 2
1 2
1
21S4
CN901
1 2 3
5
NR64
TAB4
3
ELECTRONIC 1 2 3
5
CONTROL
CN781
P.C.BOARD
HPS RED
RED
[LEGEND]
SYMBOL
NAME
CB1~3 SMOOTHING CAPACITOR
CT1, 2 CURRENT TRANSFORMER
CT61 CURRENT TRANSFORMER
F64 FUSE (T2AL 250V)
F801 FUSE (T3.15AL 250V)
F911 FUSE (T1AL 250V)
HC930 INTELLIGENT POWER MODULE
HPS HIGH PRESSURE SWITCH
IPM INTELLIGENT POWER MODULE
REACTOR
L
LEV EXPANSION VALVE COIL
12-24V
S2
S1
TO INDOOR
UNIT
CONNECTING
230V~TB2
TAB2
CN61
3
1
BLU
NF
F64
BLK
BRN
WHT
BLU
F911
R64A R64B
SSR61
BLK
BLK
BLK
LDE2
CN912
BLU
BLU
CN902 CN903
2 1 2 1
X64
YLW
BLK
L
GRN
3
1
CN601
5
BLK
BLK
BLK
PFC
2 1
CN5
7 6 5 4 3 2 1
CN2
BLK
BLK
F801
CB1
RED
CB3
WHT
CN801
L
CN931
1 2 3 4 5
53
1 2 3
TAB1
HC930
CN3
1 2
POWER SUPPLY
~/N 230V 50Hz
CIRCUIT
BREAKER
TB1
SUZ-KA71VA
5
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT
MFZ-KA25VA
MFZ-KA35VA
MFZ-KA50VA
Unit : mm
Refrigerant pipe :9.52 (MFZ-KA25/35VA)
Refrigerant pipe :12.7 (MFZ-KA50VA)
(with heat insulator)
Indoor coil
thermistor
RT12 (main)
Distributor
Indoor
heat
exchanger
Flared connection
Indoor coil
thermistor
RT12, RT14,
RT15 (main)
RT13 (sub)
Refrigerant flow in cooling
Refrigerant flow in heating
Room temperature
thermistor
RT11
Flared connection
Refrigerant pipe :6.35
(with heat insulator)
SLZ-KA·VA
SEZ-KC·VA
PCA-RP·KA
PEAD-RP·JA(L)
SLZ-KA·VAL
SEZ-KA·VA
PCA-RP·GA(2)
PEAD-RP·GA
SEZ-KD·VA
PLA-RP·BA(2)
SEZ-KD·VAL
PLA-RP·AA
PEAD-RP·EA(2)
PEA-RP·EA
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Thermistor TH5
(Cond./Eva. temperature)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Distributor
with strainer(#50)
Thermistor TH1
(Room temperature)
Thermistor TH2
Pipe temperature (Liquid)
Strainer(#50)
54
5-2. OUTDOOR UNIT
SUZ-KA25VA SUZ-KA25VAH
Unit:mm
Refrigerant pipe ø9.52
(with heat insulator)
4-way valve
Muffler
Stop valve
(with service port)
Discharge
temperature
thermistor
RT62
Flared connection
Outdoor
heat
exchanger
Muffler
Outdoor heat
exchanger
temperature
thermistor
RT68
Ambient
temperature
thermistor
RT65
Compressor
Defrost
thermistor
RT61
Strainer
#100
Flared connection
Refrigerant pipe ø6.35
(with heat insulator)
SUZ-KA35VA
Capillary tube
ø3.0×ø2.0×240
LEV
R.V. coil
heating ON
cooling OFF
Stop valve
(with strainar)
Refrigerant flow in cooling
Refrigerant flow in heating
SUZ-KA35VAH
Unit:mm
Refrigerant pipe ø9.52
(with heat insulator)
4-way valve
Muffler
Stop valve
(with service port)
Discharge
temperature
thermistor
RT62
Flared connection
Outdoor
heat
exchanger
Muffler
Outdoor heat
exchanger
temperature
thermistor
RT68
Ambient
temperature
thermistor
RT65
Compressor
Defrost
thermistor
RT61
Capillary tube
ø3.0×ø1.8×600(×2)
Flared connection
Refrigerant pipe ø6.35
(with heat insulator)
Strainer
#100
Capillary tube
ø3.0×ø2.0×240
Stop valve
(with strainar)
LEV
R.V. coil
heating ON
cooling OFF
Refrigerant flow in cooling
Refrigerant flow in heating
55
SUZ-KA50VA
Unit:mm
Muffler
4-way valve #100
Refrigerant pipe ø12.7
(with heat insulator)
Stop valve
(with service port)
Flared connection
Discharge
temperature
thermistor
RT62
Defrost
thermistor
RT61
Outdoor
heat
exchanger
Ambient
temperature
thermistor
RT65
Compressor
Outdoor heat
exchanger
temperature
thermistor
RT68
Flared connection
LEV
Receiver
Refrigerant pipe ø6.35
(with heat insulator)
Stop valve
(with strainer)
Strainer
#100
R.V. coil
heating ON
cooling OFF
Capillary tube
ø3.6×ø2.4×50
Refrigerant flow in cooling
Refrigerant flow in heating
SUZ-KA60VA
Unit:mm
Refrigerant pipe :15.88
(with heat insulator)
Muffler
4-way valve #100
Stop valve
(with service port)
Flared connection
Discharge
temperature
thermistor
RT62
High-pressure
switch
Defrost
thermistor
RT61
Outdoor
heat
exchanger
Ambient
temperature
thermistor
RT65
Compressor
Outdoor heat
exchanger
temperature
thermistor
RT68
Flared connection
LEV
Strainer
Receiver #100
Stop valve
Refrigerant pipe :6.35
(with heat insulator)
Capillary tube
:3.6:2.450
56
Strainer
#100
R.V. coil
heating ON
cooling OFF
Refrigerant flow in cooling
Refrigerant flow in heating
SUZ-KA71VA
Unit:mm
Refrigerant pipe :15.88
(with heat insulator)
Capillary tube
:1.8×:0.6×1000
Oil separator High-pressure
4-way valve
switch
Stop valve
(with service port)
Strainer
#100
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Compressor
Flared connection
Strainer
Receiver #100
Stop valve
Refrigerant pipe :9.52
(with heat insulator)
LEV
Capillary tube
:3.6×:2.4×50
57
Strainer
#100
Outdoor
heat
exchanger
Ambient
temperature
thermistor
RT65
Outdoor
heat
exchanger
temperature
thermistor
RT68
R.V. coil
heating ON
cooling OFF
Refrigerant flow in cooling
Refrigerant flow in heating
6
PERFORMANCE CURVES
FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA25VA(H)
Cooling capacity
Capacity correction factors
1.5
Indoor intake air Wet-bulb
temperature()
1.4
1.3
1.2
26
1.1
24
1.0
22
20
18
0.9
0.8
0.7
0.6
-10
-5
0
5
10
15
20
25
30
35
40
45
Outdoor intake air Dry-bulb temperature()
Total input (cooling)
1.5
Indoor intake air Wet-bulb
temperature()
Input correction factors
1.4
1.3
1.2
26
22
20
18
24
1.1
1.0
0.9
0.8
0.7
0.6
-10
-5
0
5
10
15
20
25
30
35
Outdoor intake air Dry-bulb temperature()
58
40
45
FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA35VA(H)
Cooling capacity
Capacity correction factors
1.5
Indoor intake air Wet-bulb
temperature()
1.4
1.3
26
1.2
1.1
24
1.0
22
20
18
0.9
0.8
0.7
0.6
-10
-5
0
5
10
15
20
25
30
35
40
45
Outdoor intake air Dry-bulb temperature()
Total input (cooling)
1.5
Indoor intake air Wet-bulb
temperature()
1.4
Input
correction factors
1.3
1.2
26
22
20
18
24
1.1
1.0
0.9
0.8
0.7
0.6
-10
-5
0
5
10
15
20
25
30
35
Outdoor intake air Dry-bulb temperature()
59
40
45
FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA50/60/71VA
Cooling capacity
1.5
Indoor intake air Wet-bulb
temperature()
Capacity correction factors
1.4
1.3
1.2
26
1.1
24
1.0
22
20
18
0.9
0.8
0.7
0.6
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
Outdoor intake air Dry-bulb temperature()
Total input (cooling)
1.3
Indoor intake air Wet-bulb
temperature()
1.2
22
20
18
24
26
Input correction factors
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
-15
-10
-5
0
5
10
15
20
25
30
35
Outdoor intake air Dry-bulb temperature ()
60
40
45
Heating capacity
Capacity correction factors
1.3
15
20
26
1.2
1.1
Indoor intake air Dry-bulb
temperature()
1.0
0.9
0.8
0.7
0.6
-10
-5
0
5
10
15
Outdoor intake air Wet-bulb temperature ()
Total input (heating)
1.3
Input correction factors
1.2
1.1
26
20
15
Indoor intake air Dry-bulb
temperature()
1.0
0.9
0.8
0.7
0.6
-10
-5
0
5
10
Outdoor intake air Wet-bulb temperature ()
NOTE: The above curves are for the heating operation without any frost.
61
15
7
APPLICABLE EXTENSION PIPE FOR EACH MODEL
SUZ-KA25VA SUZ-KA25VAH
SUZ-KA35VA SUZ-KA35VAH
MAX. REFRIGERANT PIPING LENGTH
Models
Refrigerant piping
Max. length : m
A
Gas
Liquid
20
9.52
6.35
SUZ-KA25VA
SUZ-KA35VA
SUZ-KA25VAH
SUZ-KA35VHA
Piping size O.D : mm
MAX. HEIGHT DIFFERENCE
Indoor
unit
+ Max. Height
difference 12m
Refrigerant Piping
Max. length
A
Outdoor unit
+ Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Refrigerant piping length (one way)
Outdoor unit
precharged
5m
6m
7m
8m
9m
10m
11m
12m
13m
14m
15m
20m
SUZ-KA25VA
SUZ-KA25VAH
800
0
0
0
90
120
150
180
210
240
270
300
450
SUZ-KA35VA
SUZ-KA35VAH
1,050
0
0
0
90
120
150
180
210
240
270
300
450
Models
Calculation : Xg=30g/m ✕ (Refrigerant piping length (m) -5)
62
SUZ-KA50VA
SUZ-KA60VA
SUZ-KA71VA
MAX. REFRIGERANT PIPING LENGTH
Models
Refrigerant piping
Max. length : m
A
Piping size O.D : mm
Gas
SUZ-KA50VA
Liquid
12.7
6.35
SUZ-KA60VA
30
15.88
SUZ-KA71VA
9.52
MAX. HEIGHT DIFFERENCE
Indoor
unit
+ Max. Height
difference 30m
Refrigerant Piping
Max. length
A
Outdoor unit
+ Height difference should be within 30m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE (R410A : g)
Refrigerant piping length (one way)
Outdoor unit
precharged
7m
10m
15m
20m
25m
30m
SUZ-KA50VA
1,600
0
60
160
260
360
460
SUZ-KA60VA
1,800
0
60
160
260
360
460
Models
Calculation : Xg=20g/m o (Refrigerant piping length (m) -7)
Models
SUZ-KA71VA
Refrigerant piping length (one way)
Outdoor unit
precharged
7m
10m
15m
20m
25m
30m
2,000
0
165
440
715
990
1,265
Calculation : Xg=55g/m o (Refrigerant piping length (m) -7)
63
8
AIR FLOW DATA
8-1. OUTLET AIR SPEED AND COVERAGE RANGE
Air flow
Air speed
Coverage range
Air flow
Air speed
Coverage range
Air flow
Air speed
Coverage range
Air flow
Air speed
Coverage range
Air flow
Air speed
Coverage range
m³/min.
MFZ-KA25VA
MFZ-KA35VA
MFZ-KA50VA
8.7
9.1
10.7
m/sec.
1.8
1.9
2.2
m
5.1
5.3
6.2
SLZ-KA25VA
SLZ-KA25VAL
SLZ-KA35VA
SLZ-KA35VAL
SLZ-KA50VA
SLZ-KA50VAL
m³/min.
10
11
11
m/sec.
3.4
3.7
3.7
m
3.7
4.1
4.1
PLA-RP35BA
PLA-RP50BA
PLA-RP60BA
PLA-RP71BA(2)
15
18
18
21
m³/min.
m/sec.
2.6
3.2
3.2
3.7
m
4.1
4.8
4.8
5.6
PLA-RP35AA
PLA-RP50AA
PLA-RP60AA
PLA-RP71AA
m³/min.
14
18
18
20
m/sec.
2.8
3.6
3.6
4.0
m
4.0
5.2
5.2
5.7
PCA-RP50KA
PCA-RP60KA
PCA-RP71KA
15
19
20
m³/min.
m/sec.
3.3
3.1
3.2
m
9.0
9.6
10.1
PCA-RP50GA PCA-RP50GA2 PCA-RP60GA
Air flow
Air speed
Coverage range
PCA-RP71GA
m³/min.
13
18
18
18
m/sec.
3.7
3.8
3.8
3.8
m
8.8
10.4
10.4
10.4
w The air coverage range is the distance to which the 0.25m/sec air can reach, when air is blown out horizontally from the unit
at the High notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
64
8-2. SLZ-KA•VA
SLZ-KA•VAL
8-2-1. Fresh air intake (Location for installation)
At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required.
Fresh air intake
Detail drawing of fresh air intake
25
:100
:73.4
Cut out hole
0°
12
12
0°
118
3-:2.8 hole
Burring hole
Ceiling surface
Refrigerant pipe
Electrical Box
Drain pipe
8-2-2. Fresh air intake amount & static pressure characteristics
Taking air into the unit
Curve in the
left graphs.
0
Q
-50
-100
Duct characteristics
at site
A
2.5
1
C
A
2
E
-150
-200
Q
-250
D
3
A
-300
NOTE: Fresh air intake amount should be 20% or less of
whole air amount to prevent dew dripping.
Q
Qa
65
C
2.0
Airflow : Q [m3/min]
3.0 3.5
B
Static pressure : P [Pa]
50
0.5 1.0 1.5
0
How to read curves
Q…Designed amount of fresh air intake
<m3/min>
A…Static pressure loss of fresh air
intake duct system with airflow
amount Q
<Pa>
B…Forced static pressure at air conditioner inlet with airflow amount Q
<Pa>
C…Static pressure of booster fan with
airflow amount Q
<Pa>
D…Static pressure loss increase
amount of fresh air intake duct system for airflow amount Q <Pa>
E…Static pressure of indoor unit with
airflow amount Q
Qa…Estimated amount of fresh air
intake without D
<m3/min>
8-3. SEZ-KD•VA(L)
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
SEZ-KD25VA(L)
SEZ-KD25VA(L)
(External static pressure 5Pa) 220-240V 50/60Hz
(External static pressure 15Pa) 220-240V 50/60Hz
40
50
Limit
Limit
40
External static pressure (Pa)
External static pressure (Pa)
30
20
High
High
30
20
Middle
Rated point
10
Middle
Low
10
Low
Rated point
0
0
4
5
6
7
8
Airflow rate(m3/min)
9
10
SEZ-KD25VA(L)
4
5
6
7
8
Airflow rate(m3/min)
9
10
SEZ-KD25VA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
(External static pressure 50Pa) 220-240V 50/60Hz
80
80
Limit
Limit
70
70
60
60
External static pressure (Pa)
External static pressure (Pa)
High
50
High
40
Rated point
30
Middle
20
50
Rated point
40
Middle
30
Low
20
Low
10
10
0
0
4
5
6
7
8
Airflow rate(m3/min)
9
10
4
66
5
6
7
8
Airflow rate(m3/min)
9
10
SEZ-KD35VA(L)
SEZ-KD35VA(L)
(External static pressure 5Pa) 220-240V 50/60Hz
(External static pressure 15Pa) 220-240V 50/60Hz
40
50
40
External static pressure (Pa)
External static pressure (Pa)
30
Limit
20
High
Limit
30
High
20
Middle
Rated point
10
Middle
10
Low
Rated point
Low
0
6
7
8
9
10
Airflow rate(m3/min)
11
SEZ-KD35VA(L)
6
7
8
9
10
Airflow rate(m3/min)
11
12
SEZ-KD35VA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
(External static pressure 50Pa) 220-240V 50/60Hz
80
80
70
70
60
50
40
Rated point
30
High
Middle
20
Limit
60
Limit
External static pressure (Pa)
External static pressure (Pa)
0
12
50
Rated point
High
40
Middle
30
20
Low
10
Low
10
0
0
6
7
8
9
10
Airflow rate(m3/min)
11
12
67
6
7
8
9
10
Airflow rate(m3/min)
11
12
SEZ-KD50VA(L)
SEZ-KD50VA(L)
(External static pressure 5Pa) 220-240V 50/60Hz
(External static pressure 15Pa) 220-240V 50/60Hz
50
40
Limit
Limit
40
External static pressure (Pa)
External static pressure (Pa)
30
20
High
Middle
30
High
20
Middle
Rated point
Low
10
10
Low
Rated point
0
0
8
9
10
11
12
13
Airflow rate(m3/min)
14
15
8
16
SEZ-KD50VA(L)
9
10
11
12
13
Airflow rate(m3/min)
14
15
16
SEZ-KD50VA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
(External static pressure 50Pa) 220-240V 50/60Hz
80
80
70
70
Limit
Limit
High
60
External static pressure (Pa)
External static pressure (Pa)
60
50
High
40
Middle
30
Rated point
20
50
Rated point
Middle
40
30
Low
20
Low
10
10
0
0
8
9
10
11
12
13
Airflow rate(m3/min)
14
15
16
8
68
9
10
11
12
13
Airflow rate(m3/min)
14
15
16
SEZ-KD60VA(L)
SEZ-KD60VA(L)
(External static pressure 5Pa) 220-240V 50/60Hz
(External static pressure 15Pa) 220-240V 50/60Hz
40
50
Limit
Limit
40
External static pressure (Pa)
External static pressure (Pa)
30
20
High
Middle
10
High
30
Middle
20
Low
Rated point
10
Low
Rated point
0
0
9
10
11
12
13
14
15
Airflow rate(m3/min)
16
17
18
19
SEZ-KD60VA(L)
9
10
11
12
13
14
15
Airflow rate(m3/min)
17
18
19
SEZ-KD60VA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
(External static pressure 50Pa) 220-240V 50/60Hz
80
80
Limit
Limit
70
70
60
60
External static pressure (Pa)
External static pressure (Pa)
16
High
50
40
Middle
Rated point
30
Low
20
High
50
30
Low
20
10
Rated point
Middle
40
10
0
0
9
10
11
12
13
14
15
Airflow rate(m3/min)
16
17
18
19
69
9
10
11
12
13
14
15
Airflow rate(m3/min)
16
17
18
19
SEZ-KD71VA(L)
SEZ-KD71VA(L)
(External static pressure 5Pa) 220-240V 50/60Hz
(External static pressure 15Pa) 220-240V 50/60Hz
40
50
40
External static pressure (Pa)
External static pressure (Pa)
30
20
Limit
30
Limit
20
High
Rated point
10
High
10
Middle
Middle
Rated point
Low
Low
0
0
11
12
13
14
15
16
17
Airflow rate(m3/min)
18
19
20
11
21
SEZ-KD71VA(L)
13
14
15
16
17
Airflow rate(m3/min)
18
19
20
21
SEZ-KD71VA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
(External static pressure 50Pa) 220-240V 50/60Hz
80
80
70
70
60
60
External static pressure (Pa)
External static pressure (Pa)
12
Limit
50
High
40
Rated point
30
Middle
20
Limit
High
50
Rated point
40
Middle
30
20
Low
Low
10
10
0
0
11
12
13
14
15
16
17
Airflow rate(m3/min)
18
19
20
11
21
70
12
13
14
15
16
17
Airflow rate(m3/min)
18
19
20
21
8-4. SEZ-KA•VA
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
SEZ-KA35VA
Corrected Air flow
1.1
Correction factor
Fan Performance
Recommended range
60
20
0
1.0
0.9
0.8
1.3
40
Correction factor
External static pressure(Pa)
(1Pa = 0.1mmAq)
80
5 7
10
15
20
25
Air flow (*/7)
Capacity
Input
Cooling
5
10
15
20
25
10
15
20
25
Air flow (*/7)
Heating
1.2
1.1
1.0
0.9
0.8
5
Air flow (*/7)
SEZ-KA50VA
Corrected Airflow
Fan Performance
Correction factor
1.1
Recommended range
60
1.0
0.9
0.8
40
1.2
0
5
10
15
20
25
10
15
20
25
Air flow (*/7)
Heating
1.1
20
5
10
15
20
Correction factor
External static pressure(Pa)
(1Pa = 0.1mmAq)
80
Capacity
Input
Cooling
25
Air flow (*/7)
71
1.0
0.9
0.8
5
Air flow (*/7)
INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW
SEZ-KA60VA
Corrected Air flow
1.1
Correction factor
Fan Performance
Recommended range
60
40
20
0
1.0
0.9
0.8
1.3
Correction factor
External static pressure(Pa)
(1Pa = 0.1mmAq)
80
5
10
15
20
25
Air flow (*/7)
Capacity
Input
Cooling
10
15
20
25
30
15
20
25
30
Air flow (*/7)
Heating
1.2
1.1
1.0
0.9
10
Air flow (*/7)
SEZ-KA71VA
Corrected Air flow
1.1
Correction factor
Fan Performance
Recommended range
60
40
20
0
1.0
0.9
0.8
1.3
Correction factor
External static pressure(Pa)
(1Pa = 0.1mmAq)
80
5
10
15
20
25
Air flow (*/7)
10
15
20
25
30
15
20
25
30
Air flow (*/7)
Heating
1.2
1.1
1.0
0.9
72
Capacity
Input
Cooling
10
Air flow (*/7)
8-5. PLA-RP·BA
8-5-1 FRESH AIR INTAKE AND BRANCH DUCT
1. Branch duct hole and fresh air intake hole (Fig. 1)
At the time of i nstallation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional
multi function casement.
When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.
When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
Unit : mm
Fresh air intake hole
Fresh air intake hole diagram
Branch duct hole
120
Indoor unit
*158
3-:2.8 burring hole
:125 burring
120
hole pitch
:100 cut
out hole
Ceiling
Drain pipe
Refrigerant pipe
100
90
100
100
130
90
Branch duct
hole diagram
(view from
either side)
*167
*155
70
350
:175 burring hole pitch
14-:2.8 burring hole
:150 cut out hole
Fig. 1
2. Fresh air intake (Installation at site)
● By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct and duct flange (option)
onto it further, fresh exterior air intake can be accomplished.
(The mounting of the multi-function casement increases the height of the ceiling plenum by 135 mm.)
73
3. Fresh air intake volume & static pressure characteristics
PLA-RP35~71BA(2)
At using multi-function casement, standard filter
50
-50
2 - inlet
-100
How to read the chart
1 - inlet
0
1
2
3
4
5
Line of chart
0
6
Field duct
characteristics
A
-200
1
Air flow rate [m3/min]
Q
Direct intake to unit
2
C
A
50
E
0
D
3
-100
A
Static pressure[Pa]
Q
-50
Q
Qa
-150
-200
0
1
2
3
4
5
6
Air flow rate [m3/min]
At using multi-function casement, high efficiency filter
50
Static pressure[Pa]
0
-50
2 - inlet
-100
-150
-200
1 - inlet
0
1
2
3
Air flow rate [m3/min]
4
5
6
74
C
-150
B
Static pressure[Pa]
0
Q…Designed fresh air intake volume
<m3/min>
A…Static pressure loss [Pa] of fresh
air intake duct at airflow rate of Q
B…Required boost pressure [Pa] of
air conditioner inlet at airflow rate
of Q
C…Required static pressure [Pa] of
booster fan at airflow rate of Q
D…Required compensation [Pa] for
static pressure loss of fresh air
intake duct to make airflow rate Q
E…Static pressure [Pa] of indoor unit
at airflow rate of Q
Qa…Estimated fresh air intake
[m3/min] without compensation of D
4. Change of outlet numbers
Indoor unit
[The optional air outlet is necessary.]
To change the air outlet number to 3-, or 2-way outlet, the
outlet number should be closed with the operational air
outlet shutter.
(When the air outlets are closed, close the vane by
removing the vane connector.)
Outlet concave
portion
Button
Vane motor
Up/down vanes
Connector
Air outlet shutter plate
(Option)
Vane motor
Connector
Button
5. Branch duct and change of outlet numbers
+ Branch duct should be connected to one of the branch duct holes on the main unit.
<4- way air flow and branch duct>
Branch
duct
Air intake
Air
outlet
+ Close the outlet on the side of branch duct and air flows in 3 directions.
<3- way air flow and branch duct>
Branch
duct
Air intake
Air
outlet
Air
outlet
closed
position
+ The outlet on the side of branch duct and one of the other outlets are closed.
Air flows in 2 directions.
<2- way air flow and branch duct>
Branch
duct
Air
Air
outlet
outlet
closed
closed
position
position
Air intake
Air
outlet
closed
position
75
PLA-RP71BA(2)
4-way airflow (horizontal vane) Round duct
4-way airflow (horizontal vane) Rectangular duct
30
Duct
Static pressure [Pa]
Static pressure [Pa]
30
20
10
High
Duct
20
10
High
Low
Low
0
0
0
2
4
6
Airflow rate [m3/min]
0
8
3-way airflow (horizontal vane) Round duct
2
80
70
70
Duct
Duct
60
Close
Static pressure [Pa]
Static pressure [Pa]
60
50
40
30
Close
50
40
30
High
20
20
High
Low
10
0
Low
10
2
4
6
8
Airflow rate [m3/min]
0
10
2-way airflow (horizontal vane) Round duct
0
100
90
90
Duct
2
Duct
80
Close
Close
10
Close
Close
Static pressure [Pa]
70
60
50
40
30
High
20
4
6
8
Airflow rate [m3/min]
2-way airflow (horizontal vane) Rectangular duct
100
80
Static pressure [Pa]
8
3-way airflow (horizontal vane) Rectangular duct
80
0
4
6
Airflow rate [m3/min]
70
60
50
40
30
20
Low
Low
High
10
10
0
0
0
2
4
6
8
10
Airflow rate [m3/min]
0
12
2
4
6
8
10
Airflow rate [m3/min]
• Use 1 of the 2 duct holes on the indoor unit.
• Air flow rate of PLA-RP35~60BA can be calculated from the airflow rate based on the characteristic
of the duct for PLA-RP71BA.
• Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow.
76
12
8-6. PLA-RP·AA
8-6-1. Fresh air intake amount
1. Adjusting the width of the air outlets
● Change of outlet numbers
[The optional air outlet shutter is necessary.]
To change the air outlet numbers to 3-, or 2-way outlet, the outlets
should be closed with the optional air outlet shutter.
When the air outlets are closed, close the vane by removing the
vane connector.
● For the portion to be cut (V-shaped groove), see the figure
below (as seen from the rear of the panel).
2. Fresh air intake (Installation at site)
● By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct and duct flange (field
supply) onto it further, fresh exterior air intake can be accomplished.
(The mounting of the multi-function casement increases the height of the ceiling plenum by 135 mm.)
77
3. Fresh air intake volume & static pressure characteristics
How to read the chart
Line of chart
Q
B
A
0
Field duct
characteristics
E
C
A
2
Q
Q…Designed fresh air intake volume
<m3/min>
A…Static pressure loss [Pa] of fresh
air intake duct at airflow rate of Q
B…Required boost pressure [Pa] of
air conditioner inlet at airflow rate
of Q
C…Required static pressure [Pa] of
booster fan at airflow rate of Q
D…Required compensation [Pa] for
static pressure loss of fresh air
intake duct to make airflow rate Q
E…Static pressure [Pa] of indoor unit
at airflow rate of Q
Qa…Estimated fresh air intake
[m3/min] without compensation of D
A
D
3
C
1
Q
Qa
8-5-2. BRANCH DUCT (Installation at site)
To be compatible with both round and rectangular branch ducts, knockout holes are designed to fit to both shapes for flexible
on-site installation.
78
Branch duct air flow rate/static pressure characteristics
PLA-RP35AA
4-way air flow (horizontal vane) Rectangular duct
4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct
3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct
2-way air flow (horizontal vane) Round duct
79
PLA-RP50AA
PLA-RP60AA
4-way air flow (horizontal vane) Rectangular duct
4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct
3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct
2-way air flow (horizontal vane) Round duct
80
PLA-RP71AA
4-way air flow (horizontal vane) Round duct
30
Static pressure [Pa]
Static pressure [Pa]
4-way air flow (horizontal vane) Rectangular duct
20
High
10
Low
0
1
2
3
4
5
6
30
20
High
10
Low
0
1
2
3
Air flow rate [m /min]
6
3-way air flow (horizontal vane) Round duct
60
60
Static pressure [Pa]
50
40
High
30
20
Low
10
0
1
2
3
4
5
6
7
8
50
40
High
30
20
Low
10
0
9
1
2
3
4
Air flow rate [m /min]
2-way air flow (horizontal vane) Rectangular duct
90
90
80
80
Static pressure [Pa]
100
70
60
High
40
Low
30
20
10
0
6
7
2-way air flow (horizontal vane) Round duct
100
50
5
70
60
High
50
40
Low
30
20
10
1
2
3
4
5
6
7
8
9
10
8
Air flow rate [m3/min]
3
Static pressure [Pa]
5
3
3-way air flow (horizontal vane) Rectangular duct
Static pressure [Pa]
4
Air flow rate [m /min]
3
0
11
Air flow rate [m3/min]
1
2
3
4
5
6
Air flow rate [m3/min]
81
7
9
8-7. PCA-RP·KA
8-7-1. Fresh air intake amount & static pressure characteristics
PCA-RP60, 71KA
50
50
0
0
Static pressure[Pa]
-50
-100
-150
-200
-250
-100
-150
-200
-250
-300
2
3
0
4
1
2
3
4
Airflow rate[m³/min]
Airflow rate[m³/min]
How to read the chart
Q
B
A
0
Duct characteristics
at site
2
Q
3
Q
Qa
82
C
Curve in the
graphs
1
C
A
1
E
0
D
-300
-50
A
Static pressure[Pa]
PCA-RP50KA
Q…Designed amount of fresh air intake
<m3/min>
A…Static pressure loss of fresh air
intake duct system with airflow
amount Q
<Pa>
B…Forced static pressure at air conditioner inlet with airflow amount Q
<Pa>
C…Static pressure of booster fan with
airflow amount Q
<Pa>
D…Static pressure loss increase
amount of fresh air intake duct system for airflow amount Q <Pa>
E…Static pressure of indoor unit with
airflow amount Q
Qa…Estimated amount of fresh air
intake without D
<m3/min>
8-8. PEAD-RP·JA(L), EA, EA2, GA
8-8-1. Fan performance
PEAD-RP·JA(L)
PEAD-RP35JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP35JA(L)
(External static pressure 35Pa) 220-240V 50Hz
120
60
110
Rated point
100
Limit
External static pressure (Pa)
External static pressure (Pa)
50
40
Rated point
High
30
Middle
20
Low
10
Limit
90
High
80
70
Middle
60
50
Low
40
30
20
10
0
7
9
11
13
15
17
19
0
21
7
9
11
Airflow rate(m3/min)
13
PEAD-RP35JA(L)
(External static pressure 50Pa) 220-240V 50Hz
17
19
21
PEAD-RP35JA(L)
(External static pressure 150Pa) 220-240V 50Hz
70
170
160
Rated point
150
60
140
Limit
External static pressure (Pa)
External static pressure (Pa)
15
Airflow rate(m3/min)
Rated point
50
High
40
Middle
30
Low
20
Limit
130
High
120
110
100
Middle
90
80
70
Low
60
50
40
30
10
20
10
0
7
9
11
13
15
17
19
0
21
Airflow rate(m3/min)
90
80
External static pressure (Pa)
Rated point
Limit
High
60
50
Middle
40
Low
30
20
10
0
7
9
11
13
15
Airflow rate(m3/min)
9
11
13
15
Airflow rate(m3/min)
PEAD-RP35JA(L)
(External static pressure 70Pa) 220-240V 50Hz
70
7
17
19
21
83
17
19
21
PEAD-RP50JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP50JA(L)
(External static pressure 35Pa) 220-240V 50Hz
130
70
120
110
60
50
High
40
Rated point
Middle
30
Low
20
Rated point
Limit
100
External static pressure (Pa)
External static pressure (Pa)
Limit
90
High
80
70
Middle
60
50
Low
40
30
20
10
10
0
9
14
0
19
9
14
19
Airflow rate(m3/min)
Airflow rate(m3/min)
PEAD-RP50JA(L)
(External static pressure 50Pa) 220-240V 50Hz
PEAD-RP50JA(L)
(External static pressure 150Pa) 220-240V 50Hz
180
80
170
160
70
Middle
40
Low
20
External static pressure (Pa)
External static pressure (Pa)
Rated point
50
High
140
High
60
30
Rated point
150
Limit
Limit
130
120
110
Middle
100
90
80
Low
70
60
50
40
10
30
20
0
9
14
10
19
0
Airflow rate(m3/min)
9
14
Airflow rate(m3/min)
PEAD-RP50JA(L)
(External static pressure 70Pa) 220-240V 50Hz
100
90
External static pressure (Pa)
80
Limit
Rated point
70
High
60
50
Middle
40
30
Low
20
10
0
9
14
19
Airflow rate(m3/min)
84
19
PEAD-RP60JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP60JA(L)
(External static pressure 35Pa) 220-240V 50Hz
120
60
110
50
Rated point
100
External static pressure (Pa)
External static pressure (Pa)
Limit
40
Rated point
30
High
20
Middle
90
Limit
High
80
70
Middle
60
50
Low
40
30
Low
10
20
10
0
10
15
20
25
0
10
30
15
Airflow rate(m3/min)
20
PEAD-RP60JA(L)
(External static pressure 50Pa) 220-240V 50Hz
170
160
Rated point
150
Limit
140
Rated point
50
External static pressure (Pa)
External static pressure (Pa)
30
PEAD-RP60JA(L)
(External static pressure 150Pa) 220-240V 50Hz
70
60
25
Airflow rate(m3/min)
High
40
Middle
30
20
Low
High
130
Limit
120
110
100
Middle
90
80
70
60
Low
50
40
30
10
20
10
0
10
15
20
25
0
30
Airflow rate(m3/min)
90
80
Rated point
External static pressure (Pa)
Limit
High
60
50
Middle
40
30
Low
20
10
0
10
15
20
15
20
Airflow rate(m3/min)
PEAD-RP60JA(L)
(External static pressure 70Pa) 220-240V 50Hz
70
10
25
30
Airflow rate(m3/min)
85
25
30
PEAD-RP71JA(L)
(External static pressure 100Pa) 220-240V 50Hz
PEAD-RP71JA(L)
(External static pressure 35Pa) 220-240V 50Hz
70
130
120
60
High
110
Rated point
50
External static pressure (Pa)
External static pressure (Pa)
100
Limit
High
40
Rated point
30
Middle
20
Low
Limit
90
Middle
80
70
60
Low
50
40
30
10
20
10
0
10
15
20
25
0
30
10
15
Airflow rate(m3/min)
20
25
30
Airflow rate(m3/min)
PEAD-RP71JA(L)
(External static pressure 50Pa) 220-240V 50Hz
PEAD-RP71JA(L)
(External static pressure 150Pa) 220-240V 50Hz
90
180
170
High
160
80
Rated point
150
140
External static pressure (Pa)
External static pressure (Pa)
70
Limit
60
High
Rated point
50
Middle
40
30
Low
20
130
Middle
Limit
120
110
100
90
80
Low
70
60
50
40
30
10
20
10
0
10
15
20
25
0
30
Airflow rate(m3/min)
100
90
High
External static pressure (Pa)
80
Limit
Rated point
70
Middle
50
40
Low
30
20
10
0
10
15
20
15
20
Airflow rate(m3/min)
PEAD-RP71JA(L)
(External static pressure 70Pa) 220-240V 50Hz
60
10
25
30
Airflow rate(m3/min)
86
25
30
8-8-2. Fan performance and corrected air flow
PEAD-RP35EA2 PEAD-RP50EA
Fan Performance <30Pa>
Corrected Air Flow
120
100
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
140
80
60
40
20
6
8
Cooling
1.0
0.9
0.8
8
10
10 12 14 16 18 20
AirFlow (CMM)
Fan Performance <70Pa>
160
12 14 16 18
Airflow (CMM)
20
22
12 14 16 18
Airflow (CMM)
20
22
Heating
1.3
140
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
1.1
Capacity
input
120
100
80
60
40
1.2
1.1
1.0
0.9
0.8
8
20
8
10
10 12 14 16 18 20 22
AirFlow (CMM)
Fan Performance <30Pa>
120
Correction factor
100
80
60
40
20
8
140
External static pressure (Pa)
(1Pa 0.1mmAq)
Corrected Air Flow
1.1
Capacity
input
Cooling
1.0
0.9
0.8
12 14 16 18 20 22
Airflow (CMM)
10 12 14 16 18 20 22 24
AirFlow (CMM)
24 26
Heating
Fan Performance <70Pa>
1.3
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
PEAD-RP60EA
120
100
80
60
40
1.2
1.1
1.0
0.9
0.8
12 14 16 18 20 22 24
Airflow (CMM)
20
10 12 14 16 18 20 22 24 26
AirFlow (CMM)
87
26
PEAD-RP71EA
Fan performance <70Pa>
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa = 0.1mmAq)
External static pressure (Pa)
(1Pa = 0.1mmAq)
Recommended range
200
180
160
140
Hi
Lo
120
100
80
60
40
20
180
160
140
120
80
60
40
20
12 16 20 24 28 32
12 16 20 24 28 32
Air flow (C MM)
A ir f low ( C MM)
Corrected Air Flow
Capacity
Input
Cooling
Heating
1.3
1.2
Correction factor
1.1
Correction factor
Hi
Lo
100
1.0
0.9
0.8
12
16
20
24
28
1.1
1.0
0.9
32
Air flow (CMM)
0.8
12
16
20
24
28
Air flow (CMM)
PEAD-RP60GA
88
32
PEAD-RP71GA
8-9. PEA-RP·EA
8-9-1. Fan performance and corrected airflow
PEA-RP71EA
Corrected Airflow
1.05
Correction factor
Fan Performance
Recommended range
Hi
150
1.0
0.95
0.9
1.2
100
50
0
15 17 20
17 20
25
30
25
30
Airflow (CMM)
Lo
Correction factor
External static pressure(Pa)
(1Pa = 0.1mmAq)
200
25
30
35
Airflow (CMM)
Heating
1.15
1.1
1.05
1.0
0.95
17 20
Airflow (CMM)
89
Capacity
Input
Cooling
NOISE CRITERION CURVES
9
MFZ-KA25VA
MFZ-KA35VA
Super High
SPL(dB(A))
COOLING
37
HEATING
37
Super High
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
Test conditions,
Cooling : Dry-bulb temperature 27°CWet-bulb temperature 19°C
Heating : Dry-bulb temperature 20°CWet-bulb temperature 15°C
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
FAN SPEED FUNCTION
LINE
4000
SPL(dB(A))
COOLING
38
HEATING
38
8000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
MFZ-KA50VA
FAN SPEED FUNCTION
Super High
SPL(dB(A))
COOLING
43
HEATING
44
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
Test conditions,
Cooling : Dry-bulb temperature 27°CWet-bulb temperature 19°C
Heating : Dry-bulb temperature 20°CWet-bulb temperature 15°C
90
80
70
INDOOR UNIT
NC-70
MICROPHONE
60
WALL
NC-60
1m
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
LINE
Test conditions,
Cooling : Dry-bulb temperature 27°CWet-bulb temperature 19°C
Heating : Dry-bulb temperature 20°CWet-bulb temperature 15°C
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
FAN SPEED FUNCTION
8000
BAND CENTER FREQUENCIES, Hz
90
1m
8000
<50Hz>
SLZ-KA25VAL
SLZ-KA25VA
NOTCH SPL(dB)
High
37
Medium
31
Low
28
LINE
NOTCH SPL(dB)
High
38
Medium
33
Low
29
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
20
63
125
250
NC-20
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
10
<50Hz>
SLZ-KA35VAL
SLZ-KA35VA
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
<50Hz>
SLZ-KA50VAL
SLZ-KA50VA
NOTCH SPL(dB)
High
39
Medium
34
Low
30
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
UNIT
80
CEILING
70
NC-70
60
NC-60
1.5m
50
NC-50
40
NC-40
MICROPHONE
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher
by about 2 dB than the indicated level during cooling and heating operation.
91
NOISE CRITERION CURVES
SEZ-KD25VA(L)
NOTCH
External static pressure: 5Pa
High
Middle
Low
SPL(dB)
29
25
22
LINE
SEZ-KD25VA(L)
External static pressure: 15Pa
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
NC-20
125
250
500
1000
2000
4000
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
SEZ-KD25VA(L)
External static pressure: 35Pa
NOTCH SPL(dB)
High
31
Middle
28
Low
24
LINE
500
SEZ-KD25VA(L)
External static pressure: 50Pa
1000
2000
4000
8000
NOTCH SPL(dB)
High
33
Middle
29
Low
25
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
250
BAND CENTER FREQUENCIES, Hz
90
10
NC-20
125
BAND CENTER FREQUENCIES, Hz
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
NOTCH SPL(dB)
High
30
Middle
26
Low
23
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
BAND CENTER FREQUENCIES, Hz
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than indicated level in actual use due to surrounding echoes. The sound level can be higher by
about 2 dB than the indicated level during cooling and heating operation.
92
SEZ-KD35VA(L)
External static pressure: 5Pa
NOTCH SPL(dB)
High
33
Middle
28
Low
23
LINE
SEZ-KD35VA(L)
External static pressure: 15Pa
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
NC-20
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
80
10
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
SEZ-KD35VA(L)
External static pressure: 35Pa
NOTCH SPL(dB)
High
34
Middle
29
Low
24
LINE
500
SEZ-KD35VA(L)
External static pressure: 50Pa
1000
2000
4000
8000
NOTCH SPL(dB)
High
35
Middle
31
Low
25
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
250
BAND CENTER FREQUENCIES, Hz
90
10
NC-20
125
BAND CENTER FREQUENCIES, Hz
20
LINE
90
90
20
NOTCH SPL(dB)
High
33
Middle
28
Low
23
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
BAND CENTER FREQUENCIES, Hz
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than indicated level in actual use due to surrounding echoes. The sound level can be higher by
about 2 dB than the indicated level during cooling and heating operation.
93
SEZ-KD50VA(L)
External static pressure: 5Pa
NOTCH SPL(dB)
High
36
Middle
33
Low
29
LINE
SEZ-KD50VA(L)
External static pressure: 15Pa
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
NC-20
125
250
500
1000
2000
4000
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
SEZ-KD50VA(L)
External static pressure: 35Pa
NOTCH SPL(dB)
High
38
Middle
35
Low
31
LINE
500
SEZ-KD50VA(L)
External static pressure: 50Pa
1000
2000
4000
8000
NOTCH SPL(dB)
High
39
Middle
36
Low
32
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
250
BAND CENTER FREQUENCIES, Hz
90
10
NC-20
125
BAND CENTER FREQUENCIES, Hz
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
NOTCH SPL(dB)
High
37
Middle
34
Low
30
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher
by about 2 dB than the indicated level during cooling and heating operation.
94
SEZ-KD60VA(L)
External static pressure: 5Pa
NOTCH SPL(dB)
High
37
Middle
33
Low
29
LINE
SEZ-KD60VA(L)
External static pressure: 15Pa
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
NC-20
125
250
500
1000
2000
4000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
BAND CENTER FREQUENCIES, Hz
SEZ-KD60VA(L)
External static pressure: 35Pa
NOTCH SPL(dB)
High
39
Middle
35
Low
31
LINE
500
SEZ-KD60VA(L)
1000
2000
4000
8000
NOTCH SPL(dB)
High
39
Middle
36
Low
32
LINE
90
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
250
External static pressure: 50Pa
80
10
NC-20
BAND CENTER FREQUENCIES, Hz
90
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
NOTCH SPL(dB)
High
38
Middle
34
Low
30
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
8000
63
BAND CENTER FREQUENCIES, Hz
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher
by about 2 dB than the indicated level during cooling and heating operation.
95
SEZ-KD71VA(L)
External static pressure: 5Pa
NOTCH SPL(dB)
High
39
Middle
34
Low
29
LINE
SEZ-KD71VA(L)
External static pressure: 15Pa
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
NC-20
125
250
500
1000
2000
4000
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
SEZ-KD71VA(L)
External static pressure: 35Pa
NOTCH SPL(dB)
High
41
Middle
36
Low
31
LINE
500
SEZ-KD71VA(L)
External static pressure: 50Pa
1000
2000
4000
8000
NOTCH SPL(dB)
High
42
Middle
37
Low
32
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
250
BAND CENTER FREQUENCIES, Hz
90
10
NC-20
125
BAND CENTER FREQUENCIES, Hz
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
NOTCH SPL(dB)
High
40
Middle
35
Low
30
80
70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
BAND CENTER FREQUENCIES, Hz
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
Aux. duct
96
test unit
1m
2m
Measurement location
1.5m
NOTE: The sound level is measured in an anechoic room where echoes
are few, when compressor stops. The sound may be bigger than
the indicated level in actual use due to surrounding echoes. The
sound level can be higher by about 2 dB than the indicated level
during cooling and heating operation.
SEZ-KC25VA
<50Hz>
NOTCH SPL(dB)
High
36
Low
25
70
High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
Low speed
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Appro
Approximate minimum
audible limit on continuous noise
0
63
125
250
500
1000
2000
4000
8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
Aux.duct
2m
1.5m
1m
Measurement location
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher
by about 2 dB than the indicated level during cooling and heating operation.
97
<50Hz>
SEZ-KA35VA
NOTCH SPL(dB)
High
35
Low
30
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
10
NOTCH SPL(dB)
High
39
Low
31
LINE
90
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
20
<50Hz>
SEZ-KA50VA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
BAND CENTER FREQUENCIES, Hz
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
<50Hz>
SEZ-KA60VA
SEZ-KA71VA
NOTCH SPL(dB)
High
43
Low
32
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
UNIT
80
70
NC-70
60
NC-60
External static
pressure 30Pa
50
1.5m
NC-50
40
MICROPHONE
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound
may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher
by about 2 dB than the indicated level during cooling and heating operation.
98
PLA-RP35BA
NOTCH SPL(dB)
High
31
Medium1
29
Medium2
28
Low
27
LINE
PLA-RP50BA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
BAND CENTER FREQUENCIES, Hz
PLA-RP60BA
NOTCH SPL(dB)
High
32
Medium1
31
Medium2
29
Low
28
LINE
500
PLA-RP71BA
PLA-RP71BA2
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
250
1000
2000
4000
8000
NOTCH SPL(dB)
High
34
Medium1
32
Medium2
30
Low
28
LINE
90
80
10
NC-20
BAND CENTER FREQUENCIES, Hz
90
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
NOTCH SPL(dB)
High
32
Medium1
31
Medium2
29
Low
28
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
8000
BAND CENTER FREQUENCIES, Hz
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
99
4000
8000
NOTCH SPL(dB)
High
31
Medium1
29
Medium2
28
Low
27
PLA-RP35AA
LINE
PLA-RP50AA
PLA-RP60AA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
BAND CENTER FREQUENCIES, Hz
125
NC-20
250
500
1000
CEILING
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
1.5m
70
NC-70
MICROPHONE
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
125
NC-20
250
500
1000
2000
8000
UNIT
80
63
4000
LINE
90
10
2000
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB)
High
34
Medium1
32
Medium2
30
Low
28
PLA-RP71AA
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
20
NOTCH SPL(dB)
High
33
Medium1
31
Medium2
29
Low
28
4000
8000
BAND CENTER FREQUENCIES, Hz
100
PEAD-RP35JA(L)
External static pressure 35Pa
80
70
2m
2m
Aux.duct
NC-70
1.5m
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
Ceiling concealed
High
Middle
Low
60
NC-60
Measurement location
50
NC-50
Noise level at anechoic room (Low-Middle-High) Unit: dB(A)
40
NC-40
Exrernal static pressure
Model
30
35Pa
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
50Pa
70Pa
100Pa
150Pa
PEAD-RP35JA(L) 23-26-29
23-27-30 24-28-31
26-29-33
29-33-37
PEAD-RP50JA(L) 25-30-34
26-31-35 28-32-36
29-33-37
31-35-39
PEAD-RP60JA(L) 25-28-32
25-29-33 26-30-34
27-31-35
29-34-38
PEAD-RP71JA(L) 25-29-34
26-30-34 27-31-35
28-32-36
30-35-39
8000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
80
70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
External static pressure 100Pa
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
500
1000
2000
80
60
0
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
20
125
4000
8000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
NC-20
10
0
8000
High
Middle
Low
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
8000
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
101
High
Middle
Low
4000
8000
PEAD-RP50JA(L)
External static pressure 35Pa
70
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
External static pressure 100Pa
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
70
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
2000
4000
8000
4000
8000
BAND CENTER FREQUENCIES, Hz
102
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
1000
70
0
8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
500
80
60
20
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
125
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
NC-20
10
0
8000
High
Middle
Low
4000
8000
PEAD-RP60JA(L)
External static pressure 35Pa
70
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
External static pressure 100Pa
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
70
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
2000
4000
8000
4000
8000
BAND CENTER FREQUENCIES, Hz
103
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
1000
70
0
8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
500
80
60
20
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
125
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
NC-20
10
0
8000
High
Middle
Low
4000
8000
PEAD-RP71JA(L)
External static pressure 35Pa
70
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
External static pressure 100Pa
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
63
BAND CENTER FREQUENCIES, Hz
70
NC-70
NC-60
50
NC-50
40
NC-40
30
NC-30
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
0
63
125
250
500
1000
2000
2000
4000
8000
4000
8000
BAND CENTER FREQUENCIES, Hz
104
High
Middle
Low
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Approximate
minimum audible
limit on continuous
noise
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
80
1000
70
0
8000
BAND CENTER FREQUENCIES, Hz
External static pressure 70Pa
500
80
60
20
250
External static pressure 150Pa
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
125
BAND CENTER FREQUENCIES, Hz
High
Middle
Low
External static pressure 50Pa
NC-20
10
0
8000
High
Middle
Low
4000
8000
Noise level at an echoic room (Low-High)
Unit : dB(A)
External static pressure
130Pa
70Pa
30Pa
38-44*
36-40
36-40
38-44*
-
Model
PEAD-RP35EA2
PEAD-RP50EA
PEAD-RP60EA
37-41
39-46*
-
-
37-41
40-45*
PEAD-RP71EA
* Optional motor
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
PEAD-RP35EA2
PEAD-RP50EA
(External static
pressure 30Pa)
70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
PEAD-RP35EA2
PEAD-RP50EA
70
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
0
Approximate minimum
audible limit on
continuous noise
63
125
250
500
1000
2000
4000
8000
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
0
Approximate minimum
audible limit on
continuous noise
63
OCTAVE BAND CENTER FREQUENCIES (Hz)
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
(External static
pressure 30Pa)
NC60
50
NC50
40
NC40
30
NC30
20
NC20
Approximate minimum
audible limit on
continuous noise
63
125
250
500
1000
2000
4000
500
PEAD-RP60EA
High
Low
0
250
70
60
10
125
1000
2000
4000
8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa
PEAD-RP60EA
70
(External static
pressure 70Pa)
8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 70Pa)
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
0
Approximate minimum
audible limit on
continuous noise
63
125
250
500
1000
2000
4000
OCTAVE BAND CENTER FREQUENCIES (Hz)
105
8000
PCA-RP50KA
NOTCH SPL(dB)
40
High
37
Medium1
34
Medium2
32
Low
PCA-RP60KA
LINE
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
80
10
LINE
90
90
20
NOTCH SPL(dB)
High
40
Medium1
37
Medium2
35
Low
33
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
8000
63
125
BAND CENTER FREQUENCIES, Hz
PCA-RP71KA
NOTCH SPL(dB)
High
41
Medium1
39
Medium2
37
Low
35
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
90
80
70
NC-70
ceiling
1m
60
NC-60
1m
about 1.4m
50
NC-50
MICROPHONE
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
106
unit
ceiling
1m
1m
unit
about 1.4m
MICROPHONE
PCA-RP50GA
NOTCH SPL(dB)
42
High
40
Medium1
38
Medium2
37
Low
LINE
PCA-RP50GA2
PCA-RP60GA
PCA-RP71GA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
BAND CENTER FREQUENCIES, Hz
PEA-RP71EA
NOTCH SPL(dB)
High
55
Low
52
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
250
500
1000
UNIT
1m
1m
MICROPHONE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
10
125
NC-20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
BAND CENTER FREQUENCIES, Hz
2000
BAND CENTER FREQUENCIES, Hz
90
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
90
NOTCH SPL(dB)
High
43
Medium1
41
Medium2
39
Low
37
NC-20
8000
107
External static
pressure 125Pa
4000
8000
SUZ-KA35VA
SUZ-KA35VAH
SUZ-KA25VA
SUZ-KA25VAH
High
Med.
SPL(dB(A))
COOLING
46
HEATING
46
High
Med.
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
Test conditions,
Cooling : Dry-bulb temperature 35°CWet-bulb temperature (24°C)
Heating : Dry-bulb temperature 7°CWet-bulb temperature 6°C
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
FAN SPEED FUNCTION
LINE
500
1000
2000
4000
High
SPL(dB(A))
COOLING
53
HEATING
55
LINE
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
1m
Test conditions,
Cooling : Dry-bulb temperature 35°CWet-bulb temperature (24°C)
Heating : Dry-bulb temperature 7°CWet-bulb temperature 6°C
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
60
MICROPHONE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
125
NC-20
250
500
1000
2000
4000
LINE
NC-70
500
1000
OUTDOORUNIT
FAN SPEED FUNCTION
63
48
2000
4000
BAND CENTER FREQUENCIES, Hz
SUZ-KA50VA
SUZ-KA60VA
SUZ-KA71VA
10
HEATING
70
10
8000
BAND CENTER FREQUENCIES, Hz
20
47
80
NC-20
250
SPL(dB(A))
COOLING
Test conditions,
Cooling : Dry-bulb temperature 35°CWet-bulb temperature (24°C)
Heating : Dry-bulb temperature 7°CWet-bulb temperature 6°C
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)
FAN SPEED FUNCTION
8000
BAND CENTER FREQUENCIES, Hz
108
8000
10
OPTIONAL PARTS
10-1. INDOOR UNIT
Part Name
Remote sensor
Multiple remote controller adapter
Applicable model
Remote on/off adapter
Model Name
PAC-SE41TS-E
PAC-SA88HA-E(1pc.)
PAC-725AD(10pcs.)
PAC-SE55RA-E
Remote operation adapter
PAC-SF40RM-E
MA & contact terminal interface
Anti-allergy enzyme filter(Air cleaning filter)
Drain pump
Wireless remote controller
Signal receiver unit
Air filter
Decoration panel
Decoration panel with wireless remote controller
Decoration panel with wired remote controller
Automatic filter elevation panel
i-see sensor corner panel
Wireless signal receiver
Space panel
Air outlet shutter plate
Multi-function casement
Flange for fresh air intake
High-efficiency filter element (PAC-SH53TM-E is needed.)
Multi-functional casement
High-efficiency filter element (PAC-SG03TM-E is needed.)
Grille + Wireless remote controller
Grille + Wired remote controller
Air outlet shutter plate (20 set, 2pcs/set)
Wireless remote controller kit
MAC-397IF-E
MAC-415FT-E
PAC-KE07DM-E
PAR-SL9CA-E
PAR-SA9CA-E
PAC-1000FT
PLP-6BA
PLP-6BALM
PLP-6BAM
PLP-6BAJ
PAC-SA1ME-E
PAR-SA9FA-E
PAC-SH48AS-E
PAC-SH51SP-E
PAC-SH53TM-E
PAC-SH65OF-E
PAC-SH59KF-E
PAC-SG03TM-E
PAC-SG01KF
PLP-6AALM
PLP-6AAMD
PAC-SG06SP-E
PAR-SL99B-E
PAR-SL94B-E
PAC-SH20DM-E
PAC-SH21DM-E
PAC-SH83DM-E
PAC-SH85DM-E
PAC-SH84DM-E
PAC-SE80KF-E
PAC-SE81KF-E
PAC-SH88KF-E
PAC-SH89KF-E
PAC-SK005MT-F
PAC-KE03DM-F
PAC-SK010DK
PAC-KE92TB-E
PAC-KE93TB-E
All models excpet wireless
remote controller use model
All models
MFZ-KA·VA
SEZ-KD·VA(L)
SEZ-KC25VA
SEZ-KA35/50/60/71VA
SEZ-KA·VA
Drain pump
High-efficiency filter
Motor (for high external static pressure)
Drain pump
Insulation kit
Filter box
All models
except MFZ-KA·VA
PLA-RP·BA(2)
PLA-RP·AA
PCA-RP·GA(2)
PCA-RP·KA
PCA-RP50, 60GA(2)
PCA-RP71GA
PCA-RP50KA
PCA-RP60KA
PCA-RP71KA
PCA-RP50GA(2)
PCA-RP60, 71GA
PCA-RP50KA
PCA-RP60, 71KA
PEAD-RP71EA
PEAD-RP·EA, EA2
PEAD-RP·GA
PEAD-RP35, 50JA(L)
PEAD-RP60, 71JA(L)
10-2. OUTOOR UNIT
Part Name
Drain socket
Drain socket assembly
Model Name
MAC-851DS
MAC-811DS
109
Applicable model
SUZ-KA25, 35VA
SUZ-KA50, 60, 71VA
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING
Distributed in Oct. 2009 No.OCS03 REVISED EDITION-C
Distributed in Nov. 2007 No.OCS03 REVISED EDITION-B
Distributed in May 2007 No.OCS03 REVISED EDITION-A
Distributed in May 2006 No.OCS03 PDF 8
Made in Japan
CO., LTD.
PDF 6
PDF 7
PDF 7
New publication, effective Oct. 2009
Specifications subject to change without notice.