SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS October 2009 No. OCS03 REVISED EDITION-C TECHNICAL DATA BOOK R410A INVERTER <Indoor unit> [Model names] <Outdoor unit> [Model names] MFZ-KA·VA SLZ-KA·VA(L) SEZ-KC·VA SEZ-KA·VA SEZ-KD·VA(L) PLA-RP·BA PLA-RP·AA PCA-RP·KA PCA-RP·GA(2) PEAD-RP·JA(L) PEAD-RP·EA(2) PEAD-RP·GA PEA-RP·EA Revision: • PLA-RP71BA2, PCA-RP·KA, and PEAD-RP·JA(L) are added, and outdoor unit data has been modified in REVISED EDITION-C. • Some descriptions have been modified. • Please void OCS03 REVISED EDITION-B. SUZ-KA25/35/50/60/71VA SUZ-KA25/35VAH CONTENTS 1. REFERENCE SERVICE MANUAL ............................................. 2 2. SPECIFICATIONS....................................................................... 3 3. OUTLINES AND DIMENSIONS ................................................ 15 4. WIRING DIAGRAM ................................................................... 36 5. REFRIGERANT SYSTEM DIAGRAM ...................................... 54 6. PERFORMANCE CURVES ...................................................... 58 7. APPLICABLE EXTENSION PIPE FOR EACH MODEL .......... 62 8. AIR FLOW DATA ...................................................................... 64 9. NOISE CRITERION CURVES .................................................. 90 10. OPTIONAL PARTS ................................................................. 109 kW Model 1 REFERENCE SERVICE MANUAL For information on service, please refer to the service manual as follows. 1-1. Indoor Unit Model name Service Ref. Service Manual No. SLZ-KA25/35/50VA SLZ-KA25/35/50VAL SLZ-KA25/35/50VA(1).TH SLZ-KA25/35/50VAL(1).TH OC320 SEZ-KA35/50/60/71VA SEZ-KA35/50/60/71VA.TH OC321 SEZ-KC25VA SEZ-KC25VA.W MEE04K350 SEZ-KD25/35/50/60/71VA SEZ-KD25/35/50/60/71VAL SEZ-KD25/35/50/60/71VA.TH SEZ-KD25/35/50/60/71VAL.TH HWE07110 MFZ-KA25/35/50VA-E1 MFZ-KA25/35/50VA-E1 OB409 MFZ-KA25/35/50VA-A1 MFZ-KA25/35/50VA-A1 OB410 PLA-RP35/50/60/71BA(1).UK PLA-RP71BA2.UK OCH412 OCB412 PLA-RP35/50/60/71BA(1) OCH416 OCB416 PLA-RP35/50/60/71BA PLA-RP35/50/60/71AA.UK OC335 PLA-RP35/50/60/71AA OC327 PLA-RP35/50/60/71AA OCH454 OCB454 PCA-RP50/60/71KA PCA-RP50/60/71KA PCA-RP50/60/71GA PCA-RP50GA2 PCA-RP50/60/71GA (#1) PCA-RP50GA2 (#1) PEAD-RP35/50/60/71JA(L) PEAD-RP35/50/60/71JA(L).UK PEAD-RP35/50/60/71JA(L)R1.UK HWE08130 BWE08240 BWE09220 PEAD-RP50/60/71EA PEAD-RP35EA2 PEAD-RP50/60/71EA.UK PEAD-RP35EA2.UK HWE05210 PEAD-RP60/71GA PEAD-RP60/71GA.UK HWE05060 PEA-RP71EA PEA-RP71EA.TH-A OC328 OC326 1-2. Outdoor Unit Model name Service Ref. Service Manual No. SUZ-KA25/35/50/60/71VA SUZ-KA25/35VAH SUZ-KA25/35VA(R1).TH SUZ-KA25/35VAH(R1).TH SUZ-KA50/60/71VA(1).TH SUZ-KA50/60VAR2.TH OC322 SUZ-KA25/35/50/60/71VA SUZ-KA25/35VA(R1).TH-A SUZ-KA50/60/71VA(1).TH-A SUZ-KA50/60VAR2.TH-A OC323 (Note) When you connect P series indoor units with SUZ, always make sure to follow the piping size of SUZ. Never use bigger sized pipings in order to ensure not only the system performance but also for your safety. 2 2 SPECIFICATIONS 2-1. FLOOR STANDING TYPE Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Model name Power supply Indoor unit Outdoor unit Refrigerant pipe size Refrigerant pipe length NOTE: Btu/h kW kW Btu/h kW kW Total input COP Energy label class Booster heater kW Phase : Cycle Hz Voltage V Breaker size A Air flow at cooling CMM (Low-Medium-High-Super High) CFM Air flow at heating CMM (Low-Medium-High-Super High) CFM External static pressure Pa Sound level at cooling dB(A) (Low-Medium-High-Super High) Sound level at heating dB(A) (Low-Medium-High-Super High) External finish (Panel) Dimension W : mm Unit (Panel) D : mm H : mm W : inch D : inch H : inch Weight kg Unit (Panel) lbs Air flow at cooling CMM (Low - High) CFM Air flow at heating CMM (Low - High) CFM Sound level at cooling dB(A) (Low - High) Sound level at heating dB(A) (Low - High) External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch Weight kg lbs Gas side O.D. mm inch Liquid side . mm inch m Height difference Length m 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor Upper Lower Upper Heating Lower Cooling limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. MFZ-KA25VA SUZ-KA25VA(H) 8,500 2.5(0.9-3.4) 0.58 4.31 A 0.66 11,600 3.4(0.9-5.1) 0.835 4.07 A — 1 50 230 10 4.8 - 5.8 - 7.1 - 8.7 170 - 205 - 250 - 310 5.0 - 6.2 - 7.6 - 9.1 180 - 220 - 270 - 320 0 22 - 27 - 32 - 37 MFZ-KA35VA SUZ-KA35VA(H) 11,900 3.5(0.9-3.9) 1.09 3.21 A 0.65 13,600 4.0(0.9-6.2) 1.10 3.64 A — 1 50 230 10 5.0 - 6.1 - 7.4 - 9.1 180 - 215 - 260 - 320 5.2 - 6.2 - 7.8 - 9.5 185 - 220 - 275 - 335 0 23 - 28 - 33 - 38 MFZ-KA50VA SUZ-KA50VA 16,400 4.8(0.9-5.4) 1.55 3.1 B 0.63 20,500 6.0(0.9-7.9) 1.86 3.23 C — 1 50 230 20 7.1 - 7.9 - 9.2 - 10.7 250 - 280 - 325 - 380 7.4 - 8.8 - 9.8 - 11.8 260 - 310 - 345 - 415 0 32 - 35 - 39 - 43 22 - 27 - 32 - 37 25 - 28 - 33 - 38 32 - 35 - 39 - 44 34.3 1,210 32.3 1,140 46 White Munsell 1.0Y 9.2/0.2 700 200 600 27 - 5/8 7 - 7/8 23 - 5/8 14 31 33.4 1,180 33.4 1,180 47 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 46 48 53 - 55 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 30 66 9.52 3/8 6.35 1/4 Max. 12 Max. 20 Ivory Munsell 3.0Y 7.8/1.1 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 33 73 9.52 3/8 6.35 1/4 Max. 12 Max. 20 840 330 850 33 - 1/16 13 33 - 7/16 53 117 12.7 1/2 6.35 1/4 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA25, KA35VA KA50 KA25,KA35VAH 46°C D.B. 46°C D.B. 43°C D.B. -10°C D.B. -15°C D.B. -10°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. -20°C D.B. ,-21°C W.B. 3 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz 2-2. CEILING CASSETTE TYPE Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Model name Power supply Indoor unit Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low - Medium - High) External static pressure Sound level (Low - Medium - High) External finish (Panel) Dimension Unit(Panel) Weight Unit (Panel) Field drain pipe O.D. Outdoor unit Air flow at cooling (Low - High) Air flow at heating (Low - High) Sound level at cooling (Low - High) Sound level at heating (Low - High) External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length SLZ-KA25VA(L) SUZ-KA25VA 8,500 2.5(0.9 - 3.2) 0.69 3.62 A 0.86 10,200 3.0(0.9 - 4.5) 0.83 3.61 A — 1 50 230 10 8 - 9 - 10 280 - 320 - 355 0 28 - 31 - 37 SLZ-KA35VA(L) SUZ-KA35VA 11,900 3.5(1.0 - 3.9) 1.06 3.30 A 0.77 13,600 4.0(0.9 - 5.0) 1.10 3.64 A — 1 50 230 10 8 - 9 - 11 280 - 320 - 390 0 29 - 33 - 38 SLZ-KA50VA(L) SUZ-KA50VA 15,700 4.6(1.1 - 5.2) 1.63 2.82 C 0.68 17,100 5.0(0.9 - 6.5) 1.55 3.23 C — 1 50 230 20 8 - 9 - 11 280 - 320 - 390 0 30 - 34 - 39 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM CMM CFM dB(A) 34.3 1,210 32.3 1,140 46 White Munsell 6.4Y 8.9/0.4 570(650) 570(650) 208(20) 22 - 7/16(25 - 9/16) 22 - 7/16(25 - 9/16) 8-3/16(13/16) 16.5(3) 36(7) 32 1 - 1/4 33.4 1,180 33.4 1,180 47 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 dB(A) 46 48 53 - 55 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 30 66 9.52 3/8 6.35 1/4 Max. 12 Max. 20 Ivory Munsell 3.0Y 7.8/1.1 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 33 76 9.52 3/8 6.35 1/4 Max. 12 Max. 20 840 330 850 33 - 1/16 13 33 - 7/16 53 117 12.7 1/2 6.35 1/4 Max. 30 Max. 30 Btu/h kW kW Btu/h kW kW kW : Hz V A CMM CFM Pa dB(A) 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor Upper Lower Upper Heating Lower Cooling limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA25, KA35VA KA50 46°C D.B. 43°C D.B. -10°C D.B. -15°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 4 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Outdoor unit Refrigerant pipe size Refrigerant pipe length Btu/h kW kW Btu/h kW kW Total input COP Energy label class Booster heater kW Phase : Cycle Hz Voltage V Breaker size A Air flow CMM (Low-Medium2-Medium1-High) CFM External static pressure Pa Sound level dB(A) (Low-Medium2-Medium1-High) External finish (Panel) Dimension W : mm Unit (Panel) D : mm H : mm W : inch D : inch H : inch Weight kg Unit (Panel) lbs Field drain pipe O.D. mm inch Air flow at cooling CMM (Low - High) CFM Air flow at heating CMM (Low - High) CFM Sound level at cooling dB(A) (Low - High) Sound level at heating dB(A) (Low - High) External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch Weight kg lbs Gas side O.D. mm inch Liquid side O.D. mm inch Height difference m Length m PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA(2) SUZ-KA35VA SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA 11,900 17,100 19,400 24,200 3.5(1.0 - 3.9) 5.0(1.1 - 5.6) 5.7(1.1 - 6.3) 7.1(0.9 - 8.1) 1.09 1.78 1.94 2.53(2.47) 3.21 2.81 2.94 2.81(2.87) A C C C (—) 0.84 0.81 0.76 0.73 14,000 20,500 23,500 27,300 4.1(0.9 - 5.0) 6.0(0.9 - 7.2) 6.9(0.9 - 8.0) 8.0(0.9 - 10.2) 1.11 1.82 2.11 2.49(2.45) 3.69 3.30 3.27 3.21(3.27) A C C C (—) — — — — 1 1 1 1 50 50 50 50 230 230 230 230 10 20 20 20 11 - 12 - 13 - 15 12 - 14 - 16 - 18 12 - 14 - 16 - 18 14 - 16 - 18 - 21 390 - 425 - 460 - 530 425 - 495 - 565 - 635 425 - 495 - 565 - 635 495 - 565 - 635 - 740 0 0 0 0 27 - 28 - 29 - 31 28 - 29 - 31 - 32 28 - 29 - 31 - 32 28 - 30 - 32 - 34 White Munsell 6.4Y 8.9/0.4 840 (950) 840 (950) 258 (35) 33 - 1/16 (37 - 3/8) 33 - 1/16 (37 - 3/8) 10 - 3/16 (1 - 3/8) 22 (6) 49 (13) 23 (6) 51 (13) 32 1 - 1/4 33.4 1,180 33.4 1,180 47 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 48 53 - 55 53 - 55 53 - 55 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 33 76 9.52 3/8 6.35 1/4 Max. 12 Max. 20 Ivory Munsell 3.0Y 7.8/1.1 840 840 330 330 850 850 33 - 1/16 33 - 1/16 13 13 33 - 7/16 33 - 7/16 53 53 117 117 12.7 15.88 1/2 5/8 6.35 6.35 1/4 1/4 Max. 30 Max. 30 Max. 30 Max. 30 840 330 850 33 - 1/16 13 33 - 7/16 58 128 15.88 5/8 9.52 3/8 Max. 30 Max. 30 The values in the parentheses indicate the specification values for PLA-RP71BA2. NOTE: 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor Upper Lower Upper Heating Lower Cooling limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA50, KA60, KA71 KA35VA 46°C D.B. 43°C D.B. -10°C D.B. -15°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 5 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Outdoor unit Refrigerant pipe size Refrigerant pipe length NOTE: Btu/h kW kW Btu/h kW kW Total input COP Energy label class Booster heater kW Phase : Cycle Hz Voltage V Breaker size A Air flow CMM (Low-Medium2-Medium1-High) CFM External static pressure Pa Sound level dB(A) (Low-Medium2-Medium1-High) External finish (Panel) Dimension W : mm Unit (Panel) D : mm H : mm W : inch D : inch H : inch Weight kg Unit (Panel) lbs Field drain pipe O.D. mm inch Air flow at cooling CMM (Low - High) CFM Air flow at heating CMM (Low - High) CFM Sound level at cooling dB(A) (Low - High) Sound level at heating dB(A) (Low - High) External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch Weight kg lbs Gas side O.D. mm inch Liquid side O.D. mm inch Height difference m Length m PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA SUZ-KA35VA SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA 11,900 17,100 19,400 24,200 3.5(1.0 - 3.9) 5.0(1.1 - 5.6) 5.7(1.1 - 6.3) 7.1(0.9 - 8.1) 1.09 1.78 1.94 2.53 3.21 2.81 2.94 2.81 A C C C 0.88 0.86 0.83 0.77 14,000 20,500 23,500 27,300 4.1(0.9 - 5.0) 6.0(0.9 - 7.2) 6.9(0.9 - 8.0) 8.0(0.9 - 10.2) 1.11 1.76 2.11 2.49 3.69 3.41 3.27 3.21 A B C C — — — — 1 1 1 1 50 50 50 50 230 230 230 130 10 20 20 20 11 - 12 - 13 - 14 14 - 15 - 16 - 18 14 - 15 - 16 - 18 15 - 16 - 18 - 20 390 - 425 - 460 - 495 495 - 530 - 565 - 635 495 - 530 - 565 - 635 530 - 565 - 635 - 705 0 0 0 0 27 - 28 - 29 - 31 28 - 29 - 31 - 33 28 - 29 - 31 - 33 28 - 30 - 32 - 34 33.4 1,180 33.4 1,180 47 48 Upper Lower Upper Heating Lower Cooling limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. 53 - 55 53 - 55 Ivory Munsell 3.0Y 7.8/1.1 840 840 330 330 850 850 33 - 1/16 33 - 1/16 13 13 33 - 7/16 33 - 7/16 53 53 117 117 12.7 15.88 1/2 5/8 6.35 6.35 1/4 1/4 Max. 30 Max. 30 Max. 30 Max. 30 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 33 76 9.52 3/8 6.35 1/4 Max. 12 Max. 20 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor White Munsell 0.70Y 8.59/0.97 840 (950) 840 (950) 258 (30) 33 - 1/16 (37 - 3/8) 33 - 1/16 (37 - 3/8) 10 - 3/16 (1 - 3/16) 24 (5) 53 (11) 32 1 - 1/4 27.5 - 49 27.5 - 49 970 - 1,730 970 - 1,730 36.8 - 49 36.8 - 49 1,300 - 1,730 1,300 - 1,730 51 - 53 51 - 53 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 53 - 55 840 330 850 33 - 1/16 13 33 - 7/16 58 128 15.88 5/8 9.52 3/8 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA35VA KA50, KA60, KA71 46°C D.B. 43°C D.B. -10°C D.B. -15°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 6 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz 2-3. CEILING-SUSPENDED TYPE Model name Indoor unit Outdoor unit Capacity Cooling Total input PCA-RP50KA SUZ-KA50VA 17,100 5.0(1.1-5.6) 1.660 3.01 B 0.79 18,800 5.5(0.9-6.6) 1.710 3.22 C — 1 50 230 20 10 - 11 - 13 - 15 355 - 390 - 460 - 530 0 32 - 34 - 37 - 40 PCA-RP60KA SUZ-KA60VA 19,400 5.7(1.1-6.3) 1.770 3.22 A 0.81 23,500 6.9(0.9-8.0) 2.020 3.42 B — 1 50 230 20 15 - 16 - 17 - 19 530 - 565 - 600 - 670 0 33 - 35 - 37 - 40 PCA-RP71KA SUZ-KA71VA 24,200 7.1(0.9-8.1) 2.210 3.21 A 0.76 27,000 7.9(0.9-10.2) 2.320 3.41 B — 1 50 230 20 16 - 17 - 18 - 20 565 - 600 - 635 - 705 0 35 - 37 - 39 - 41 lbs mm inch CMM CFM CMM CFM dB(A) 960 680 230 37 - 13/16 26 - 3/4 9 - 1/16 25 55 26 1 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 White Munsell 6.4Y 8.9/0.4 1,280 680 230 50 - 3/8 26 - 34 9 - 1/16 32 71 26 1 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 1,280 680 230 50 - 3/8 26 - 3/4 9 - 1/16 32 71 26 1 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 dB(A) 53 - 55 53 - 55 53 - 55 W : mm D : mm H : mm W : inch D : inch H : inch kg 840 330 850 33 - 1/16 13 33 - 7/16 53 117 12.7 1/2 6.35 1/4 Max. 30 Max. 30 Btu/h kW kW EER Energy label class SHF Capacity Heating Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-Medium2-Medium1-High) Power supply Indoor unit External static pressure Sound level (Low-Medium2-Medium1-High) External finish Dimension Weight Field drain pipe O.D. Outdoor unit Air flow at cooling (Low - High) Air flow at heating (Low - High) Sound level at cooling (Low - High) Sound level at heating (Low - High) External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW kW : Hz V A CMM CFM Pa dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Upper limit Lower limit Upper limit Heating Lower limit Cooling Indoor D.B. 32°C, W.B. 23°C D.B. 21°C, W.B. 15°C D.B. 27°C D.B. 20°C Ivory Munsell 3.0Y 7.8/1.1 840 330 850 33 - 1/16 13 33 - 7/16 53 117 15.88 5/8 6.35 1/4 Max. 30 Max. 30 840 330 850 33 - 1/16 13 33 - 7/16 58 128 15.88 5/8 9.52 3/8 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor D.B. 43°C D.B. -15°C D.B. 24°C, W.B. 18°C D.B. -10°C, W.B. -11°C 7 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Indoor unit Outdoor unit Capacity Cooling Total input Btu/h kW kW EER Energy label class SHF Capacity Heating Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-Medium2-Medium1-High) Power supply Indoor unit External static pressure Sound level (Low-Medium2-Medium1-High) External finish Dimension Weight Field drain pipe O.D. Outdoor unit Air flow at cooling (Low - High) Air flow at heating (Low - High) Sound level at cooling (Low - High) Sound level at heating (Low - High) External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW kW : Hz V A CMM CFM Pa dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg Upper limit Lower limit Upper limit Heating Lower limit PCA-RP50GA2 SUZ-KA50VA 17,000 5.0(1.1 - 5.6) 1.78 2.81 C 0.81 20,500 6.0(0.9 - 7.2) 1.76 3.41 B — PCA-RP60GA SUZ-KA60VA 18,800 5.5(1.1 - 6.3) 1.92 2.86 C 0.79 23,500 6.9(0.9 - 8.0) 2.05 3.37 C — PCA-RP71GA SUZ-KA71VA 24,200 7.1(0.9 - 8.1) 2.53 2.81 C 0.71 27,300 8.0(0.9 - 10.2) 2.49 3.21 C — 1 50 230 20 10 - 11 - 12 - 13 355 - 390 - 425 - 460 0 37 - 38 - 40 - 42 1000 39 - 3/8 27 60 14 - 15 - 16 - 18 495 - 530 - 565 - 635 0 37 - 39 - 41 - 43 White Munsell 0.70Y 8.59/0.97 1310 680 210 51 - 9/16 26 - 3/4 8 - 1/4 34 75 26 1 27.5 - 49 27.5 - 49 970 - 1,730 970 - 1,730 36.8 - 49 36.8 - 49 970 - 1,730 1,300 - 1,730 51 - 53 51 - 53 lbs mm inch CMM CFM CMM CFM dB(A) 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 dB(A) 53 - 55 53 - 55 840 330 850 33 - 1/16 13 33 - 7/16 53 117 12.7 1/2 6.35 1/4 Max. 30 Max. 30 840 330 850 33 - 1/16 13 33 - 7/16 53 117 12.7 1/2 6.35 1/4 Max. 30 Max. 30 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 53 - 55 53 - 55 Ivory Munsell 3.0Y 7.8/1.1 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling PCA-RP50GA SUZ-KA50VA 16,000 4.7(1.1 - 5.4) 1.80 2.61 D 0.70 18,800 5.5(0.9 - 6.6) 1.92 2.86 D — Indoor D.B. 32°C, W.B. 23°C D.B. 21°C, W.B. 15°C D.B. 27°C D.B. 20°C 840 330 850 33 - 1/16 13 33 - 7/16 53 117 15.88 5/8 6.35 1/4 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor D.B. 43°C D.B. -15°C D.B. 24°C, W.B. 18°C D.B. -10°C, W.B. -11°C 8 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz 840 330 850 33 - 1/16 13 33 - 7/16 58 128 15.88 5/8 9.52 3/8 Max. 30 Max. 30 2-4. CEILING-CONCEALED TYPE Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Btu/h kW kW Btu/h kW kW Total input COP Energy label class Booster heater kW Power supply Phase : Cycle Hz Voltage V Breaker size A Indoor unit Air flow CMM (Low - Medium - High) CFM External static pressure Pa Sound level dB(A) (Low - Medium - High) External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch Weight kg lbs mm Field drain pipe O.D. inch Outdoor unit Air flow at cooling CMM (Low - High) CFM Air flow at heating CMM (Low - High) CFM Sound level at cooling dB(A) (Low - High) Sound level at heating dB(A) (Low - High) External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch Weight kg lbs Refrigerant pipe size Gas side O.D. mm inch Liquid side O.D. mm inch Refrigerant pipe length Height difference m Length m NOTE: SEZ-KD25VA(L) SUZ-KA25VA 8,500 2.5(0.9 - 3.2) 0.778 3.21 A 0.80 10,200 3.0(0.9 - 4.5) 0.83 3.61 A — 1 50 230 10 5.5 - 7.0 - 9.0 190 - 250 - 320 5 - 15 - 35 - 50 23 - 26 -30 SEZ-KD35VA(L) SUZ-KA35VA 11,900 3.5(1.0 - 3.9) 1.09 3.21 A 0.78 13,600 4.0(0.9 - 5.0) 1.108 3.61 A — 1 50 230 10 7.0 - 9.0 - 11.0 250 - 320 - 390 5 - 15 - 35 - 50 23 - 28 -33 700 700 200 27 - 9/16 27 - 9/16 7 - 7/8 18 40 900 700 200 35 - 7/16 27 - 9/16 7 - 7/8 21 47 34.3 1,210 32.3 1,140 46 Upper Lower Upper Heating Lower Cooling limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. SEZ-KD60VA(L) SUZ-KA60VA 18,800 5.5(1.1 - 6.3) 1.89 2.91 C 0.79 23,900 7.0(0.9 - 8.0) 2.05 3.41 B — 1 50 230 20 12.0 - 15.0 - 18.0 420 - 530 - 640 5 - 15 - 35 - 50 30 - 34 -38 SEZ-KD71VA(L) SUZ-KA71VA 24,200 7.1(0.9 - 8.3) 2.53 2.81 C 0.74 27,600 8.1(0.9 - 10.4) 2.37 3.42 B — 1 50 230 20 12.0 - 16.0 - 20.0 420 - 570 - 710 5 - 15 - 35 - 50 30 - 35 -40 1100 700 200 43 - 5/16 27 - 9/16 7 - 7/8 27 60 1100 700 200 43 - 5/16 27 - 9/16 7 - 7/8 27 60 33.4 1,180 33.4 1,180 47 Galvanized sheets 900 700 200 35 - 7/16 27 - 9/16 7 - 7/8 23 51 32 1 - 9/32 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 27.5 - 49 970 - 1,730 36.8 - 49 1.300 - 1,730 51 - 53 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 46 48 53 - 55 53 - 55 53 - 55 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 30 66 9.52 3/8 6.35 1/4 Max. 12 Max. 20 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 33 76 9.52 3/8 6.35 1/4 Max. 12 Max. 20 Ivory Munsell 3.0Y 7.8/1.1 840 330 850 33 - 1/16 13 33 - 7/16 53 117 12.7 1/2 6.35 1/4 Max. 30 Max. 30 840 330 850 33 - 1/16 13 33 - 7/16 53 117 15.88 5/8 6.35 1/4 Max. 30 Max. 30 840 330 850 33 - 1/16 13 33 - 7/16 58 128 15.88 5/8 9.52 3/8 Max. 30 Max. 30 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor SEZ-KD50VA(L) SUZ-KA50VA 17,100 5.0(1.1 - 5.6) 1.78 2.81 C 0.76 20,500 6.0(1.1 - 7.2) 1.87 3.21 C — 1 50 230 20 10.0 - 12.5 - 15.0 350 - 440 - 530 5 - 15 - 35 - 50 30 - 34 -37 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA25, KA35VA KA50, KA60, KA71 46°C D.B. 43°C D.B. -15°C D.B. -10°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 9 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Btu/h kW kW Btu/h kW kW Total input COP Energy label class Booster heater kW Phase : Cycle Hz Voltage V Breaker size A Air flow CMM (Low - High) CFM External static pressure Pa Sound level dB(A) (Low - High) External finish Dimension W : mm 790 D : mm 550 H : mm 225 W : inch 31 - 1/8 D : inch 21 - 5/8 H : inch 8 - 7/8 Weight kg 19 lbs 42 Unit drain pipe R1(External thread) Power supply Indoor unit Outdoor unit Air flow at cooling CMM (Low - High) CFM Air flow at heating CMM (Low - High) CFM Sound level at cooling dB(A) (Low - High) Sound level at heating dB(A) (Low - High) External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch Weight kg lbs Refrigerant pipe size Gas side O.D. mm inch Liquid side O.D. mm inch Refrigerant pipe length Height difference m Length m NOTE: SEZ-KC25VA SUZ-KA25VA 8,500 2.5(0.9 - 3.2) 0.73 3.42 A 0.74 10,200 3.0(0.9 - 4.5) 0.83 3.61 A — 1 50 230 10 4.8 - 7.9 170 - 280 Std:5 Max:5 25 - 36 Upper Lower Upper Heating Lower Cooling limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. SEZ-KA50VA SUZ-KA50VA 17,100 5.0(1.1 - 5.6) 1.78 2.81 C 0.75 20,100 5.9(1.1 - 7.2) 1.84 3.21 C — 1 50 230 20 12 - 17 425 - 600 Std:30 Max:50 31 - 39 SEZ-KA60VA SUZ-KA60VA 18,800 5.5(1.1 - 6.3) 1.96 2.81 C 0.75 23,500 6.9(0.9 - 8.0) 2.45 2.82 D — 1 50 230 20 12 - 20 425 - 705 Std:30 Max:50 32 - 43 Galvanized sheets 1100 700 270 43 - 5/16 27 - 9/16 10 - 5/8 33.5 74 R1(External thread) SEZ-KA71VA SUZ-KA71VA 24,200 7.1(0.9 - 8.3) 2.46 2.89 C 0.74 27,600 8.1(0.9 - 10.4) 2.36 3.43 B — 1 50 230 20 12 - 20 425 - 705 Std:30 Max:50 32 - 43 35 77 34.3 1,210 32.3 1,140 46 33.4 1,180 33.4 1,180 47 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 27.5 - 49 970 - 1,730 36.8 - 49 1.300 - 1,730 51 - 53 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 46 48 53 - 55 53 - 55 53 - 55 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 30 66 9.52 3/8 6.35 1/4 Max. 12 Max. 20 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 33 76 9.52 3/8 6.35 1/4 Max. 12 Max. 20 Ivory Munsell 3.0Y 7.8/1.1 840 330 850 33 - 1/16 13 33 - 7/16 53 117 12.7 1/2 6.35 1/4 Max. 30 Max. 30 840 330 850 33 - 1/16 13 33 - 7/16 53 117 15.88 5/8 6.35 1/4 Max. 30 Max. 30 840 330 850 33 - 1/16 13 33 - 7/16 58 128 15.88 5/8 9.52 3/8 Max. 30 Max. 30 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor SEZ-KA35VA SUZ-KA35VA 11,900 3.5(1.0 - 3.9) 1.06 3.30 A 0.77 13,600 4.0(0.9 - 5.0) 1.10 3.64 A — 1 50 230 10 10 - 13 355 - 460 Std:30 Max:50 30 - 35 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA25, KA35VA KA50, KA60, KA71 46°C D.B. 43°C D.B. -15°C D.B. -10°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 10 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low - High) External static pressure Sound level (Low - High) External finish Dimension Power supply Indoor unit Weight Field drain pipe O.D. Outdoor unit Air flow at cooling (Low - High) Air flow at heating (Low - High) Sound level at cooling (Low - High) Sound level at heating (Low - High) External finish Dimension Btu/h kW kW Btu/h kW kW kW : Hz V A CMM CFM Pa dB(A) PEAD-RP35JA(L) PEAD-RP50JA(L) SUZ-KA35VA SUZ-KA50VA 12,300 16,700 3.6 (1.0-3.9) 4.9 (1.1-5.6) 1.060 (1.040) 1.520 (1.500) 3.40 (3.46) 3.22 (3.27) A A 0.85 0.85 14,000 20,100 4.1 (0.9-5.0) 5.9 (0.9-7.2) 1.110 1.620 3.69 3.64 A A — — 1 1 50 50 230 230 16 20 10 - 12 - 14 12 - 14.5 - 17 353 - 424 - 494 424 - 512 - 600 35/50/70/100/150 23 - 27 - 30 26 - 31 - 35 PEAD-RP60JA(L) PEAD-RP71JA(L) SUZ-KA71VA SUZ-KA60VA 24,200 19,400 7.1 (0.9-8.1) 5.7 (1.1-6.3) 2.210 (2.190) 1.680 (1.660) 3.21 (3.24) 3.39 (3.43) A A 0.83 0.86 27,300 23,900 8.0 (0.9-10.2) 7.0 (0.9-8.0) 2.090 1.940 3.83 3.61 A A — — 1 1 50 50 230 230 20 20 17.5 - 21 - 25 14.5 - 18 - 21 618 - 742 - 883 512 - 636 - 742 35/50/70/100/150 26 - 30 - 34 25 - 29 - 33 Galvanized sheets 900 732 250 35 - 7/16 28 - 7/8 9 - 7/8 26 (25) 28 (27) 58 (56) 62 (60) Galvanized sheets 1,100 732 250 43 - 5/16 28 - 7/8 9 - 7/8 33 (32) 33 (32) 73 (71) 73 (71) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM CMM CFM dB(A) 32 1 - 1/4 dB(A) 33.4 1,180 33.4 1,180 47 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 48 53 - 55 53 - 55 53 - 55 W : mm 800 D : mm 285 H : mm 550 W : inch 31 - 1/2 D : inch 11 - 1/4 H : inch 21 - 5/8 Weight kg 33 lbs 76 Refrigerant pipe size Gas side O.D. mm 9.52 inch 3/8 Liquid side O.D. mm 6.35 inch 1/4 Refrigerant pipe length Height difference m Max. 12 Length m Max. 20 The values in the parentheses indicate the specification values for PEAD-RP·JAL. NOTE: 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor Upper Lower Upper Heating Lower Cooling limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. Ivory Munsell 3.0Y 7.8/1.1 840 840 330 330 850 850 33 - 1/16 33 - 1/16 13 13 33 - 7/16 33 - 7/16 53 53 117 117 12.7 15.88 1/2 5/8 6.35 6.35 1/4 1/4 Max. 30 Max. 30 Max. 30 Max. 30 840 330 850 33 - 1/16 13 33 - 7/16 58 128 15.88 5/8 9.52 3/8 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA25, KA35VA KA50, KA60, KA71 46°C D.B. 43°C D.B. -15°C D.B. -10°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 11 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low - High) External static pressure Sound level (Low - High) External finish Dimension Power supply Indoor unit Weight Unit drain pipe Air flow at cooling (Low - High) Air flow at heating (Low - High) Sound level at cooling (Low - High) Sound level at heating (Low - High) External finish Dimension Outdoor unit Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW Btu/h kW kW kW : Hz V A CMM CFM Pa dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs CMM CFM CMM CFM dB(A) PEAD-RP35EA2 PEAD-RP50EA SUZ-KA35VA SUZ-KA50VA 12,300 16,700 3.6(1.0 - 3.9) 4.9(1.1 - 5.6) 1.12 1.74 3.21 2.82 A C 0.90 0.79 14,000 20,100 4.1(0.9 - 5.0) 5.9(0.9 - 7.2) 1.13 1.69 3.63 3.49 A B — — 1 1 50 50 230 230 10 20 13.5 - 17 476 - 600 30(70) 36 - 40 (70Pa : 38 - 44) Galvanized sheets 935 700 295 36 - 13/16 27 - 5/8 11 - 5/8 33 35 73 77 R1(External thread) 33.4 27.5 - 49 1,180 970 - 1,730 33.4 36.8 - 49 1,180 1,300 - 1,730 47 51 - 53 dB(A) 48 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 33 76 9.52 3/8 6.35 1/4 Max. 12 Max. 20 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor Upper Lower Upper Heating Lower Cooling limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. PEAD-RP60EA PEAD-RP71EA SUZ-KA60VA SUZ-KA71VA 20,500 24,200 6.0(1.1 - 6.3) 7.1(0.9 - 8.1) 2.05 2.53 2.93 2.81 C C 0.80 0.81 23,900 27,300 7.0(0.9 - 8.0) 8.0(0.9 - 10.2) 2.07 2.49 3.38 3.21 C C — — 1 1 50 50 230 230 20 20 17 - 21 20 - 25 600 - 741 706 - 883 30(70) 70(130) 37 - 41 37 - 41 (70Pa : 39 - 46) (130Pa : 40 - 45) Galvanized sheets 1175 700 740 295 325 46 - 1/8 27 - 5/8 29 - 1/8 11 - 5/8 12 - 13/16 42 44 92 97 R1(External thread) 27.5 - 49 27.5 - 49 970 - 1,730 970 - 1,730 36.8 - 49 36.8 - 49 1,300 - 1,730 1,300 - 1,730 51 - 53 51 - 53 53 - 55 53 - 55 Ivory Munsell 3.0Y 7.8/1.1 840 840 330 330 850 850 33 - 1/16 33 - 1/16 13 13 33 - 7/16 33 - 7/16 53 53 117 117 12.7 15.88 1/2 5/8 6.35 6.35 1/4 1/4 Max. 30 Max. 30 Max. 30 Max. 30 53 - 55 840 330 850 33 - 1/16 13 33 - 7/16 58 128 15.88 5/8 9.52 3/8 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA25, KA35VA KA50, KA60, KA71 46°C D.B. 43°C D.B. -15°C D.B. -10°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 12 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low - High) External static pressure Sound level (Low - High) External finish Dimension Power supply Indoor unit Weight Unit drain pipe Air flow at cooling (Low - High) Air flow at heating (Low - High) Sound level at cooling (Low - High) Sound level at heating (Low - High) External finish Dimension Outdoor unit Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW Btu/h kW kW kW : Hz V A CMM CFM Pa dB(A) dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m Indoor Upper Lower Upper Heating Lower limit limit limit limit PEAD-RP71GA SUZ-KA71VA 24,200 7.1(0.9 - 8.1) 2.53 2.81 C 0.81 27,300 8.0(0.9 - 10.2) 2.49 3.21 C — 1 50 230 20 16.5 - 21 582 - 741 20 - 25 706 - 883 10/50/70 33 - 37/35 - 40/36 - 42 35 - 38/37 - 41/37 - 43 (10/50/70Pa) (10/50/70Pa) Galvanized sheets W : mm 1171 D : mm 740 H : mm 275 W : inch 46 - 1/8 D : inch 29 - 1/8 H : inch 10 - 13/16 kg 42 lbs 93 R1(External thread) CMM 27.5 - 49 27.5 - 49 CFM 970 - 1,730 970 - 1,730 CMM 36.8 - 49 36.8 - 49 CFM 1,300 - 1,730 1,300 - 1,730 dB(A) 51 - 53 51 - 53 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling PEAD-RP60GA SUZ-KA60VA 19,400 5.7(1.1 - 6.3) 2.03 2.81 C 0.82 23,900 7.0(0.9 - 8.0) 2.05 3.41 B — 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. 53 - 55 53 - 55 Ivory Munsell 3.0Y 7.8/1.1 840 840 330 330 850 850 33 - 1/16 33 - 1/16 13 13 33 - 7/16 33 - 7/16 53 58 117 128 15.88 15.88 5/8 5/8 6.35 9.52 1/4 3/8 Max. 30 Max. 30 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA60, KA71 43°C D.B. -15°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 13 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER SHF Capacity Btu/h kW kW Total input COP Booster heater Phase Cycle Voltage Breaker size Air flow (Low - High) External static pressure Sound level (Low - High) External finish Dimension Power supply Indoor unit Weight Btu/h kW kW kW : Hz V A CMM R/s Pa dB(A) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs Galvanized sheets 785 690 428 31 27 - 1/16 16 - 7/8 46 101 R1(External thread) CMM CFM CMM CFM dB(A) 27.5 - 49 970 - 1,730 36.8 - 49 1,300 - 1,730 51 - 53 dB(A) 53 - 55 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m Ivory Munsell 3.0Y 7.8/1.1 840 330 850 33 - 1/16 13 33 - 7/16 58 128 15.88 5/8 9.52 3/8 Max. 30 Max. 30 Unit drain pipe Outdoor unit Air flow at cooling (Low - High) Air flow at heating (Low - High) Sound level at cooling (Low - High) Sound level at heating (Low - High) External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor Upper Lower Upper Heating Lower Cooling limit limit limit limit PEA-RP71EA SUZ-KA71VA 23,500 6.9 2.90 2.38 0.84 27,300 8.0 2.49 3.21 — 1 50 230 20 22 - 27 367 - 450 125 52 - 55 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA71 43°C D.B. -15°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 14 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz OUTLINES AND DIMENSIONS Unit : mm INDOOR UNIT MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA 700 607 46.5 More than 100mm Air in 600 96 54 508 60 155 131 7 131 593 333 363 Installation plate 210 Indoor unit 337 337 15 60 60 60 80 454 12 128 45 35 72 110 4-:6 Hole drain 137 147 12 60 Gas pipe 25, 35::9.52(flared)3/8" 50::12.7(flared)1/2" Liquid pipe :6.35(flared)1/4 11 123 125 60 Air out 19 118 125 More than 100mm 200 12 12 Air out 19 More than 100mm 46.5 165 205 3 W 100 25 W 73.4 Cut out hole 420 Suspension bolt pitch Refrigerant pipe (liquid) Refrigerant pipe (gas) Emergency operation switch(cooling) Receiver Emergency operation switch(heating) MITSUBISHI ELECTRIC DEFROST/STAND BY lamp Operation lamp (WIRELESS PANEL) Ceiling surface 118 3- W 2.8 hole Burring hole 66 121 Detail drawing of fresh air intake 12 0° 15~37 576~620 Ceiling hole 15~37 93 650 17 202 230 35 55 V/M V/M 377 Air intake hole Grille Terminal block (Case of Wired remote controller)Terminal block 650 301 Air outlet hole 15~37 199 352 335 576~620 Ceiling hole 570 530 Suspension bolt pitch V/M V/M Ceiling surface 335 15~37 193 570 Brand label Vane motor Air intake grille Auto vane Drain hole Grille SLZ-KA50VA(L) W 12.7mm flared connection 1/2"F W 9.52mm flared connection 3/8"F W 6.35mm SLZ-KA35VA(L) flared connection 1/4"F W 6.35mm flared connection 1/4"F W 9.52mm flared connection 3/8"F W 6.35mm flared connection 1/4"F SLZ-KA25VA(L) Refrigerant pipe (gas) Models Refrigerant pipe (liquid) Wiring entry Suspension bolt M10 or 3/8 (procure locally) Drain pipe VP-25 connection (O.D. W 32) 87 235 20 31 208 +5 27 0 57 56 38~58 55 35 Suspension bolt lower edge 301 Air outlet hole 16 377 Air intake hole 182 0° 12 48 Fresh air intake SLZ-KA25VAL SLZ-KA35VAL SLZ-KA50VAL SLZ-KA25VA SLZ-KA35VA SLZ-KA50VA Unit : mm SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) Unit : mm 20 12 157.5 37 100 37 H 100XJ=K 23 20 12 57 625 (Suspension bolt pitch) 49 Terminal block Terminal block (Indoor/outdoor connecting line) (Remote controller transmission line) 70 270 1 Refrigerant piping flare connection (gas) Drain pipe(O.D.W32)(Spontaneous draining) Access door 50 7 77 G Note2 Knockout hole W27 (Indoor/outdoor connecting line) 200 102 23 25 116 2X2-W2.9 Knockout hole W27 (Remote controller transmission line) Control box 100 150 (Duct) 700 677 23 10 Air filter Suspension bolt hole 4-14X30 Slot 170 2 Refrigerant piping flare connection (liquid) L-W2.9 90 10 2XE-W2.9 More than 10mm More than 20mm 25 20 30 88 100 100 Air inlet C A Air outlet B (Suspension bolt pitch) D (Duct) 100X(E-1)=F 88 15 50 50 ~1 50 0 00 45 n3 tha e r Mo 45 0 Ceiling surface Access door Make the access door at the appointed position properly for service maintenance. Required space for service and maintenance Model SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) A 700 B 752 C 798 D 660 E 7 F 600 G 800 H 660 J 5 K 500 L 16 900 952 998 860 9 800 1000 860 7 700 20 1100 1152 1198 1060 11 1000 1200 1060 9 900 24 Note1.Use M10 screw for the suspension bolt (field supply). 2.Keep the service space for the maintenance at the bottom. 3.This chart indicates for SEZ-KD50VA(L) model,which has 3 fans. SEZ-KD25,35VA(L) models have 2 fans. SEZ-KD60,71VA(L) models have 4 fans. 4.In case an inlet duct is used,remove the air filter(supply with the unit), then install the filter(field supply) at suction side. 17 1 Gas pipe 2 Liquid pipe W9.52 W12.7 W15.88 W6.35 W9.52 Air filter 664(Lifting bolt pitch) 23 Terminal bed (Power source) Lifting plate (4-14%30) Bottom plate 550(+1) 510 459 (Lifting bolt pitch) Control box 80 113 148 55 15 30 15 Air outlet 2X3- :3hole 14 610 150 50 16 14 127 13.5 50 50 Air inlet 582 710 2X12- : 3hole 50X11=550 204.5 (52) 42.5 56.5 301 301 450 (57) 50~ 150 Make the access door at the appointed position properly for service maintenance. Ceiling surface 300 25 450 Required space for service and maintenance Access door 5 6- :3hole 500 150 50~ Detailed chart around the air intake duct flange(+3) (Duct and flange should be supplied in the field.) 5 Refrigerant piping flare connection (gas :9.52 copper tube):LP ········ Refrigerant piping flare connection (liquid :6.35 copper tube):HP ········ Drain piping connection R1 (External thread) ········ 12 189 9 (When the air intake duct is used) 225(+2) Note 1. Use M10 screw for the lifting bolt (field supply). 2. Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned. 3. The direction of air intake can be changed from the bottom to the rear by attaching the bottom plate to the air intake side. 4. Drain Pan is changeable from right and left. 5. The dimension is changed, in case the optional long-life filter is attached. Rear Air-Intake spec. :Depth is increased by 30mm(+1) Bottom Air-Intake spec. :Height is increased by 30mm(+2) More than 20mm 18 More than 20mm The part air intake duct is attached.(+3) SEZ-KC25VA Unit : mm 790 SEZ-KA35VA SEZ-KA50VA SEZ-KA60VA SEZ-KA71VA Unit : mm 42 In case of bottom side suction, mount the PLATE (A) on the rear side. 930 After installation, remove the transportation support PLATE (B). 215 120 7%100=700 955 PLATE (B)%2 24-W2.9 holes 27 50 1016 150 Select the either back side or bottom side. 77 bolt pitch Service space (It is necessary to maintain a working service area from the ceiling.) 40 50 (10) 680 700 Access door 60 38 350 50 Suspension 1000 600 50 + 450 Electrical parts box Air inlet (rear side) 150 77.5 100 29 25 12.5 240 (Inlet size) (Inlet size) Air inlet (rear side) dimensions 100 7%100=700 880 Air outlet duct flange 9 % 2-W2.9 holes Air outlet Refrigerant pipe (gas) 1070 Refrigerant pipe (liquid) 50 Wiring entry 20 25 32.5 (10) Air inlet (bottom side) Access door Air outlet duct flange 94 25 2%2-W2.9 holes 108 75 270 30 Electrical parts box 1100 + 100 Terminal block 170 (1070) (Suspension bolt pitch) 20 or more Suspension bolt pitch Suspension bolt M10 or 3/8 (procure locally) 80 350 Select the either back side or bottom side. Electrical parts box Drain plug R1 (male) Air inlet (bottom side) dimensions PLATE (A) Models SEZ-KA35VA SEZ-KA50VA 7%100=700 120 215 930 (Inlet size) 25 12.5 240 51 39 77.5 100 (Inlet size) SEZ-KA60VA SEZ-KA71VA 955 24-W2.9 holes 19 Refrigerant pipe (liquid) Refrigerant pipe (gas) W6.35mm W9.52mm flared connection 1/4"F W6.35mm flared connection 1/4"F W6.35mm flared connection 1/4"F W9.52mm flared connection 3/8"F flared connection 3/8"F W12.7mm flared connection 1/2"F W15.88mm flared connection 5/8"F W15.88mm flared connection 5/8"F PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA PLA-RP71BA2 Unit : mm Ceiling hole 20~45 860~910 810 90 100 100 90 Cut out hole 620 860~910 Indoor power supply terminal block(Option part) Ceiling hole 167 + + 605 +35 -5 840 Branch duct hole Suspension bolt pitch Remote controller terminal block Indoor unit/Outdoor unit connecting terminal block 155 70° 160 (7.5) 100 Suspension bolt pitch 160 Detail connecting of branch duct(Both aspects) 20~45 Fresh air intake hole 130 20~45 Branch duct hole 350 :175 14-:2.8 Burring hole Burring hole pitch :150 Detail drawing of fresh air intake hole (7.5) 24 1 60 284 Drain pipe connected to VP-25 377 B A + 190 156 105 140 + Control wire entry Ceiling ) Cut out hole :100 + Ceiling In case of standard grille : PLP-6BA / PLP-6BAMD 35 Power supply wire, Indoor unit/Outdoor unit connecting wire entry 17 +50 50~70 170 Connect the attached drain socket. + + + + Suspension bolt lower edge ( Keep approximately 10 to 15mm space between unit ceiling and ceiling slab. 2 + Burring hole pitch :125 120° 120° 840 3-:2.8 158 160 Suspension bolt M10 or W3/8 Burring hole 20~45 187.5 160 D C 90 150 Cut out hole MITSUBISHI ELECTRIC Grille 597 Drain hole Drain pump clean hole and Drain emergency drainage hole 597 Auto vane (Air outlet) switch<Cooling>and Emergency Up/Down switch<Up> Emergency operation switch<Heating>and Emergency Up/Down switch<Down> Air intake hole 500 Air outlet hole 950 M In case of Auto-Grille : PLP-6BAJ In case of wireless remote controller : PLP-6BALM Auto Grille Air intake grille up/down discharge Emergency operation Air intake grille Receiver M 83 M 36 500 83 36 Indoor unit 1500mm or more 1000mm or more Indoor unit 3000mm or more Obstacle Air intake grille Vane motor 950 Grille DEFROST/STAND BY lamp Operation lamp Air outlet hole Ceiling Ceiling L.L Filter MITSUBISHI ELECTRIC 1800mm or more from floor For high attachment Note : 1. Please choose the Grille from a standard grille, auto-grille. 2. As for drain pipe, please use VP-25(O.D. :32 PVC TUBE). Drain pump is included. Max. lifting height is 850mm from the ceiling. 3. As for suspension bolt, please use M10 or W3/8. (Procured at local site) 4. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/ power wires connection. 5. The height of the indoor unit is able to be adjusted with the grille attached. 6. For the installation of the optional high efficiency filter or optional multi-functional casement. 1) Requires E or more space between transom and ceiling for the installation. 2) Add 135 mm to the dimensions + marked on the figure. 3) The optional high efficiency filter must be used jointly with optional multi-functional casement. 7. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.) 8. As for necessary installation/service space, please refer to the left figure. Models Floor PLA-RP35/50BA PLA-RP60BA PLA-RP71BA PLA-RP71BA2 20 Refrigerant pipe ···:6.35 Flared connection ···1/4 inch Refrigerant pipe :6.35 Flared connection 1/4 inch Refrigerant pipe ···:9.52 Flared connection ···3/8 inch Refrigerant pipe ···:12.7 Flared connection ··1/2 inch Refrigerant pipe ···:15.88 Flared connection ···5/8 inch A B C D E 80 74 241 258 87 85 77 400 Max. 4.0m Air intake hole M PLA-RP50AA PLA-RP60AA PLA-RP71AA Ceiling hole 860 - 910 20 - 45 Fresh air intake 20 - 45 810 Suspension bolt pitch 159 197 W125 Burring hole pitch 158 120" 120" 20 - 45 3 - W2.8 Burring hole 159 16 C 89 Detail drawing of fresh air intake 98 192 W150 159 840 W100 (Cut out hole) Suspension bolt M10 or W3/8 1 Ceiling surface Feeding hole (Drain pump) 286 374 60 860 - 910 Ceiling hole 14 - W2.8 Burring hole Terminal block 840 W175 Branch duct hole Suspension bolt pitch 605 350 167 155 159 130 70" 100 90 100 100 90 Branch duct hole (Cut out hole) Unit : mm 20 - 45 PLA-RP35AA Drain pipe VP-25connection (O.D.W32) +5 0 B +5 0 30 135 Ceiling surface 17 Control wire entry Power line entry Suspension bolt lower edge 190 105 140 50 - 70 170 A 2 577 Air intake hole Air intake grille 17 High efficiency filter & Fresh air intake casement (option) Grille Drain hole M A M (WIRELESS PANEL) 950 Emergency operation switch (heating) 411 Air outlet hole Emergency operation switch (cooling) Auto vane 577 Air intake hole A DEFROST/STAND BY lamp M Receiver 77 Operation lamp M 51 411 Air outlet hole 950 Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size (Unit : mm) LIQUID SIDE GAS SIDE RP35, 50 RP60 RP71 :6.35 :6.35 — :9.52 :9.52 :9.52 :12.7 — — :15.88 :15.88 :15.88 (Unit : mm) Models PLA-RP35,50AA PLA-RP60,71AA : Initial flare nut size 21 A B C 241 258 80 Vane motor 77 51 Branch duct hole 1 2 3 4 5 6 7 8 9 Ceiling 461 25 ø1 9 38 38 7 387 18 120° 85 260 2 8 48 233 246 When drain socket is installed (Drainage) 2 2 Drainage pipe connection(26mmI.D.) Drainage pipe connection(for the left arrangement) Knock out hole for left drain-piping arrangement Refrigerant-pipe connection(gas pipe side/flared connection) Refrigerant-pipe connection(liquid pipe side/flared connection) Knock out hole for upper drain pipe arrangement Knock out hole for fresh air intake ø100 Knock out hole for wiring arrangement 2-ø22 Knock out hole for wiring arrangement 2-ø26 Air intake Accessory···Drain socket (I.D. 26) Electrical box 138 86 4 Air outlet 878 853 960 917(Suspension bolt pitch) 182 140 62 80 1 In case of the rear pipe arrangement, make sure to remove the shaded portions from the independent piece. Then put the independent piece back in initial position. (The heat exchanger might be clogged because of dust) 75 3 When electrical box is pulled down 121 24 5 126 2 190 46 76 124 (71) 8 169 37 1 190 Electrical box 84 88 2 85 254 320 195 57 6 680 230 680 22 476 150 18 [FRONT VIEW] 5 10 51 184 (liquid ø6.35) (gas ø12.7) When drain socket is installed (Drainage) NOTES. 1.Use M10 or W3/8 screw for anchor bolt. 2.Please be sure when installing the drain pump (option parts), refrigerant pipe will be only upward. 246 233 203 PCA-RP50KA Unit : mm 121 37 190 46 1 2 3 4 5 6 7 8 9 461 25 ø1 9 38 7 387 18 120° 2 8 48 246 233 (Drainage) When drain socket is installed 138 85 86 260 2 4 2 Air outlet 1198 1173 1280 1237(Suspension bolt pitch) 182 140 62 80 1 Drainage pipe connection(26mmI.D.) Drainage pipe connection(for the left arrangement) Knock out hole for left drain-piping arrangement Refrigerant-pipe connection(gas pipe side/flared connection) Refrigerant-pipe connection(liquid pipe side/flared connection) Knock out hole for upper drain pipe arrangement Knock out hole for fresh air intake ø100 Knock out hole for wiring arrangement 2-ø22 Knock out hole for wiring arrangement 2-ø26 Air intake Accessory···Drain socket (I.D. 26) Flare nut ø6.35 (RP60 only) Electrical box Ceiling 38 24 5 In case of the rear pipe arrangement, make sure to remove the shaded portions from the independent piece. Then put the independent piece back in initial position. (The heat exchanger might be clogged because of dust) When electrical box is pulled down 75 169 3 124 76 (71) 2 8 126 1 190 Electrical box 84 88 2 85 254 320 195 57 680 230 680 23 476 150 [FRONT VIEW] 6 5 10 60 179 203 A B 246 233 71 180 200 (gas ø15.88) When drain socket is installed (Drainage) (liquid ) 236 4 GAS SIDE ø15.88 :Initial flare nut size ø9.52 5 LIQUID SIDE ø6.35 RP60 ø9.52 ø15.88 RP71 Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size NOTES. 1.Use M10 or W3/8 screw for anchor bolt. 2.Please be sure when installing the drain pump (option parts), refrigerant pipe will be only upward. 51 A B PCA-RP60KA PCA-RP71KA Unit : mm 18 PCA-RP50GA Unit : mm NOTES: 1. Use M10 or W3/8 screws for anchor bolt. 2. When optional drain pump is installed, always provide upward piping for refrigerant piping. 140 70 320 150 80 17 933 (suspension bolt pitch) 85 983 226 157 15 81 76 Electrical box 180 210 70 904 182 1000 gas 241 (Drainage) 254 506 680 56 Air outlet liquid 201 Air intake 161 90 918 1 2 3 4 5 6 7 8 38 131 46 175 1 38 79 32 Ceiling 161 6~7 42 179 Electrical box [Front view] Use the current nuts meeting the pipe size of the outdoor unit. 86 138 171 263 352 525 Drainage pipe connection (26mm I.D.) Drainage pipe connection (for the left arrangement) Knock out hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for left drain pipe arrangement Knockout hole for wiring arrangement Available pipe size LIQUID SIDE 928 (Unit : mm) RP50 :6.35 :9.52 When electrical box is pulled down GAS SIDE :12.7 :15.88 : Initial flare nut size 24 PCA-RP50GA2 PCA-RP60GA PCA-RP71GA Unit : mm NOTES: 1. Use M10 or W3/8 screws for anchor bolt. 2. When optional drain pump is installed, always provide upward piping for refrigerant piping. 140 70 320 150 80 17 1240 (suspension bolt pitch) 85 1290 Electrical box 15 226 210 180 81 76 157 70 1214 182 (liquid) 1310 201 (5/8F gas) 241 (Drainage) 254 506 680 56 Air outlet Air intake 161 90 1228 38 131 161 525 46 175 1 Ceiling 3879 32 [ Front view ] 6~7 42 179 Electrical box 86 138 171 263 416 1 2 3 4 5 6 7 8 Drainage pipe connection (26mm I.D.) Drainage pipe connection (for the left arrangement) Knock out hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for left drain pipe arrangement Knockout hole for wiring arrangement Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size RP50 LIQUID SIDE :6.35 1235 :9.52 GAS SIDE :12.7 :15.88 When electrical box is pulled down : Initial flare nut size 25 RP60 (Unit : mm) RP71 :6.35 :9.52 :9.52 :15.88 :15.88 PEAD-RP35, 50, 60, 71JA Unit : mm 2xE-:2.9 Suspension bolt hole 4-14x30 Slot 18 Air inlet 210 G Air outlet A B(Suspension bolt pitch) C D (Duct) 100x(E-1)=F 15 643 (Suspension bolt pitch) 32 238 10 Terminal block (Remote controller transmission line) 175±5mm (Actual length) 217 250 Control box 2×2-:2.9 136 67 356 Drain pipe(O.D.:32) Terminal block (Spontaneous draining) (Indoor/Outdoor connecting line) NOTE 1. Use M10 screw for the Suspension bolt (field supply). 2. Keep the service space for the maintenance at the bottom. 3. This chart indicates for PEAD-RP60•71JA models, which have 2 fans. PEAD-RP35•50JA models have 1 fan. 4. In case that the inlet duct is used, remove the air filter (supplied with the unit), then install the filter (field supply) at suction side. Model A B Gas pipe D E F G PEAD-RP35,50JA 900 954 1000 860 9 800 858 PEAD-RP60JA 1100 1154 1200 1060 11 1000 1058 :15.88 PEAD-RP71JA 1100 1154 1200 1060 11 1000 1058 :15.88 Liquid pipe :12.7 :6.35 Outdoor unit (SUZ): :6.35 Outdoor unit : :9.52* :9.52 * Setting at shipment 6 J Kx(L-1)=M J K More than 20mm Ceiling surface 112 112 N-:2.9 More than 10mm C Drain hose (I.D.:32) <accessory> 11 1 Refrigerant piping Flare connection (gas) Less than 300mm Less than 700mm 732 700 Drain pipe Drain pump (O.D.:32) 41 57 178 (Duct) 100 33 23 40 122 2 Refrigerant piping Flare connection (liquid) 23 10 58 40 57 21 20 30 100 Air Filter Access door Q Make the access door at the appointed position properly for service maintenance. P Qx(R-1)=S Model PEAD-RP35,50JA PEAD-RP60,71JA 777 50 H Note2 Access door 50 250 ~30 45 0 0 450 0 30 han re t Mo Required space for service and maintenance 26 H 1000 1200 J 54 49 K 260 330 L 4 4 M 780 990 N 10 10 P 40.5 40 Q 273 340 R 4 4 S 819 1020 PEAD-RP35, 50, 60, 71JAL Unit : mm 2xE-:2.9 Suspension bolt hole 4-14x30 Slot 210 G Air inlet C Air outlet A 18 B(Suspension bolt pitch) D (Duct) 100x(E-1)=F 15 21 Terminal block (Remote controller transmission line) 732 700 32 175±5mm (Actual length) 217 250 10 33 23 40 122 100 178 (Duct) 643 (Suspension bolt pitch) 57 2 Refrigerant piping Flare connection (liquid) 23 10 58 40 57 20 30 100 Air Filter 2×2-:2.9 1 Refrigerant piping Flare connection (gas) Control box 136 67 356 NOTE 1. Use M10 screw for the Suspension bolt (field supply). 2. Keep the service space for the maintenance at the bottom. 3. This chart indicates for PEAD-RP60•71JAL models, which have 2 fans. PEAD-RP35•50JAL models have 1 fan. 4. In case of the inlet duct is used,remove the air filter (supplied with the unit), then install the filter (field supply) at suction side. Drain pipe(O.D.:32) Model Drain hose (I.D.:32) <accessory> Terminal block (Indoor/Outdoor connecting line) A B C Liquid pipe Gas pipe D E F G PEAD-RP35,50JAL 900 954 1000 860 9 800 858 PEAD-RP60JAL 1100 1154 1200 1060 11 1000 1058 :15.88 PEAD-RP71JAL 1100 1154 1200 1060 11 1000 1058 :15.88 :12.7 :6.35 Outdoor unit (SUZ): :6.35 Outdoor unit : :9.52* :9.52 * Setting at shipment J J 112 112 Ceiling surface More than 20mm More than 10mm Kx(L-1)=M K 11 6 N-:2.9 Access door Q P Make the access door at the appointed position properly for service maintenance. Qx(R-1)=S Model 777 50 H Note2 Access door 50 250 ~30 45 0 0 re Mo 450 0 0 n3 tha Required space for service and maintenance 27 H J K L M N P Q R S PEAD-RP35,50JAL 1000 54 260 4 780 10 40.5 273 4 819 PEAD-RP60,71JAL 1200 49 330 4 990 10 40 340 4 1020 PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA A RP35,50 772 RP60 B 305 1012 280 + Initial flare nut size (Unit : mm) F G R410A Outdoor unit : 6.35 + R410A Outdoor unit : 12.7 + 830 804 R407C Outdoor unit : 9.52 R407C Outdoor unit : 15.88 Outdoor unit (SUZ) : 6.35 15.88 290 1070 1044 R407C Outdoor unit : 9.52 + C D E Service space:500 or more 50~150 29 450 Refrigerant piping flare connection (liquid : F copper tube):HP Refrigerant piping flare connection (gas :G copper tube):LP Drain R1(External thread) Electrical parts box Drain Pump (Option) Set Drain Pipe (Option) ... Flexible joint VP-25(I.D. :32) Filter 55 Access door 81 C B 81 197 450 Lifting bolt hole (14s22) C 13 277 45 80 85 24 282 288 256 176 Air inlet 7 E 13 D 30 10- :3 (RP35,50) 12- :3 (RP60) 6 40 2 179 1 243 10 35 227 109 10 3.5 21 In case of rear inlet 30 61 4 81 A 44 75 640 30 B 10 18 56 355 365~465 159 1 2 3 4 5 6 7 10- :3 (RP35,50) 12- :3 (RP60) A 10 Model Unit : mm 5 Air outlet 3.5 3 Keep duct-work length 850mm or more. Be sure to apply the air filter near the air inlet grille. In case of bottom inlet 10- :3 (RP35,50) 12- :3 (RP60) Air outlet 40 15 176 256 10 3.5 10 7 81 C B 81 A Air inlet PEAD-RP71EA Service space:500 or more F 15.88 55 2 35 1 Air inlet 375 12-:3 44 E 75 D 243 6 5 7 Air outlet 4 3 Keep duct-work length 850mm or more. Be sure to apply the air filter near the air inlet grille. 28 B 81 10 C A 13 307 45 122 113 53 81 80 30 10 680 B 365~465 323 308 169 20 30 C Lifting bolt hole (14x22) 81 210 7 140 6 282 5 3.5 30 4 40 3 Refrigerant piping flare connection (liquid :9.52 copper tube):HP Refrigerant piping flare connection (gas :F copper tube):LP Drain R1 (External thread) Electrical parts box Drain Pump (Option) Set Drain Pipe (Option) ... Flexible joint VP25(I.D.:32) Filter 319 261 181 2 3.5 1 12-:3 A 81 197 450 Access door 10 (Unit : mm) A B C D E Model RP71 1012 280 290 1070 1044 + Initial flare nut size 50~150 29 450 13 30 PEAD-RP60GA PEAD-RP71GA Unit : mm (Unit : mm) J Model A B C D E F G H RP60 1125 1090 1050 1012 7 840 8 Outdoor unit(SUZ) : 6.35 Other outdoor unit : 9.52 + 15.88 RP71 1125 1090 1050 1012 7 840 8 9.52 15.88 + Initial flare nut size 29 PEA-RP71EA Unit : mm Refrigerant-pipe flared connection :9.52(3/8) Drainage pan connection R1 70 40 672 (Drainage pan) 11 Refrigerant-pipe flared connection :15.88(5/8) 11 Wiring entry(2-:22holes) Service panel (Condenser/evaporator temperature thermistor) 105 510 35 20 345 Electrical parts box Room temperature thermistor 24.5 (130) 12-:2.9 holes For air outlet duct connection 530 690 200 200 Terminal block 70 25 40 4-12 30 oblong Suspension bolt holes 125 125 15 35 Heat insulator t10 25 25 40 650 Air outlet duct flange Air outlet 730 Mounting plate 300 220 3.2 120 242 14 Heat insulator t10 600 Service space (opening) in the ceiling Air intake 70 (530) 900 300 100 Air outlet 30 145 175 55 50 45 14-:2.9 holes For air intake duct connection 145 11 22.5 562 (Drainage pan) 155 90 155 (10) 339 21 155 22.5 20 20 15 265 690 15 20 250 75 60 418 Air intake Air intake duct flange 15 Service panel (Room temperature thermistor) 85 85 25 381 (10) Unit: mm OUTDOOR UNIT SUZ-KA25VA SUZ-KA25VAH SUZ-KA35VA SUZ-KA35VAH Drain hole :42 (SUZ-KA25/KA35VA) Drain hole :33 (SUZ-KA25/KA35VAH) Bolt pitch for installation 304~325 44 17.5 40 2 holes 10X21 Service panel Air out 22.3 23 Liquid refrigerant pipe joint Refrigerant pipe (flared) :6.35 Handle 35 69 302.5 170.5 Service port 500 Bolt pitch for installation 800 REQUIRED SPACE Basically open 100mm or more without any obstruction in front and on both sides of the unit. ore or m m m 100 100 mm or m ore mm 200 Gas refrigerant pipe joint Refrigerant pipe (flared) :9.52 99.5 10 164.5 280 150 ore or m 350 mm or m ore Open two sides of left, right, or rear side. 31 43 285 Air in 550 344.5 400 Air in SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA Unit: mm Drain holes :33 515 299 40 360 330 51 34 66 500 840 121 80 Service panel 155 90 35 30 430 850 Liquid refrigerant pipe joint Refrigerant pipe(flared) :6.35·····(SUZ-KA50/KA60VA) :9.52·····(SUZ-KA71VA) 198 REQUIRED SPACE Open as a rule 500mm or more if the front and both sides are open 100mm or more Open as a rule 500mm or more if the back, both sides and top are open 100mm or more 200mm or more if there are obstacles to both sides 350mm or more 32 Gas refrigerant pipe joint Refrigerant pipe(flared) :12.7·····(SUZ-KA50VA) :15.88···(SUZ-KA60/KA71VA) Unit : mm WIRED REMOTE CONTROLLER 19.5 43.5 120 130 33 Unit : mm WIRELESS REMOTE CONTROLLER SLZ-KA25/35/50VAL SEZ-KC25,KA35/50/60/71VA(Option) 57 17.5 h 140 ON/OFF AUTO COOL HEAT DRY TOO WARM TOO COOL FAN SELECT VANE TIME MODE RESET Installation area • Area in which the remote controller is not exposed to direct sunshine • Area in which there is no heating source nearby • Area in which the remote controller is not exposed to cold (or warm) winds • Area in which the remote controller can be operated easily • Area in which the remote controller is beyond the reach of children Installation method Attach the remote controller holder to the desired location using two tapping screws. Place the lower end of the controller into the holder. Wireless remote controller (Accessory) Wall Remote controller holder (Accessory) Fixing screw (Accessory) • The signal can travel up to approximately 7 meters (in a straight line) within 45 degrees to both right and left of the center line of the receiver. In addition, the signal may not be received if there are interferences of fluorescent lights or strong sunlight. 34 Unit : mm WIRELESS REMOTE CONTROLLER 159.3 58 19 55 35 4 WIRING DIAGRAM MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA INDOOR UNIT DISP REC P.C.BOARD MV1 ML1 MV2 ML2 2 1 CN 2 106 3 CN113 4 RT15 1 2 3 CN112 4 5 6 RT12 RT13 RT14 RT11 CN 111 LS1 CN 1X1 LS2 CN 1Y1 230V~ TB TO OUTDOOR UNIT CONNECTING 12-24V S1 S2 S3 BLK WHT WHT RED 6 CN 125 5 5 5 CN 151 MF1 MF2 5 5 5 1 2 3 4 5 6 1 2 3 4 5 6 CN 152 CN211 CN212 F11 DB111 T11 NR11 3 2 CN201 1 3 2 CN202 1 LD103 INDOOR ELECTRONIC CONTROL P.C. BOARD GRN [LEGEND] SYMBOL DB111 NAME SYMBOL NAME SYMBOL NAME DIODE STACK ML2 DAMPER LOCK MOTOR (LEFT) RT14 INDOOR COIL THERMISTOR (MAIN 2) TR15 INDOOR COIL THERMISTOR (MAIN 3) F11 FUSE (T3.15AL250V) MV1 HORIZONTAL VANE MOTOR LS1 DAMPER LIMIT SWITCH (OPEN) MV2 DAMPER MOTOR NR11 VARISTOR LS2 DAMPER LIMIT SWITCH (CLOSE) MF1 UPPER INDOOR FAN MOTOR RT11 ROOM TEMPERATURE THERMISTOR MF2 LOWER INDOOR FAN MOTOR RT12 INDOOR COIL THERMISTOR (MAIN 1) ML1 DAMPER LOCK MOTOR (RIGHT) RT13 INDOOR COIL THERMISTOR (SUB) NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing. 2. Use copper conductors only. (For field wiring) 3. Symbols below indicate : /: Terminal block, : Connector 36 T11 TRANSFORMER SLZ-KA25VAL SLZ-KA25VA SLZ-KA35VAL SLZ-KA35VA SLZ-KA50VAL SLZ-KA50VA GRILLE TB4 S1 GRY 7 PINK 8 5 7 WHT 9 (FAN) FAN 1 1 X1 ORN 3 (POWER) CND 1 I.B BLU ORN BLU RED WHT RED YLW 1 RED 3 (POWER 1 BOARD) CNDK FUSE TRANS 3 BLU (CONTROL) CN3C DC13.1V 1 2 CN2S(WHT) X6 X5 X4 ZNR X7 X6 X5 X4 X7 SW1 SW2 GRN (VANE) CN6V 5 4 5 6 VLT 3 7 8 9 1 2 BLK RED (2 PHASE) (INTAKE) CN29 CN20 1 2 1 2 3 MODELS LED2 WHT (LIQUID) CN21 1 2 SKYBLU See fig:+1 2 WHT (DRAIN) CN31 GRY 1 BRN REMOTE CONTROLLER CN90 (WIRELESS) WHT 6 PINK 5 BLU 4 RED 3 YLW 2 ORN 1 RED CN41 BLU CN51 YLW ORN 12345 CN32 W.R <fig:+1> LED1 CN2L WHT ON OFF RU WHT LED3 12345 SW2 BLK WHT (POWER 1 BOARD) 2 CN2D X1 SW3 SWE ON ON OFF OFF BLU (REMOCON) CN22 1 2 SW2 KA25 ON OFF KA35 ON OFF KA50 ON OFF 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 BLU LED1 BLU SKY BLU 3 BLU 3 (D·U·M) CNP 9 LED2 VLT 6 BZ BLU 5 CNB 1 1 2 3 AC220-240V CNSK(RED) 4 YLW 9 2 3 ORN W.B RED 3 (D·HEATER) CNC 3 YLW YLW RED 1 RED YLW 9 C1 BRN BRN H2 P.B 1 ORN BLU YLW DP WHT YLW 5 10 8 5 MF 7 4 RED 6 ORN 5 5 BLK 5 TO OUTDOOR UNIT S3 3 MV YLW 2 MV WHT 1 MV S2 BLU 5 YLW MV * Case of wired model 9 TB15 1 2 DS SYMBOL SYMBOL NAME INDOOR POWER BOARD W.B TO MA-REMOTE } CONTROLLER DC8.7-13V NAME WIRELESS REMOTE CONTROLLER BOARD INDOOR CONTROLLER BOARD RU RECEIVING UNIT CN2L CONNECTOR(LOSSNAY) BZ BUZZER CN32 CONNECTOR(REMOTE SWITCH) LED1 LED(RUN INDICATOR) CN41 CONNECTOR(HA TERMINAL-A) LED2 LED(HOT ADJUST) CN51 CENTRALLY CONTROL SW1 SWITCH(HEATING ON/OFF) FUSE FUSE(T6.3AL250V) SW2 LED1 POWER SUPPLY(I.B) C1 CAPACITOR(FAN MOTOR) LED2 POWER SUPPLY(I.B) DP DRAIN PUMP LED3 TRANSMISSION(INDOOR-OUTDOOR) DS DRAIN SENSOR SW2 SWITCH(CAPACITY CODE) H2 DEW PREVENTION HEATER SW3 SWITCH(MODE SELECTION) MF FAN MOTOR SWE SWITCH(EMERGENCY OPERATION) MV VANE MOTOR X1 DRAIN PUMP/DEW PREVENTION HEATER X4 RELAY(FAN MOTOR LL) X5 RELAY(FAN MOTOR Lo) X6 RELAY(FAN MOTOR Hi) X7 RELAY(FAN MOTOR Me) ZNR VARISTOR I.B TH2 * Case of wireless model [LEGEND] P.B TH5 TH1 TB4 TB15 TH1 TH2 TH5 SWITCH(COOLING ON/OFF) TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP.THERMISTOR (0/15kΩ, 25/5.4kΩ DETECT) PIPE TEMP.THERMISTOR/LIQUID (0/15kΩ, 25/5.4kΩ DETECT) COND./EVA.TEMP.THERMISTOR (0/15kΩ, 25/5.4kΩ DETECT) Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. + For details on how to operate self-diagnosis, refer to the service manuals etc. 37 SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KD50VA(L) SEZ-KD60VA(L) SEZ-KD71VA(L) INSIDE SECTION OF CONTROL BOX TB15 1 2 TO MA REMOTE CONTROLLER I.B. ;For SEZ-KD • VA SW1 1 SW2 CN32 CN01 (Black) 3 CN3C (Blue) CN41 CN51 DC310~340V Rectify circuit ZNR01 L1:only SEZ-KD71VA(L) FUSE U LED2 LED3 L1 LED1 CN90 5 U CN22 (Blue) ON OFF SWE 3 ZNR02 12 CN2L 1 DSA CN44 CN4F 123456789 34 123456789 1234 CN20 (Red) 1234 12 X1 CNMF 7654 1 3 1 CNP (Blue) W.B. CN4F TB4 S1 S2 CN1 S3 LED1 BZ1 RU RECEIVER SW1 SW2 ;For SEZ-KD • VAL t° FS t° TH2 t° TH5 M 1~ M TH1 Fan motor Optional Parts Drainpump Optional Parts SYMBOL EXPLANATION SYMBOL I.B. SYMBOL NAME INDOOR CONTROLLER BOARD W.B. NAME WIRELESS REMOTE CONTROLLER BOARD FUSE AC250V 6.3A RU RECEIVING UNIT ZNR01,02 VARISTOR BZ1 BUZZER DSA ARRESTER LED1 LED (RUN INDICATOR) X1 AUX. RELAY SW1 SWITCH (HEATING ON/OFF) CN2L CONNECTOR (LOSSNAY) SW2 CN32 CONNECTOR (REMOTE SWITCH) TH1 INTAKE AIR TEMP. THERMISTOR CN41 CONNECTOR (HA TERMINAL-A) TH2 PIPE TEMP. THERMISTOR/LIQUID CN51 CONNECTOR (CENTRALLY CONTROL) TH5 COND. /EVA. TEMP. THERMISTOR LED1 POWER SUPPLY(I.B.) L1 AC REACTOR(POWER FACTOR IMPROVEMENT) LED2 POWER SUPPLY(I.B.) FS FLOAT SWITCH LED3 TRANSMISSION(INDOOR-OUTDOOR) SW1 SWITCH (FOR MODE SELECTION) TB4 TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) SW2 SWITCH (FOR CAPACITY CODE) SWE CONNECTOR (EMERGENCY OPERATION) TB15 TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) FUSE SWITCH (COOLING ON/OFF) NOTE) 1. Since the outdoor side electric wiring may change,be sure to check the outdoor unit electric wiring diagram for servicing. 2. Indoor and outdoor connecting wires have polarities, make sure to match terminal numbers(S1,S2,S3) for correct wirings. 3. Symbols used in wiring diagram above are, :Connector, :Terminal Block. 38 TO OUTDOOR UNIT 39 INDOOR CONTROLLER BOARD I.B. RELAY (FAN MOTOR Lo) RELAY (FAN MOTOR HI) X5 X6 ZNR VARISTOR RELAY (FAN MOTOR LL) X4 SWE SWITCH (EMERGENCY OPERATION) SW3 SWITCH (MODE SELECTION) SW2 SWITCH (CAPACITY CODE) LED3 TRANSMISSION (INDOOR-OUTDOOR) LED2 POWER SUPPLY (I.B.) LED1 POWER SUPPLY (I.B.) FUSE FUSE (6.3A) CN90 CONNECTOR (WIRELESS) CN51 CENTRALLY CONTROL CN41 CONNECTOR (HA TERMINAL-A) TH5 TH2 TH1 TB15 X4 CN90 (0°C/15kΩ. 25°C/5.2kΩ DETECT) COND./EVA. TEMP. THERMISTOR (0°C/15kΩ. 25°C/5.2kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (0°C/15kΩ. 25°C/5.2kΩ DETECT) INTAKE AIR TEMP. THERMISTOR TRANSMISSION LINE) TERMINAL BLOCK (REMOTE CONTROLLER TH1 RED (INTAKE) CN20 1 2 BLU (REMOCON) CN22 1 2 LED1 WHT (POWER 1 BOARD) 2 CN2D WHT (LIQUID) CN21 1 2 TH2 I.B. 1 3 BLU (CONTROL) CN3C LED2 1 3 ORN (POWER) CND TB15 1 2 TB4 S1 S2 S3 TO MA-REMOTE CONTROLLER DC8.7-13V 1 2 DC13.1V CN2S(WHT) TRANS 1 2 3 AC220-240V CNSK(RED) P.B. TO OUTDOOR UNIT NOTE: 1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 4. The wiring between MA-REMOTE CONTROLLER and TB15 is included in the package. TH5 BLK (2 PHASE) CN29 1 2 ZNR FUSE LED3 RED 1 3 (POWER BOARD) CNDK TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) FAN MOTOR TB4 X4 X5 NAME CN41 MF CN51 X5 CAPACITOR (FAN MOTOR) CN32 CN2L X6 C SYMBOL 12345 SW2 CN32 CONNECTOR (REMOTE SWITCH) CN2L CONNECTOR (LOSSNAY) INDOOR POWER BOARD NAME ON OFF SWE SW3 ON ON OFF OFF 1 12345 X6 WHT 1 2 3 4 5 6 7 (FAN) FAN 7 6 5 4 3 2 1 7 6 5 4 3 2 1 INSERT C MF BLU 7 6 5 4 3 2 1 P.B. SYMBOL [LEGEND] The motor connector is connected with 230V, 240V power at factory shipment. If 220V power is used, Insert the attachment. Color/Power source WHT/230,240V BLU/220V SEZ-KC25VA SEZ-KA35VA SEZ-KA50VA SEZ-KA60VA SEZ-KA71VA MF TB4 BRN 3 4 5 6 7 8 1 2 3 4 5 6 7 8 BLU 2 YLW TO OUTDOOR UNIT S3 1 ORN C1 BLU YLW BLK RED ORN WHT S1 S2 RED P.B 3 4 5 6 7 WHT (FAN) FAN ORN BLU 3 BLU 1 RED WHT 2 RED BRN BLU BLK 1 WHT 1 2 3 AC220-240V CNSK(RED) RED 1 (POWER BOARD) CNDK FUSE ORN (POWER) CND 3 1 I.B TRANS 3 BLU (CONTROL) CN3C 1 2 DC13.1V CN2S(WHT) X6 X6 WHT (POWER BOARD) CN2D X4 SW3 1 2 BLK WHT LED3 12345 LED1 CN2L BLK RED (2 PHASE) (INTAKE) CN20 CN29 12345 CN32 CN51 CN41 CN90 1 2 1 2 See fig:+1. LED2 WHT (LIQUID) CN21 1 2 BLU (REMOCON) CN22 1 2 BLU ON OFF SW2 ON OFF X5 ZNR X4 BLU SWE ON OFF X5 TB15 [LEGEND] 1 SYMBOL SYMBOL NAME P.B INDOOR POWER BOARD C1 I.B INDOOR CONTROLLER BOARD MF CN2L CONNECTOR(LOSSNAY) TB4 CN32 CONNECTOR(REMOTE SWITCH) TB15 CN41 CONNECTOR(HA TERMINAL-A) CN51 CENTRALLY CONTROL TH1 CN90 CONNECTOR(WIRELESS) FUSE FUSE(T6.3AL250V) TH2 LED1 POWER SUPPLY(I.B) LED2 POWER SUPPLY(I.B) TH5 LED3 TRANSMISSION(INDOOR-OUTDOOR) SW2 SWITCH(CAPACITY CODE) SW3 SWITCH(MODE SELECTION) SWE SWITCH(EMERGENCY OPERATION) RELAY(FAN MOTOR LL) X4 RELAY(FAN MOTOR Lo) X5 X6 RELAY(FAN MOTOR Hi) ZNR VARISTOR NAME 2 TH5 CAPACITOR(FAN MOTOR) TH1 TH2 FAN MOTOR TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) <fig:+1> MODELS ROOM TEMP.THERMISTOR (0/15kΩ,25/5.4kΩ DETECT) PIPE TEMP.THERMISTOR/LIQUID (0/15kΩ,25/5.4kΩ DETECT) COND./EVA.TEMP.THERMISTOR (0/15kΩ,25C/5.4kΩ DETECT) SW2 KA35 ON OFF KA50 ON OFF KA60 ON OFF KA71 ON OFF 12345 12345 12345 12345 Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. Since the indoor fan motor(MF) is connected with 50Hz power, if 60Hz power is used, change the wiring connection shown in fig:+2. <fig:+2> Indoor Fan Motor(MF) for 60Hz BLUE 50 YELLOW 60 BLUE +For details on how to operate self-diagnosis, refer to the service manuals etc. 40 } TO MA-REMOTE CONTROLLER DC8.7-13V PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA PLA-RP71BA2 <Table 1> SW1 (MODEL SELECTION) [LEGEND] SYMBOL I.B CN2L CN32 CN41 CN51 FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 DCL DP FS MF MV NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) +See table 1 SWITCH (CAPACITY CODE) +See table 2 CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) REACTOR DRAIN PUMP DRAIN FLOAT SWITCH FAN MOTOR VANE MOTOR SYMBOL TB4 NAME TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (0 / 15k, 25 / 5. 4k DETECT) PIPE TEMP. THERMISTOR/LIQUID (0 / 15k, 25 / 5. 4k DETECT) COND. / EVA. TEMP. THERMISTOR (0 / 15k, 25 / 5. 4k DETECT) TB5,TB6 TH1 TH2 TH5 OPTION PART W.B BZ LED1 LED2 RU SW1 SW2 SW1 SETTING MODELS PLA-RP·BA 1 2 3 4 5 PLA-RP71BA2 1 2 3 4 5 ON OFF ON OFF <Table 2> SW2 (CAPACITY CODE) SW2 CAPACITY SETTING 1 2 3 4 5 35 PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP) 1 2 3 4 5 50 1 2 3 4 5 60 1 2 3 4 5 71 ON OFF ON OFF ON OFF ON OFF The black square (■) indicates a switch position. Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. Refer to tables 1 and 2. TRANSMISSION WIRES DC12V 2 1 TB6 VANE CNV(WHT) SW1 20 18 16 14 12 10 8 6 4 2 J41 J42 SW2 19 17 15 13 11 9 7 5 3 1 CN32 (WHT) 1 CN51(WHT) Pair No. 5 CN2L LED3 3 1 3 AUTO GRILLE CN3G 1 (BLK) WIRELESS CN90 (WHT) 9 5 5 M M M M MV MV MV MV GRILLE LED2 1 4 4 CNB LED1 2 1 OUTDOOR 1 3 5 CN01 3 INDOOR/OUTDOOR COMMUNICATION CN3C 1 CN41(WHT) 4 (BLU) 1 2 REMOCON CN22 1 SWE BZ SW1 LED2 SW2 LED1 RU I-SEE SENSOR 1 6 MT I-SEE SENSOR CORNER PANEL (OPTION PART) 1 4 4 1 2 t° t° TH2 TH5 t° TH1 1 FUSE DC325V RECTIFICATION (BLU) 7 FAN CNMF (WHT) 4 MS 3 5 M 3 1 (BLK) 1 3 ON OFF AUTO GRILLE I-SEE FLOAT SW LIQUID/PIPE INTAKE POWER I-SEE SENSOR SENSOR MOTOR CN4F CN44 CN20 CNAC CN4Y CN6Y (WHT) (WHT) (RED) (WHT) (WHT) (RED) 9 5 YLW R.B I.B 5 DCL TB5 2 1 FS U.B 3 1 CN3G 5 3 1 CN3A X1 1 1 D.U.M 3 CNP (BLU) YLW ORN TB4 YLW S1 ORN S2 S3 TO OUTDOOR UNIT ORN BRN M 3~ 1~ MF DP + Be sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in fan motor.) AUTOMATIC FILTER ELEVATION PANEL (OPTION PART) W.B Notes: 1.SymboIs used in wiring diagram above are, :Connector, : Terminal (block). 2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system for power and signal. + :For power supply system of this unit, refer to the caution label located near this diagram. 41 PLA-RP35AA [LEGEND] SYMBOL P.B I.B FUSE ZNR BCR CN2L CN32 CN41 CN51 LED1 LED2 LED3 X1 X4 SW1 SW2 SWE C PLA-RP50AA NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE(T6.3AL250V) VARISTOR FAN CONTROL ELEMENT CONNECTOR(LOSSNAY) CONNECTOR(REMOTE SWITCH) CONNECTOR(HA TERMINAL-A) CONNECTOR(CENTRALLY CONTROL) POWER SUPPLY(I.B) POWER SUPPLY(I.B) TRANSMISSION(INDOOR-OUTDOOR) RELAY(DRAIN PUMP) RELAY(FAN MOTOR) SWITCH(MODEL SELECTION) See table 1 SWITCH(CAPACITY CODE) See table 2 CONNECTOR(EMERGENCY OPERATION) CAPACITOR(FAN MOTOR) PLA-RP60AA SYMBOL MF MV H2 DP DS TB4 PLA-RP71AA NAME SYMBOL NAME FAN MOTOR W.B WIRELESS REMOTE CONTROLLER BOARD VANE MOTOR RU RECEIVING UNIT DEW PREVENTION HEATER BZ BUZZER DRAIN PUMP LED1 LED(RUN INDICATOR) DRAIN SENSOR LED2 LED(HOT ADJUST) SW1 SWITCH(HEATING ON/OFF) TERMINAL BLOCK (INDOOR/ OUTDOOR CONNECTING LINE) SW2 SWITCH(COOLING ON/OFF) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP.THERMISTOR Please set the voltage using the (0°C/15kΩ,25°C/5.4kΩ DETECT) remote controller. For the setting method, please refer to PIPE TEMP.THERMISTOR/LIQUID the indoor unit Installation Manual. (0°C/15kΩ,25°C/5.4kΩ DETECT) COND./EVA. TEMP. THERMISTOR (0°C/15kΩ,25°C/5.4kΩ DETECT) WIRED REMOTE CONTROLLER BOARD TB5, TB6 TH1 TH2 TH5 R.B GRILLE MV MV 5 MV 5 MV 5 5 H2 5 MF CN2S (WHT) 2 1 1 2 3 6 7 4 8 9 5 10 1 2 3 CNSK (RED) P.B 3 2 1 DC 13.1V TB4 YLW S1 ORN S2 ORN S3 BRN TO OUTDOOR UNIT 5 1 2 3 DP X4 BCR X4 X1 D.HEATER 1 3 1 3 CNC(RED) POWER CNDK (RED) BRN ORN BLK WHT YLW ORN RED WHT D.U.M 1 3 CNP (BLU) YLW YLW YLW YLW FAN 1 3 5 (WHT) I.B VANE 1 3 POWER 1 2 1 3 CND POWER INDOOR/OUTDOOR CN6V (GRN) (ORN) CN2D COMMUNICATION (WHT) CN3C (BLU) CN51 CN41 CN2L ZNR FUSE RED WHT BLK C X1 CN32 SW2 SW1 DS Refer to tables 1 and 2. LIQUID CN21 (WHT) 1 2 PIPE CN29 (BLK) 1 2 TH1 2 1 BZ 9 REMOCON CN22 WIRELESS (BLU) CN90 (WHT) 1 2 BLU BLU SWE ON OFF LED3 LED2 LED1 HEATER D.SENSOR INTAKE CN31 CN20 CN24 (WHT) (RED) (YLW) 1 2 3 1 2 W.B LED2 LED1 SW1 SW2 CNB R.B TB5 1 2 TB6 TRANSMISSION WIRES DC12V TH2 RU TH3 Table 1 Notes: SW1 1. SymboIs used in wiring diagram above are, : Connector, MODELS Service board : Terminal (block). 1 2 3 4 5 ON PLA-RP. AA 2. Indoor and outdoor connecting wires have poIarities, make sure to match OFF terminal numbers (S1, S2, S3) for correct wirings. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system of power and signal. Table 2 MODELS SW2 Service board PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA 42 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 ON OFF ON OFF ON OFF ON OFF PCA-RP50KA PCA-RP60KA PCA-RP71KA [ LEGEND] SYMBOL I.B CN2L CN32 CN41 CN51 FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 R.B DCL MF MV NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) + See table 1 SWITCH (CAPACITY CODE) + See table 2 CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) WIRED REMOTE CONTROLLER BOARD REACTOR FAN MOTOR VANE MOTOR SYMBOL TB4 TB5,TB6 NAME TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (0°C / 15kΩ, 25°C / 5. 4kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (0°C / 15kΩ, 25°C / 5. 4kΩ DETECT) COND. / EVA. TEMP. THERMISTOR (0°C / 15kΩ, 25°C / 5. 4kΩ DETECT) TH1 TH2 TH5 OPTIONAL PARTS W.B BZ LED1 LED2 RU SW1 SW2 DP FS PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP) DRAIN PUMP DRAIN FLOAT SWITCH Refer to tables 1 and 2 DCL TB5 2 1 TRANSMISSION WIRES DC12V 2 1 TB6 YLW R.B I.B VANE CNV (WHT) SW1 20 18 16 14 12 10 8 6 4 2 J41 J42 SW2 19 17 15 13 11 9 7 5 3 1 Pair No. CN32 (WHT) 1 5 CN2L LED3 LED2 2 1 LED1 3 1 CN41 (WHT) 4 1 2 INDOOR/OUTDOOR COMMUNICATION CN3C (BLU) REMOCON CN22 (BLU) 1 SWE OUTDOOR 1 3 5 CN01 (BLK) 1 3 CN51 (WHT) DC311~339V RECTIFICATION ON OFF 1 WIRELESS CN90 (WHT) 9 FLOAT SW CN4F (WHT) 1 LIQUID/PIPE INTAKE CN44 CN20 (WHT) (RED) 4 4 1 2 t° t° TH2 TH5 t° TH1 1 FUSE 7 FAN CNMF (WHT) 4 MS 9 CNB 5 M MV BZ SW1 LED2 SW2 LED1 RU W.B (OPTIONAL PARTS) When attaching drain pump (optional parts), remove the jumper connector CN4F and fit the drain float switch (FS). When attaching drain pump (optional parts) FLOAT SW CN4F (WHT) 1 3~ YLW ORN X1 1 1 D.U.M 3 TB4 YLW S1 ORN S2 S3 TO OUTDOOR UNIT ORN BRN CNP (BLU) M 1~ DP MF (OPTIONAL PARTS) +Be sure to turn off the source power and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor) 4 FS <Table 1> SW1 (MODEL SELECTION) SW1 Service 1 2 3 4 5 <Table 2> SW2 (CAPACITY CODE) SW2 MODELS Service PCA-RP50KA ON OFF PCA-RP60KA PCA-RP71KA 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 ON OFF ON OFF ON OFF The black square (■) indicates a switch position. Notes: 1. 2. 3. 4. SymboIs used in wiring diagram above are, :Connector, :Terminal (block). Indoor and outdoor connecting wires are made with poIarities, make wiring matching terminal numbers (S1, S2, S3). Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system for power and signal. + : For power supply system of this unit, refer to the caution label located near this diagram. 43 PCA-RP50GA NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD FUSE (T6.3AL250V) VARISTOR CONNECTOR(LOSSNAY) CONNECTOR(REMOTE SWITCH) CONNECTOR(HA TERMINAL-A) CONNECTOR(CENTRALLY CONTROL) SWITCH (MODEL SELECTION) See Table 1. SWITCH (CAPACITY CODE) See Table 2. SWITCH(EMERGENCY OPERATION) RELAY(DRAIN PUMP) RELAY(FAN MOTOR) FAN CONTROL ELEMENT POWER SUPPLY(I.B) POWER SUPPLY(R.B) TRANSMISSION(INDOOR-OUTDOOR) CAPACITOR(FAN MOTOR) PCA-RP60GA SYMBOL MF MV DP DS TB4 TB5,TB6 TH1 TH2 TH5 R.B P.B CNDK (RED) 1 2 3 (OPTION) C THERMAL FUSE(98˚C10A:50GAH/117˚C16A:100GAH 110˚C16A:60,71,125,140GAH) HEATER HEATER THERMAL SWITCH HEATER CONTACTOR H1 26H 88H 1 2 BRN ORN YLW ORN RED WHT SW1 D.SENSOR INTAKE LIQUID PIPE CN31 CN20 CN21 CN29 (WHT) (RED) (WHT) (BLK) 1 2 3 BLK BLK Refer to tables 1 and 2 for service PCB. When installing optional drain pump, disconnect the CN31 jumper connector and replace it with the drain sensor (DS). CN31 DRAIN SENSOR (WHT) 1 2 3 When installing drain pump (Optional part). DS 1 2 1 2 REMOCON CN22 (BLU) 1 2 1 2 1 2 50~71 TYPE 6 6 6 TH2 100~140 TYPE 5 5 MV 9 CNB RU RECEIVER LED1 LED2 SW2 SW1 W.B 2 1 TRANSMISSION WIRES DC12V TB5 TH1 MV MV BZ 1 2 BLU BLU SW2 D.U.M 1 3 POWER 1 3 POWER 1 3 1 2 1 3 VANE CND CNDK CNP 6 INDOOR/OUTDOOR CN6V POWER (ORN) (RED) (BLU) ( ) CN2D(WHT) COMMUNICATION GRN CN3C(BLU) X4 X1 CN41 CN2L WIRELESS ZNR CN90 CN51 CN32 (WHT) X4 X1 LED3 LED2 LED1 BLK BLK BCR TB4 S1 S2 S3 YLW ORN ORN BRN FUSE FAN 1 3 5 (WHT) SWE ON OFF NAME WIRELESS REMOTE CONTROLLER BOARD(OPTION) RECEIVING UNIT BUZZER LED(RUN INDICATOR) LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF) DP RED WHT BLK I.B SYMBOL W.B RU BZ LED1 LED2 SW1 SW2 HEATER FS1,2 Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. CN2S (WHT) 1 2 DC13.1V 3 MF PCA-RP71GA NAME FAN MOTOR VANE MOTOR DRAIN PUMP (OPTION) DRAIN SENSOR (OPTION) TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE ) ROOM TEMP.THERMISTOR (0˚C/15kΩ, 25˚C/5.4kΩ DETECT) PIPE TEMP.THERMISTOR/LIQUID (0˚C/15kΩ, 25˚C/5.4kΩ DETECT) COND./EVA.TEMP.THERMISTOR (0˚C/15kΩ, 25˚C/5.4kΩ DETECT) WIRED REMOTE CONTROLLER BOARD BLK WHT [LEGEND] SYMBOL P.B I.B FUSE ZNR CN2L CN32 CN41 CN51 SW1 SW2 SWE X1 X4 BCR LED1 LED2 LED3 C PCA-RP50GA2 R.B 1 2 TB6 TH5 [Servicing] Fasten terminal of the terminal board "TB4"equips lock system. To remove the fastened terminal, pull it while pressing the protruding portion (locking lever) of the terminal. The fastened terminal protruding portion should face upward. Table 1 NOTES: 1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Make sure that the main power supply of the booster heater is independent. 4. Symbols used in wiring diagram above are, : Connector, : Terminal (block). MODELS PCA-RP·GA 1 2 3 4 5 ON OFF Table 2 MODELS PCA-RP50GA PCA-RP50GA2 PCA-RP60GA PCA-RP71GA 44 SW1 Service board SW2 Service board 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 ON OFF ON OFF ON OFF TO OUTDOOR UNIT t° 45 TH1 SYMBOL I.B. CN2A CN2L CN32 CN41 CN51 CN90 CN105 LED1 LED2 LED3 1 2 FS *1 1 2 3 4 CN4F CNXB2 (Red) 1 CN2L 23 4 5 CN51 OFF ON LED2 1 2 CNXC2 SWE LED1 4 3 2 1 CNXA2 (Blue) CN22 2 (Blue) 1 (Black) CN2A (Red) CN105 NAME SYMBOL NAME I.B. Indoor controller board Indoor controller board SW1 Switch (for mode selection) Connector (0-10V Analog input) SW2 Switch (for capacity code) Connector (Lossnay) SWE Connector (emergency operation) Connector (Remote switch) Connector (HA terminal-A) Power supply board P.B. F01 Connector (Centrally control) Fuse AC250V 6.3A ZNR01, 02 Varistor Connector (Wireless) DSA Arrester Connector (IT terminal) X01 Aux. relay LED(Power supply) X10 Aux. relay LED(Remote controller supply) LED(Transmission indoor-outdoor) SYMBOL EXPLANATION t° (Red) CN20 CN41 CN32 TB15 SYMBOL TH1 TH2 TH5 ACL FS TB4 M 1~ Drain pump CNP (Blue) X01 1 2 3 4 (Blue) X10 F01 CND 5 (Red) CNXC1 CNXA1 1 2 U ZNR01 3 Fan motor M 7 6 5 4 CNMF 1 DC280~340V Rectifier circuit TO OUTDOOR UNIT *1. Drain pump and float switch: only for PEAD-JA model S3 TB4 NOTE: 1. Since the outdoor side electric wiring may change be sure to NAME Intake air temp. Thermistor check the outdoor unit electric wiring for servicing. Pipe temp. Thermistor/liquid 2. Indoor and outdoor connecting wires are made with polarities, Cond./eva.temp. Thermistor make wiring matching terminal numbers (S1,S2,S3). AC reactor (Power factor improvement) Float switch 3. Symbols used in wiring diagram above are, terminal block, Terminal block connector. (Indoor/outdoor connecting line) Terminal block (Remote controller transmission line) *1 1 2 3 4 5 CNXB1 3 1 DSA ZNR02 U 1 P.B. S1 S2 TO MA REMOTE CONTROLLER PEAD-RP60JA(L) TH2 TH5 1 2 3 4 CN44 SW2 SW1 2 TB15 1 2 PEAD-RP50JA(L) t° LED3 CN90 1 CN3C 3 (Blue) I.B. 1 2 1 ACL INSIDE SECTION OF CONTROL BOX PEAD-RP35JA(L) PEAD-RP71JA(L) PEAD-RP35EA2 PEAD-RP50EA [LEGEND] NAME SYMBOL I.B. INDOOR CONTROLLER BOARD FUSE FUSE(T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR(LOSSNAY) CN24 CONNECTOR(HEATER) CN32 CONNECTOR(REMOTE SWITCH) CN41 CONNECTOR(HA TERMINAL-A) CN51 CONNECTOR(CENTRALLY CONTROL) CN90 CONNECTOR(WIRELESS) LED1 POWER SUPPLY(I.B.) LED2 POWER SUPPLY(REMOTE CONTROLLER) LED3 TRANSMISSION(INDOOR•OUTDOOR) SW1 SWITCH(MODEL SELECTION) SYMBOL SW2 SWE X1 X4 X5 X6 P.B. DRAIN PUMP PEAD-RP60EA PEAD-RP71EA NAME SWITCH(CAPACITY CORD) SWITCH(EMERGENCY OPERATION) RELAY(DRAIN PUMP) RELAY(FAN MOTOR) RELAY(FAN MOTOR) RELAY(FAN MOTOR) INDOOR POWER BOARD (OPTIONAL PARTS) TB4 TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK(REMOTE CONTROLLER) INTAKE AIR TEMP. THERMISTOR (0 /15kΩ, 25/5.4kΩ DETECT) TB5 TH1 TH2 PIPE TEMP. THERMISTOR/LIQUID (0 /15kΩ, 25/5.4kΩ DETECT) TH5 COND./EVA. TEMP. THERMISTOR (0 /15kΩ, 25/5.4kΩ DETECT) DRAIN PUMP DRAIN SENSOR CAPACITOR(FAN MOTOR) FAN MOTOR DP DS C MF NAME SYMBOL INSIDE SECTION OF CONTROL BOX DS TH1 TH2 TH5 B B L L U U 1 3 CN31 1 2 1 2 CN22 (BLU) CN20 (RED) I.B. 1 2 1 2 3 1 2 3 4 5 6 7 8 9 1 2 3 4 1 2 1 2 3 45 1 2 3 CN21 CN29 (WHT) (BLK) CN31 (WHT) CN90 (WHT) CN41 (WHT) CN24 (YLW) CN51 (WHT) CN32 (WHT) 1 2 1 2 SW1 CN2L (RED) SW2 SWE ON OFF LED1 LED2 LED3 2 1 WHT BLK X1 (BLU) CN3C O3B 1 R R N N ZNR W3B1 H L T K O3Y 1 R L N W 2 1 TO MA-REMOTE CONTROLLER DC8.7-13V TB4 S3 S2 S1 TO OUTDOOR UNIT 2 1 B L K W H T CN2S (WHT) X4 X1 FUSE (ORN) CND W B H L T K TB5 BL U B 2 L 1 U X4 X5 X6 X5 CN2D (WHT) 3 (RED) CNDK P.B. 1 CNSK (RED) 3 1 (BLU) CNP DP Optional parts X6 7 5 3 1 W P P B H N N L T K K K <PEAD-RP35•50•60EA, 35EA2> External static pressure 30Pa <PEAD-RP71•100•125•140EA, 100EA2> External static pressure 70Pa <PEAD-RP35•50•60EA, 35EA2> External static pressure 70Pa 1 2 3 4 5 6 Optional parts (RED) (WHT) BRN ORN YLW MF C SW1 SW2 Model selection Capacity cord switch switch 12345 35EA2 50EA 60EA 71EA 12345 12345 ON OFF 12345 12345 1 2 3 4 5 6 (RED) 1 2 3 4 5 6 MF MODELS (WHT) FAN ON OFF ON OFF ON OFF C <PEAD-RP71•100•125•140EA, 100EA2> External static pressure 130Pa NOTES: 1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Symbols used in wiring diagram above are, : Connector, : Terminal (block). 4. The wiring between MA-Remote controller and TB5 is included in the package. ON OFF 46 PEAD-RP60GA PEAD-RP71GA [LEGEND] NAME NAME SYMBOL SYMBOL I.B. INDOOR CONTROLLER BOARD SW1 SWITCH(MODEL SELECTION) FUSE FUSE(T6.3AL250V) SW2 SWITCH(CAPACITY CODE) ZNR VARISTOR SWE SWITCH(EMERGENCY OPERATION) CN2L CONNECTOR(LOSSNAY) X1 RELAY(DRAIN PUMP) X4 RELAY(FAN MOTOR) CN24 CONNECTOR(HEATER) CN32 CONNECTOR(REMOTE SWITCH) X5 RELAY(FAN MOTOR) CN41 CONNECTOR(HA TERMINAL-A) X6 RELAY(FAN MOTOR) CN51 CONNECTOR(CENTRALLY CONTROL) P.B. INDOOR POWER BOARD C CAPACITOR(FAN MOTOR) CN90 CONNECTOR(WIRELESS) MF LED1 POWER SUPPLY(I.B.) FAN MOTOR LED2 POWER SUPPLY(REMOTE CONTROLLER) TB4 TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) LED3 TRANSMISSION(INDOOR•OUTDOOR) NAME SYMBOL TERMINAL BLOCK(REMOTE CONTROLLER) TB5 TH1 INTAKE AIR TEMP.THERMISTOR (0 /15kΩ, 25/5.4kΩ DETECT) TH2 PIPE TEMP. THERMISTOR/LIQUID (0 /15kΩ, 25/5.4kΩ DETECT) TH5 COND./EVA. TEMP. THERMISTOR (0 /15kΩ, 25/5.4kΩ DETECT) INSIDE SECTION OF CONTROL BOX TH1 TH2 TH5 1 2 1 2 1 2 1 2 CN22 (BLU) CN20 (RED) CN21 (WHT) CN29 (BLK) B B L L U U I.B. 1 2 3 1 2 3 4 5 6 7 8 9 1 2 3 4 CN90 (WHT) CN41 (WHT) CN31 (WHT) 1 2 CN24 (YLW) 1 2 3 4 5 1 2 3 CN51 (WHT) CN32 (WHT) 1 2 SW1 CN2L (RED) SW2 SWE ON LED1 LED2 LED3 WHT BLK 2 1 OFF X1 (BLU) CN3C O3B1 R R N N ZNR (ORN) CND TO MA-REMOTE CONTROLLER DC8.7-13V W3B1 H L T K O3Y1 R L N W TB4 S3 S2 S1 TO OUTDOOR UNIT MODELS 60GA 71GA 2 1 U B L U 2 1 X1 FUSE W B H L T K TB5 BL X4 X5 X6 X5 CN2D (WHT) 2 1 W H T CN2S (WHT) B L K 3 (RED) CNDK 3 P.B. 1 1 (BLU) CNP X4 X6 7 5 3 1 G Y Y B R L L L Y W W K B B O L L R U K G CNSK (RED) (WHT) FAN *External static pressure CONNECTOR COLOR 220V * 1 2 3 4 5 6 (WHT) 230V 240V BLU 5Pa 10Pa 20Pa WHT 35Pa 50Pa 60Pa RED 50Pa 70Pa 75Pa (FACTORY SHIPMENT) BRN ORN YLW MF C SW1 SW2 Model selection Capacity cord switch switch 12345 12345 ON OFF 12345 ON OFF ON OFF NOTES: 1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Symbols used in wiring diagram above are, : Connector, : Terminal (block). 4. The wiring between MA-Remote controller and TB5 is included in the package. 47 PEA-RP71EA [LEGEND] SYMBOL SYMBOL NAME P.B INDOOR POWER BOARD I.B SW1 I.B INDOOR CONTROLLER BOARD SW2 FUSE FUSE(T6.3AL250V) SWE ZNR VARISTOR X4 CN2L CONNECTOR(LOSSNAY) X5 CN32 CONNECTOR(REMOTE SWITCH)) X6 CN41 CONNECTOR(HA TERMINAL-A) R.B CN51 CONNECTOR(CENTRALLY CONTROL) TB6 LED1 POWER SUPPLY(I.B) C LED2 POWER SUPPLY(R.B) LED3 TRANSMISSION(INDOOR • OUTDOOR) MF SYMBOL NAME SWITCH(MODEL SELECTION)+See table 1 SWITCH(CAPACITY CODE)+See table 2 SWITCH(EMERGENCY OPERATION) RELAY(FAN MOTOR) RELAY(FAN MOTOR) RELAY(FAN MOTOR) REMOTE CONTROLLER BOARD TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) TB2 TB4 CAPACITOR(FAN MOTOR) FAN MOTOR NAME TERMINAL BLOCK(INDOOR UNIT POWER(OPTION)) TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TB5 TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE) TH1 ROOM TEMPERATURE THERMISTOR (0˚C/15kΩ, 25˚C/5.4kΩ DETECT) TH2 PIPE TEMPERATURE THERMISTOR/LIQUID (0˚C/15kΩ, 25˚C/5.4kΩ DETECT) TH5 COND./EVA. TEMPERATURE THERMISTOR (0˚C/15kΩ, 25˚C/5.4kΩ DETECT) INDOOR UNIT P.B CN2S (WHT) 2 1 ORN 5 7 POWER 1 CNDK (RED) 3 POWER 1 CND (ORN) 3 ZNR X6 X5 X4 X6 X5 X4 LED3 LED2 LED1 SWE SW2 SW1 ON OFF CN24 Refer to tables 1 and 2. 1 2 1 3 POWER INDOOR/OUTDOOR COMMUNICATION CN2D CN3C (WHT) (BLU) WIRELESS 2 LIQUID CN21 CN90 1 (WHT) (WHT) 2 INTAKE CN20 REMOCON 2 1 (RED) CN22 1 (BLU) 2 PIPE CN29 1 (BLK) CN2L CN41 CN32 TB5 1 2 BLU 2 TH5 PEA-RP·EA BLU BLU 1 TH1 MODELS BLU R.B TH2 Table 1 ORN YLW 3 BRN WHT 1 WHT RED FAN (WHT) BLK 6 C I.B S3 2 FUSE 5 ORN BLU 1 TO OUTDOOR UNIT S2 1 WHT RED 4 BRN BLK 3 ORN 3 DC13.1V MF 2 TB4 S1 YLW CNSK (RED) TB6 TRANSMISSION WIRE DC12V Table 2 SW1 Manufacture/Service MODELS 1 2 3 4 5 ON OFF PEA-RP71EA SW2 Manufacture/Service Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit installation Manual. 1 2 3 4 5 ON OFF NOTES: 1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3. Symbols used in wiring diagram above are, : Connector, : Terminal (block). 4. This diagram shows the wiring of Indoor and Outdoor connecting wires(specification of 230V), adopting superimposed system of power and signal. 48 NOTES:1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing. 2. Use copper conductors only. (For field wiring) 3. Symbols below indicate. : Terminal block SUZ-KA25VA SUZ-KA35VA 49 NOTES:1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing. 2. Use copper conductors only. (For field wiring) 3. Symbols below indicate. : Terminal block SUZ-KA25VAH SUZ-KA35VAH 50 51 3~ MC U BLK WHT RED 1 3 SYMBOL CT C61,62,63 DB61,DB65 DSA F61 F701,F801,F901 HC930,IPM IC802 L61 L62 W MS V RED LDW LDV LDU U V P N IPM W R825 TR821 1 R61 3 5 MF MS 3~ CN932 3 5 F901 F801 R937A 1 T801 1 RT64 2 1 CN642 HC930 R937B IC802 RT68 CN644 RT65 RT61 RT62 CN641 4 1 LEV M 6 CN724 6 CT LD61 U F701 LD63 BRN U 1 CN721 LD-E1 2 F61 LD62 U LD-S L62 DSA PTC65 PTC64 X64 X63 21S4 BRN BLU RED GRN/YLW BLK S1 S3 S2 TB2 L N TB1 230V~ 12-24V CIRCUIT BREAKER NOTES: 1. About the indoor side electric wiring, NAME refer to the indoor unit electric wiring CURRENT-DETECTING RESISTOR diagram for servicing. CURRENT-DETECTING RESISTOR CURRENT-DETECTING RESISTOR 2. Use copper conductors only (for field wiring). TERMINAL BLOCK 3. Symbols below indicate. SWITCHING POWER TRANSISTOR :Terminal block TRANSFORMER RELAY REVERSING VALVE COIL 2 1 SYMBOL R61 R825 R937A, B TB1,TB52 TR821 T801 X63,X64 21S4 3 1 CN643 INVERTER P.C. BOARD NAME EXPANSION VALVE COIL COMPRESSOR FAN MOTOR CIRCUIT PROTECTION DEFROST THERMISTOR DISCHARGE TEMP. THERMISTOR FIN TEMP. THERMISTOR AMBIENT TEMP. THERMISTOR RT68 OUTDOOR HEAT EXCHANGER TEMP. THERMISTOR SYMBOL LEV MC MF PTC64,PTC65 RT61 RT62 RT64 RT65 CN931 C63 C62 C61 LD66 NAME CURRENT TRANSFORMER SMOOTHING CAPACITOR DIODE MODULE SURGE ABSORBER FUSE (T20AL 250V) FUSE (T3.15AL 250V) INTELLIGENT POWER MODULE INTELLIGENT POWER DEVICE REACTOR REACTOR BLK WHT 1 3 DB65 DB61 LD70 YLW BLU BRN L61 POWER SUPPLY ~/N 230V 50Hz TO INDOOR UNIT CONNECTING ORN SUZ-KA50VA SYMBOL CB1~3 CT1, 2 CT61 F64 F801 F911 HC930 HPS IPM L NAME SMOOTHING CAPACITOR CURRENT TRANSFORMER CURRENT TRANSFORMER FUSE (T2AL 250V) FUSE (T3.15AL 250V) FUSE (T1AL 250V) INTELLIGENT POWER MODULE HIGH PRESSURE SWITCH INTELLIGENT POWER MODULE REACTOR SYMBOL LEV MC MF NF NR64 PFC RS1~4 RT61 RT62 RT64 NAME EXPANSION VALVE COMPRESSOR FAN MOTOR NOISE FILTER VARISTOR POWER FACTOR CONTROLLER RESISTOR DEFROST THERMISTOR DISCHARGE TEMP. THERMISTOR FIN TEMP. THERMISTOR SYMBOL RT65 RT68 R64A,B R937A, B SSR61 TB1 TB2 T801 X64 21S4 NOTES: 1. About the indoor side electric wiring NAME refer to the indoor unit electric wiring AMBIENT TEMP. THERMISTOR diagram for servicing. OUTDOOR HEAT EXCHANGER TEMP. THERMISTOR RESISTOR 2. Use copper conductors only (for field wiring). RESISTOR 3. Symbols below indicate. SOLENOID COIL RELAY :Terminal block TERMINAL BLOCK TERMINAL BLOCK TRANSFORMER RELAY REVERSING VALVE COIL SUZ-KA60VA 52 PE NOISE FILTER P.C.BOARD GRN/YLW N S3 RED BLU WHT GRN LDE1 CT61 1 2 RED SYMBOL MC MF NF NR64 PFC R64A,B R937A, B RS1~4 RT61 RT62 RT64 RT61 RT62 CN661 1 2 3 4 RED BLK BLK BLK 4 YLW 1 RT68 7 8 LEV 6 CN795 5 6 7 CN702 3 2 S R CN4 1 2 RS2 RS1 T801 1 3 RS3 LD1 RS4 R937B R937A LD2 CB2 CT1 U U CN932 RED WHT BLK GRN MF POWER RT64 BOARD BLK WHT MC W RED V GRY PNK ORN BLU YLW LD9 IPM V CT2 W NOTES: 1.About the indoor electric wiring, refer to the indoor unit electric wiring diagram for servicing. 2.Use copper conductors only (for field wiring). 3.Symbols below indicate. :Terminal block :Connector 1 2 CN701 NAME SYMBOL NAME COMPRESSOR RT65 AMBIENT TEMPERATURE THERMISTOR OUTDOOR FAN MOTOR OUTDOOR HEAT EXCHANGER RT68 TEMPERATURE THERMISTOR NOISE FILTER VARISTOR SSR61 SOLENOID COIL RELAY POWER FACTOR CONTROLLER T801 TRANSFORMER RESISTOR TB1 TERMINAL BLOCK TB2 TERMINAL BLOCK RESISTOR X64 RELAY RESISTOR 21S4 R.V. COIL DEFROST THERMISTOR DISCHARGE TEMPERATURE THERMISTOR FIN TEMPERATURE THERMISTOR RT65 CN681 CN663 1 2 1 2 1 21S4 CN901 1 2 3 5 NR64 TAB4 3 ELECTRONIC 1 2 3 5 CONTROL CN781 P.C.BOARD HPS RED RED [LEGEND] SYMBOL NAME CB1~3 SMOOTHING CAPACITOR CT1, 2 CURRENT TRANSFORMER CT61 CURRENT TRANSFORMER F64 FUSE (T2AL 250V) F801 FUSE (T3.15AL 250V) F911 FUSE (T1AL 250V) HC930 INTELLIGENT POWER MODULE HPS HIGH PRESSURE SWITCH IPM INTELLIGENT POWER MODULE REACTOR L LEV EXPANSION VALVE COIL 12-24V S2 S1 TO INDOOR UNIT CONNECTING 230V~TB2 TAB2 CN61 3 1 BLU NF F64 BLK BRN WHT BLU F911 R64A R64B SSR61 BLK BLK BLK LDE2 CN912 BLU BLU CN902 CN903 2 1 2 1 X64 YLW BLK L GRN 3 1 CN601 5 BLK BLK BLK PFC 2 1 CN5 7 6 5 4 3 2 1 CN2 BLK BLK F801 CB1 RED CB3 WHT CN801 L CN931 1 2 3 4 5 53 1 2 3 TAB1 HC930 CN3 1 2 POWER SUPPLY ~/N 230V 50Hz CIRCUIT BREAKER TB1 SUZ-KA71VA 5 REFRIGERANT SYSTEM DIAGRAM 5-1. INDOOR UNIT MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA Unit : mm Refrigerant pipe :9.52 (MFZ-KA25/35VA) Refrigerant pipe :12.7 (MFZ-KA50VA) (with heat insulator) Indoor coil thermistor RT12 (main) Distributor Indoor heat exchanger Flared connection Indoor coil thermistor RT12, RT14, RT15 (main) RT13 (sub) Refrigerant flow in cooling Refrigerant flow in heating Room temperature thermistor RT11 Flared connection Refrigerant pipe :6.35 (with heat insulator) SLZ-KA·VA SEZ-KC·VA PCA-RP·KA PEAD-RP·JA(L) SLZ-KA·VAL SEZ-KA·VA PCA-RP·GA(2) PEAD-RP·GA SEZ-KD·VA PLA-RP·BA(2) SEZ-KD·VAL PLA-RP·AA PEAD-RP·EA(2) PEA-RP·EA Strainer(#50) Heat exchanger Refrigerant GAS pipe connection (Flare) Thermistor TH5 (Cond./Eva. temperature) Refrigerant flow in cooling Refrigerant flow in heating Refrigerant LIQUID pipe connection (Flare) Distributor with strainer(#50) Thermistor TH1 (Room temperature) Thermistor TH2 Pipe temperature (Liquid) Strainer(#50) 54 5-2. OUTDOOR UNIT SUZ-KA25VA SUZ-KA25VAH Unit:mm Refrigerant pipe ø9.52 (with heat insulator) 4-way valve Muffler Stop valve (with service port) Discharge temperature thermistor RT62 Flared connection Outdoor heat exchanger Muffler Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Compressor Defrost thermistor RT61 Strainer #100 Flared connection Refrigerant pipe ø6.35 (with heat insulator) SUZ-KA35VA Capillary tube ø3.0×ø2.0×240 LEV R.V. coil heating ON cooling OFF Stop valve (with strainar) Refrigerant flow in cooling Refrigerant flow in heating SUZ-KA35VAH Unit:mm Refrigerant pipe ø9.52 (with heat insulator) 4-way valve Muffler Stop valve (with service port) Discharge temperature thermistor RT62 Flared connection Outdoor heat exchanger Muffler Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Compressor Defrost thermistor RT61 Capillary tube ø3.0×ø1.8×600(×2) Flared connection Refrigerant pipe ø6.35 (with heat insulator) Strainer #100 Capillary tube ø3.0×ø2.0×240 Stop valve (with strainar) LEV R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating 55 SUZ-KA50VA Unit:mm Muffler 4-way valve #100 Refrigerant pipe ø12.7 (with heat insulator) Stop valve (with service port) Flared connection Discharge temperature thermistor RT62 Defrost thermistor RT61 Outdoor heat exchanger Ambient temperature thermistor RT65 Compressor Outdoor heat exchanger temperature thermistor RT68 Flared connection LEV Receiver Refrigerant pipe ø6.35 (with heat insulator) Stop valve (with strainer) Strainer #100 R.V. coil heating ON cooling OFF Capillary tube ø3.6×ø2.4×50 Refrigerant flow in cooling Refrigerant flow in heating SUZ-KA60VA Unit:mm Refrigerant pipe :15.88 (with heat insulator) Muffler 4-way valve #100 Stop valve (with service port) Flared connection Discharge temperature thermistor RT62 High-pressure switch Defrost thermistor RT61 Outdoor heat exchanger Ambient temperature thermistor RT65 Compressor Outdoor heat exchanger temperature thermistor RT68 Flared connection LEV Strainer Receiver #100 Stop valve Refrigerant pipe :6.35 (with heat insulator) Capillary tube :3.6:2.450 56 Strainer #100 R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating SUZ-KA71VA Unit:mm Refrigerant pipe :15.88 (with heat insulator) Capillary tube :1.8×:0.6×1000 Oil separator High-pressure 4-way valve switch Stop valve (with service port) Strainer #100 Defrost thermistor RT61 Discharge temperature thermistor RT62 Flared connection Compressor Flared connection Strainer Receiver #100 Stop valve Refrigerant pipe :9.52 (with heat insulator) LEV Capillary tube :3.6×:2.4×50 57 Strainer #100 Outdoor heat exchanger Ambient temperature thermistor RT65 Outdoor heat exchanger temperature thermistor RT68 R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating 6 PERFORMANCE CURVES FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA25VA(H) Cooling capacity Capacity correction factors 1.5 Indoor intake air Wet-bulb temperature() 1.4 1.3 1.2 26 1.1 24 1.0 22 20 18 0.9 0.8 0.7 0.6 -10 -5 0 5 10 15 20 25 30 35 40 45 Outdoor intake air Dry-bulb temperature() Total input (cooling) 1.5 Indoor intake air Wet-bulb temperature() Input correction factors 1.4 1.3 1.2 26 22 20 18 24 1.1 1.0 0.9 0.8 0.7 0.6 -10 -5 0 5 10 15 20 25 30 35 Outdoor intake air Dry-bulb temperature() 58 40 45 FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA35VA(H) Cooling capacity Capacity correction factors 1.5 Indoor intake air Wet-bulb temperature() 1.4 1.3 26 1.2 1.1 24 1.0 22 20 18 0.9 0.8 0.7 0.6 -10 -5 0 5 10 15 20 25 30 35 40 45 Outdoor intake air Dry-bulb temperature() Total input (cooling) 1.5 Indoor intake air Wet-bulb temperature() 1.4 Input correction factors 1.3 1.2 26 22 20 18 24 1.1 1.0 0.9 0.8 0.7 0.6 -10 -5 0 5 10 15 20 25 30 35 Outdoor intake air Dry-bulb temperature() 59 40 45 FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA50/60/71VA Cooling capacity 1.5 Indoor intake air Wet-bulb temperature() Capacity correction factors 1.4 1.3 1.2 26 1.1 24 1.0 22 20 18 0.9 0.8 0.7 0.6 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 Outdoor intake air Dry-bulb temperature() Total input (cooling) 1.3 Indoor intake air Wet-bulb temperature() 1.2 22 20 18 24 26 Input correction factors 1.1 1.0 0.9 0.8 0.7 0.6 0.5 0.4 -15 -10 -5 0 5 10 15 20 25 30 35 Outdoor intake air Dry-bulb temperature () 60 40 45 Heating capacity Capacity correction factors 1.3 15 20 26 1.2 1.1 Indoor intake air Dry-bulb temperature() 1.0 0.9 0.8 0.7 0.6 -10 -5 0 5 10 15 Outdoor intake air Wet-bulb temperature () Total input (heating) 1.3 Input correction factors 1.2 1.1 26 20 15 Indoor intake air Dry-bulb temperature() 1.0 0.9 0.8 0.7 0.6 -10 -5 0 5 10 Outdoor intake air Wet-bulb temperature () NOTE: The above curves are for the heating operation without any frost. 61 15 7 APPLICABLE EXTENSION PIPE FOR EACH MODEL SUZ-KA25VA SUZ-KA25VAH SUZ-KA35VA SUZ-KA35VAH MAX. REFRIGERANT PIPING LENGTH Models Refrigerant piping Max. length : m A Gas Liquid 20 9.52 6.35 SUZ-KA25VA SUZ-KA35VA SUZ-KA25VAH SUZ-KA35VHA Piping size O.D : mm MAX. HEIGHT DIFFERENCE Indoor unit + Max. Height difference 12m Refrigerant Piping Max. length A Outdoor unit + Height difference should be within 12m regardless of which unit, indoor or outdoor position is high. ADDITIONAL REFRIGERANT CHARGE (R410A:g) Refrigerant piping length (one way) Outdoor unit precharged 5m 6m 7m 8m 9m 10m 11m 12m 13m 14m 15m 20m SUZ-KA25VA SUZ-KA25VAH 800 0 0 0 90 120 150 180 210 240 270 300 450 SUZ-KA35VA SUZ-KA35VAH 1,050 0 0 0 90 120 150 180 210 240 270 300 450 Models Calculation : Xg=30g/m ✕ (Refrigerant piping length (m) -5) 62 SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA MAX. REFRIGERANT PIPING LENGTH Models Refrigerant piping Max. length : m A Piping size O.D : mm Gas SUZ-KA50VA Liquid 12.7 6.35 SUZ-KA60VA 30 15.88 SUZ-KA71VA 9.52 MAX. HEIGHT DIFFERENCE Indoor unit + Max. Height difference 30m Refrigerant Piping Max. length A Outdoor unit + Height difference should be within 30m regardless of which unit, indoor or outdoor position is high. ADDITIONAL REFRIGERANT CHARGE (R410A : g) Refrigerant piping length (one way) Outdoor unit precharged 7m 10m 15m 20m 25m 30m SUZ-KA50VA 1,600 0 60 160 260 360 460 SUZ-KA60VA 1,800 0 60 160 260 360 460 Models Calculation : Xg=20g/m o (Refrigerant piping length (m) -7) Models SUZ-KA71VA Refrigerant piping length (one way) Outdoor unit precharged 7m 10m 15m 20m 25m 30m 2,000 0 165 440 715 990 1,265 Calculation : Xg=55g/m o (Refrigerant piping length (m) -7) 63 8 AIR FLOW DATA 8-1. OUTLET AIR SPEED AND COVERAGE RANGE Air flow Air speed Coverage range Air flow Air speed Coverage range Air flow Air speed Coverage range Air flow Air speed Coverage range Air flow Air speed Coverage range m³/min. MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA 8.7 9.1 10.7 m/sec. 1.8 1.9 2.2 m 5.1 5.3 6.2 SLZ-KA25VA SLZ-KA25VAL SLZ-KA35VA SLZ-KA35VAL SLZ-KA50VA SLZ-KA50VAL m³/min. 10 11 11 m/sec. 3.4 3.7 3.7 m 3.7 4.1 4.1 PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA(2) 15 18 18 21 m³/min. m/sec. 2.6 3.2 3.2 3.7 m 4.1 4.8 4.8 5.6 PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA m³/min. 14 18 18 20 m/sec. 2.8 3.6 3.6 4.0 m 4.0 5.2 5.2 5.7 PCA-RP50KA PCA-RP60KA PCA-RP71KA 15 19 20 m³/min. m/sec. 3.3 3.1 3.2 m 9.0 9.6 10.1 PCA-RP50GA PCA-RP50GA2 PCA-RP60GA Air flow Air speed Coverage range PCA-RP71GA m³/min. 13 18 18 18 m/sec. 3.7 3.8 3.8 3.8 m 8.8 10.4 10.4 10.4 w The air coverage range is the distance to which the 0.25m/sec air can reach, when air is blown out horizontally from the unit at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room. 64 8-2. SLZ-KA•VA SLZ-KA•VAL 8-2-1. Fresh air intake (Location for installation) At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required. Fresh air intake Detail drawing of fresh air intake 25 :100 :73.4 Cut out hole 0° 12 12 0° 118 3-:2.8 hole Burring hole Ceiling surface Refrigerant pipe Electrical Box Drain pipe 8-2-2. Fresh air intake amount & static pressure characteristics Taking air into the unit Curve in the left graphs. 0 Q -50 -100 Duct characteristics at site A 2.5 1 C A 2 E -150 -200 Q -250 D 3 A -300 NOTE: Fresh air intake amount should be 20% or less of whole air amount to prevent dew dripping. Q Qa 65 C 2.0 Airflow : Q [m3/min] 3.0 3.5 B Static pressure : P [Pa] 50 0.5 1.0 1.5 0 How to read curves Q…Designed amount of fresh air intake <m3/min> A…Static pressure loss of fresh air intake duct system with airflow amount Q <Pa> B…Forced static pressure at air conditioner inlet with airflow amount Q <Pa> C…Static pressure of booster fan with airflow amount Q <Pa> D…Static pressure loss increase amount of fresh air intake duct system for airflow amount Q <Pa> E…Static pressure of indoor unit with airflow amount Q Qa…Estimated amount of fresh air intake without D <m3/min> 8-3. SEZ-KD•VA(L) INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW SEZ-KD25VA(L) SEZ-KD25VA(L) (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 40 50 Limit Limit 40 External static pressure (Pa) External static pressure (Pa) 30 20 High High 30 20 Middle Rated point 10 Middle Low 10 Low Rated point 0 0 4 5 6 7 8 Airflow rate(m3/min) 9 10 SEZ-KD25VA(L) 4 5 6 7 8 Airflow rate(m3/min) 9 10 SEZ-KD25VA(L) (External static pressure 35Pa) 220-240V 50/60Hz (External static pressure 50Pa) 220-240V 50/60Hz 80 80 Limit Limit 70 70 60 60 External static pressure (Pa) External static pressure (Pa) High 50 High 40 Rated point 30 Middle 20 50 Rated point 40 Middle 30 Low 20 Low 10 10 0 0 4 5 6 7 8 Airflow rate(m3/min) 9 10 4 66 5 6 7 8 Airflow rate(m3/min) 9 10 SEZ-KD35VA(L) SEZ-KD35VA(L) (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 40 50 40 External static pressure (Pa) External static pressure (Pa) 30 Limit 20 High Limit 30 High 20 Middle Rated point 10 Middle 10 Low Rated point Low 0 6 7 8 9 10 Airflow rate(m3/min) 11 SEZ-KD35VA(L) 6 7 8 9 10 Airflow rate(m3/min) 11 12 SEZ-KD35VA(L) (External static pressure 35Pa) 220-240V 50/60Hz (External static pressure 50Pa) 220-240V 50/60Hz 80 80 70 70 60 50 40 Rated point 30 High Middle 20 Limit 60 Limit External static pressure (Pa) External static pressure (Pa) 0 12 50 Rated point High 40 Middle 30 20 Low 10 Low 10 0 0 6 7 8 9 10 Airflow rate(m3/min) 11 12 67 6 7 8 9 10 Airflow rate(m3/min) 11 12 SEZ-KD50VA(L) SEZ-KD50VA(L) (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 50 40 Limit Limit 40 External static pressure (Pa) External static pressure (Pa) 30 20 High Middle 30 High 20 Middle Rated point Low 10 10 Low Rated point 0 0 8 9 10 11 12 13 Airflow rate(m3/min) 14 15 8 16 SEZ-KD50VA(L) 9 10 11 12 13 Airflow rate(m3/min) 14 15 16 SEZ-KD50VA(L) (External static pressure 35Pa) 220-240V 50/60Hz (External static pressure 50Pa) 220-240V 50/60Hz 80 80 70 70 Limit Limit High 60 External static pressure (Pa) External static pressure (Pa) 60 50 High 40 Middle 30 Rated point 20 50 Rated point Middle 40 30 Low 20 Low 10 10 0 0 8 9 10 11 12 13 Airflow rate(m3/min) 14 15 16 8 68 9 10 11 12 13 Airflow rate(m3/min) 14 15 16 SEZ-KD60VA(L) SEZ-KD60VA(L) (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 40 50 Limit Limit 40 External static pressure (Pa) External static pressure (Pa) 30 20 High Middle 10 High 30 Middle 20 Low Rated point 10 Low Rated point 0 0 9 10 11 12 13 14 15 Airflow rate(m3/min) 16 17 18 19 SEZ-KD60VA(L) 9 10 11 12 13 14 15 Airflow rate(m3/min) 17 18 19 SEZ-KD60VA(L) (External static pressure 35Pa) 220-240V 50/60Hz (External static pressure 50Pa) 220-240V 50/60Hz 80 80 Limit Limit 70 70 60 60 External static pressure (Pa) External static pressure (Pa) 16 High 50 40 Middle Rated point 30 Low 20 High 50 30 Low 20 10 Rated point Middle 40 10 0 0 9 10 11 12 13 14 15 Airflow rate(m3/min) 16 17 18 19 69 9 10 11 12 13 14 15 Airflow rate(m3/min) 16 17 18 19 SEZ-KD71VA(L) SEZ-KD71VA(L) (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 40 50 40 External static pressure (Pa) External static pressure (Pa) 30 20 Limit 30 Limit 20 High Rated point 10 High 10 Middle Middle Rated point Low Low 0 0 11 12 13 14 15 16 17 Airflow rate(m3/min) 18 19 20 11 21 SEZ-KD71VA(L) 13 14 15 16 17 Airflow rate(m3/min) 18 19 20 21 SEZ-KD71VA(L) (External static pressure 35Pa) 220-240V 50/60Hz (External static pressure 50Pa) 220-240V 50/60Hz 80 80 70 70 60 60 External static pressure (Pa) External static pressure (Pa) 12 Limit 50 High 40 Rated point 30 Middle 20 Limit High 50 Rated point 40 Middle 30 20 Low Low 10 10 0 0 11 12 13 14 15 16 17 Airflow rate(m3/min) 18 19 20 11 21 70 12 13 14 15 16 17 Airflow rate(m3/min) 18 19 20 21 8-4. SEZ-KA•VA INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW SEZ-KA35VA Corrected Air flow 1.1 Correction factor Fan Performance Recommended range 60 20 0 1.0 0.9 0.8 1.3 40 Correction factor External static pressure(Pa) (1Pa = 0.1mmAq) 80 5 7 10 15 20 25 Air flow (*/7) Capacity Input Cooling 5 10 15 20 25 10 15 20 25 Air flow (*/7) Heating 1.2 1.1 1.0 0.9 0.8 5 Air flow (*/7) SEZ-KA50VA Corrected Airflow Fan Performance Correction factor 1.1 Recommended range 60 1.0 0.9 0.8 40 1.2 0 5 10 15 20 25 10 15 20 25 Air flow (*/7) Heating 1.1 20 5 10 15 20 Correction factor External static pressure(Pa) (1Pa = 0.1mmAq) 80 Capacity Input Cooling 25 Air flow (*/7) 71 1.0 0.9 0.8 5 Air flow (*/7) INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW SEZ-KA60VA Corrected Air flow 1.1 Correction factor Fan Performance Recommended range 60 40 20 0 1.0 0.9 0.8 1.3 Correction factor External static pressure(Pa) (1Pa = 0.1mmAq) 80 5 10 15 20 25 Air flow (*/7) Capacity Input Cooling 10 15 20 25 30 15 20 25 30 Air flow (*/7) Heating 1.2 1.1 1.0 0.9 10 Air flow (*/7) SEZ-KA71VA Corrected Air flow 1.1 Correction factor Fan Performance Recommended range 60 40 20 0 1.0 0.9 0.8 1.3 Correction factor External static pressure(Pa) (1Pa = 0.1mmAq) 80 5 10 15 20 25 Air flow (*/7) 10 15 20 25 30 15 20 25 30 Air flow (*/7) Heating 1.2 1.1 1.0 0.9 72 Capacity Input Cooling 10 Air flow (*/7) 8-5. PLA-RP·BA 8-5-1 FRESH AIR INTAKE AND BRANCH DUCT 1. Branch duct hole and fresh air intake hole (Fig. 1) At the time of i nstallation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required. • A fresh air intake hole for the optional multi function casement can also be made. Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. Unit : mm Fresh air intake hole Fresh air intake hole diagram Branch duct hole 120 Indoor unit *158 3-:2.8 burring hole :125 burring 120 hole pitch :100 cut out hole Ceiling Drain pipe Refrigerant pipe 100 90 100 100 130 90 Branch duct hole diagram (view from either side) *167 *155 70 350 :175 burring hole pitch 14-:2.8 burring hole :150 cut out hole Fig. 1 2. Fresh air intake (Installation at site) ● By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct and duct flange (option) onto it further, fresh exterior air intake can be accomplished. (The mounting of the multi-function casement increases the height of the ceiling plenum by 135 mm.) 73 3. Fresh air intake volume & static pressure characteristics PLA-RP35~71BA(2) At using multi-function casement, standard filter 50 -50 2 - inlet -100 How to read the chart 1 - inlet 0 1 2 3 4 5 Line of chart 0 6 Field duct characteristics A -200 1 Air flow rate [m3/min] Q Direct intake to unit 2 C A 50 E 0 D 3 -100 A Static pressure[Pa] Q -50 Q Qa -150 -200 0 1 2 3 4 5 6 Air flow rate [m3/min] At using multi-function casement, high efficiency filter 50 Static pressure[Pa] 0 -50 2 - inlet -100 -150 -200 1 - inlet 0 1 2 3 Air flow rate [m3/min] 4 5 6 74 C -150 B Static pressure[Pa] 0 Q…Designed fresh air intake volume <m3/min> A…Static pressure loss [Pa] of fresh air intake duct at airflow rate of Q B…Required boost pressure [Pa] of air conditioner inlet at airflow rate of Q C…Required static pressure [Pa] of booster fan at airflow rate of Q D…Required compensation [Pa] for static pressure loss of fresh air intake duct to make airflow rate Q E…Static pressure [Pa] of indoor unit at airflow rate of Q Qa…Estimated fresh air intake [m3/min] without compensation of D 4. Change of outlet numbers Indoor unit [The optional air outlet is necessary.] To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter. (When the air outlets are closed, close the vane by removing the vane connector.) Outlet concave portion Button Vane motor Up/down vanes Connector Air outlet shutter plate (Option) Vane motor Connector Button 5. Branch duct and change of outlet numbers + Branch duct should be connected to one of the branch duct holes on the main unit. <4- way air flow and branch duct> Branch duct Air intake Air outlet + Close the outlet on the side of branch duct and air flows in 3 directions. <3- way air flow and branch duct> Branch duct Air intake Air outlet Air outlet closed position + The outlet on the side of branch duct and one of the other outlets are closed. Air flows in 2 directions. <2- way air flow and branch duct> Branch duct Air Air outlet outlet closed closed position position Air intake Air outlet closed position 75 PLA-RP71BA(2) 4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct 30 Duct Static pressure [Pa] Static pressure [Pa] 30 20 10 High Duct 20 10 High Low Low 0 0 0 2 4 6 Airflow rate [m3/min] 0 8 3-way airflow (horizontal vane) Round duct 2 80 70 70 Duct Duct 60 Close Static pressure [Pa] Static pressure [Pa] 60 50 40 30 Close 50 40 30 High 20 20 High Low 10 0 Low 10 2 4 6 8 Airflow rate [m3/min] 0 10 2-way airflow (horizontal vane) Round duct 0 100 90 90 Duct 2 Duct 80 Close Close 10 Close Close Static pressure [Pa] 70 60 50 40 30 High 20 4 6 8 Airflow rate [m3/min] 2-way airflow (horizontal vane) Rectangular duct 100 80 Static pressure [Pa] 8 3-way airflow (horizontal vane) Rectangular duct 80 0 4 6 Airflow rate [m3/min] 70 60 50 40 30 20 Low Low High 10 10 0 0 0 2 4 6 8 10 Airflow rate [m3/min] 0 12 2 4 6 8 10 Airflow rate [m3/min] • Use 1 of the 2 duct holes on the indoor unit. • Air flow rate of PLA-RP35~60BA can be calculated from the airflow rate based on the characteristic of the duct for PLA-RP71BA. • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow. 76 12 8-6. PLA-RP·AA 8-6-1. Fresh air intake amount 1. Adjusting the width of the air outlets ● Change of outlet numbers [The optional air outlet shutter is necessary.] To change the air outlet numbers to 3-, or 2-way outlet, the outlets should be closed with the optional air outlet shutter. When the air outlets are closed, close the vane by removing the vane connector. ● For the portion to be cut (V-shaped groove), see the figure below (as seen from the rear of the panel). 2. Fresh air intake (Installation at site) ● By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct and duct flange (field supply) onto it further, fresh exterior air intake can be accomplished. (The mounting of the multi-function casement increases the height of the ceiling plenum by 135 mm.) 77 3. Fresh air intake volume & static pressure characteristics How to read the chart Line of chart Q B A 0 Field duct characteristics E C A 2 Q Q…Designed fresh air intake volume <m3/min> A…Static pressure loss [Pa] of fresh air intake duct at airflow rate of Q B…Required boost pressure [Pa] of air conditioner inlet at airflow rate of Q C…Required static pressure [Pa] of booster fan at airflow rate of Q D…Required compensation [Pa] for static pressure loss of fresh air intake duct to make airflow rate Q E…Static pressure [Pa] of indoor unit at airflow rate of Q Qa…Estimated fresh air intake [m3/min] without compensation of D A D 3 C 1 Q Qa 8-5-2. BRANCH DUCT (Installation at site) To be compatible with both round and rectangular branch ducts, knockout holes are designed to fit to both shapes for flexible on-site installation. 78 Branch duct air flow rate/static pressure characteristics PLA-RP35AA 4-way air flow (horizontal vane) Rectangular duct 4-way air flow (horizontal vane) Round duct 3-way air flow (horizontal vane) Rectangular duct 3-way air flow (horizontal vane) Round duct 2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct 79 PLA-RP50AA PLA-RP60AA 4-way air flow (horizontal vane) Rectangular duct 4-way air flow (horizontal vane) Round duct 3-way air flow (horizontal vane) Rectangular duct 3-way air flow (horizontal vane) Round duct 2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct 80 PLA-RP71AA 4-way air flow (horizontal vane) Round duct 30 Static pressure [Pa] Static pressure [Pa] 4-way air flow (horizontal vane) Rectangular duct 20 High 10 Low 0 1 2 3 4 5 6 30 20 High 10 Low 0 1 2 3 Air flow rate [m /min] 6 3-way air flow (horizontal vane) Round duct 60 60 Static pressure [Pa] 50 40 High 30 20 Low 10 0 1 2 3 4 5 6 7 8 50 40 High 30 20 Low 10 0 9 1 2 3 4 Air flow rate [m /min] 2-way air flow (horizontal vane) Rectangular duct 90 90 80 80 Static pressure [Pa] 100 70 60 High 40 Low 30 20 10 0 6 7 2-way air flow (horizontal vane) Round duct 100 50 5 70 60 High 50 40 Low 30 20 10 1 2 3 4 5 6 7 8 9 10 8 Air flow rate [m3/min] 3 Static pressure [Pa] 5 3 3-way air flow (horizontal vane) Rectangular duct Static pressure [Pa] 4 Air flow rate [m /min] 3 0 11 Air flow rate [m3/min] 1 2 3 4 5 6 Air flow rate [m3/min] 81 7 9 8-7. PCA-RP·KA 8-7-1. Fresh air intake amount & static pressure characteristics PCA-RP60, 71KA 50 50 0 0 Static pressure[Pa] -50 -100 -150 -200 -250 -100 -150 -200 -250 -300 2 3 0 4 1 2 3 4 Airflow rate[m³/min] Airflow rate[m³/min] How to read the chart Q B A 0 Duct characteristics at site 2 Q 3 Q Qa 82 C Curve in the graphs 1 C A 1 E 0 D -300 -50 A Static pressure[Pa] PCA-RP50KA Q…Designed amount of fresh air intake <m3/min> A…Static pressure loss of fresh air intake duct system with airflow amount Q <Pa> B…Forced static pressure at air conditioner inlet with airflow amount Q <Pa> C…Static pressure of booster fan with airflow amount Q <Pa> D…Static pressure loss increase amount of fresh air intake duct system for airflow amount Q <Pa> E…Static pressure of indoor unit with airflow amount Q Qa…Estimated amount of fresh air intake without D <m3/min> 8-8. PEAD-RP·JA(L), EA, EA2, GA 8-8-1. Fan performance PEAD-RP·JA(L) PEAD-RP35JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP35JA(L) (External static pressure 35Pa) 220-240V 50Hz 120 60 110 Rated point 100 Limit External static pressure (Pa) External static pressure (Pa) 50 40 Rated point High 30 Middle 20 Low 10 Limit 90 High 80 70 Middle 60 50 Low 40 30 20 10 0 7 9 11 13 15 17 19 0 21 7 9 11 Airflow rate(m3/min) 13 PEAD-RP35JA(L) (External static pressure 50Pa) 220-240V 50Hz 17 19 21 PEAD-RP35JA(L) (External static pressure 150Pa) 220-240V 50Hz 70 170 160 Rated point 150 60 140 Limit External static pressure (Pa) External static pressure (Pa) 15 Airflow rate(m3/min) Rated point 50 High 40 Middle 30 Low 20 Limit 130 High 120 110 100 Middle 90 80 70 Low 60 50 40 30 10 20 10 0 7 9 11 13 15 17 19 0 21 Airflow rate(m3/min) 90 80 External static pressure (Pa) Rated point Limit High 60 50 Middle 40 Low 30 20 10 0 7 9 11 13 15 Airflow rate(m3/min) 9 11 13 15 Airflow rate(m3/min) PEAD-RP35JA(L) (External static pressure 70Pa) 220-240V 50Hz 70 7 17 19 21 83 17 19 21 PEAD-RP50JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP50JA(L) (External static pressure 35Pa) 220-240V 50Hz 130 70 120 110 60 50 High 40 Rated point Middle 30 Low 20 Rated point Limit 100 External static pressure (Pa) External static pressure (Pa) Limit 90 High 80 70 Middle 60 50 Low 40 30 20 10 10 0 9 14 0 19 9 14 19 Airflow rate(m3/min) Airflow rate(m3/min) PEAD-RP50JA(L) (External static pressure 50Pa) 220-240V 50Hz PEAD-RP50JA(L) (External static pressure 150Pa) 220-240V 50Hz 180 80 170 160 70 Middle 40 Low 20 External static pressure (Pa) External static pressure (Pa) Rated point 50 High 140 High 60 30 Rated point 150 Limit Limit 130 120 110 Middle 100 90 80 Low 70 60 50 40 10 30 20 0 9 14 10 19 0 Airflow rate(m3/min) 9 14 Airflow rate(m3/min) PEAD-RP50JA(L) (External static pressure 70Pa) 220-240V 50Hz 100 90 External static pressure (Pa) 80 Limit Rated point 70 High 60 50 Middle 40 30 Low 20 10 0 9 14 19 Airflow rate(m3/min) 84 19 PEAD-RP60JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP60JA(L) (External static pressure 35Pa) 220-240V 50Hz 120 60 110 50 Rated point 100 External static pressure (Pa) External static pressure (Pa) Limit 40 Rated point 30 High 20 Middle 90 Limit High 80 70 Middle 60 50 Low 40 30 Low 10 20 10 0 10 15 20 25 0 10 30 15 Airflow rate(m3/min) 20 PEAD-RP60JA(L) (External static pressure 50Pa) 220-240V 50Hz 170 160 Rated point 150 Limit 140 Rated point 50 External static pressure (Pa) External static pressure (Pa) 30 PEAD-RP60JA(L) (External static pressure 150Pa) 220-240V 50Hz 70 60 25 Airflow rate(m3/min) High 40 Middle 30 20 Low High 130 Limit 120 110 100 Middle 90 80 70 60 Low 50 40 30 10 20 10 0 10 15 20 25 0 30 Airflow rate(m3/min) 90 80 Rated point External static pressure (Pa) Limit High 60 50 Middle 40 30 Low 20 10 0 10 15 20 15 20 Airflow rate(m3/min) PEAD-RP60JA(L) (External static pressure 70Pa) 220-240V 50Hz 70 10 25 30 Airflow rate(m3/min) 85 25 30 PEAD-RP71JA(L) (External static pressure 100Pa) 220-240V 50Hz PEAD-RP71JA(L) (External static pressure 35Pa) 220-240V 50Hz 70 130 120 60 High 110 Rated point 50 External static pressure (Pa) External static pressure (Pa) 100 Limit High 40 Rated point 30 Middle 20 Low Limit 90 Middle 80 70 60 Low 50 40 30 10 20 10 0 10 15 20 25 0 30 10 15 Airflow rate(m3/min) 20 25 30 Airflow rate(m3/min) PEAD-RP71JA(L) (External static pressure 50Pa) 220-240V 50Hz PEAD-RP71JA(L) (External static pressure 150Pa) 220-240V 50Hz 90 180 170 High 160 80 Rated point 150 140 External static pressure (Pa) External static pressure (Pa) 70 Limit 60 High Rated point 50 Middle 40 30 Low 20 130 Middle Limit 120 110 100 90 80 Low 70 60 50 40 30 10 20 10 0 10 15 20 25 0 30 Airflow rate(m3/min) 100 90 High External static pressure (Pa) 80 Limit Rated point 70 Middle 50 40 Low 30 20 10 0 10 15 20 15 20 Airflow rate(m3/min) PEAD-RP71JA(L) (External static pressure 70Pa) 220-240V 50Hz 60 10 25 30 Airflow rate(m3/min) 86 25 30 8-8-2. Fan performance and corrected air flow PEAD-RP35EA2 PEAD-RP50EA Fan Performance <30Pa> Corrected Air Flow 120 100 Correction factor External static pressure (Pa) (1Pa 0.1mmAq) 140 80 60 40 20 6 8 Cooling 1.0 0.9 0.8 8 10 10 12 14 16 18 20 AirFlow (CMM) Fan Performance <70Pa> 160 12 14 16 18 Airflow (CMM) 20 22 12 14 16 18 Airflow (CMM) 20 22 Heating 1.3 140 Correction factor External static pressure (Pa) (1Pa 0.1mmAq) 1.1 Capacity input 120 100 80 60 40 1.2 1.1 1.0 0.9 0.8 8 20 8 10 10 12 14 16 18 20 22 AirFlow (CMM) Fan Performance <30Pa> 120 Correction factor 100 80 60 40 20 8 140 External static pressure (Pa) (1Pa 0.1mmAq) Corrected Air Flow 1.1 Capacity input Cooling 1.0 0.9 0.8 12 14 16 18 20 22 Airflow (CMM) 10 12 14 16 18 20 22 24 AirFlow (CMM) 24 26 Heating Fan Performance <70Pa> 1.3 Correction factor External static pressure (Pa) (1Pa 0.1mmAq) PEAD-RP60EA 120 100 80 60 40 1.2 1.1 1.0 0.9 0.8 12 14 16 18 20 22 24 Airflow (CMM) 20 10 12 14 16 18 20 22 24 26 AirFlow (CMM) 87 26 PEAD-RP71EA Fan performance <70Pa> Fan performance <130Pa> Recommended range External static pressure (Pa) (1Pa = 0.1mmAq) External static pressure (Pa) (1Pa = 0.1mmAq) Recommended range 200 180 160 140 Hi Lo 120 100 80 60 40 20 180 160 140 120 80 60 40 20 12 16 20 24 28 32 12 16 20 24 28 32 Air flow (C MM) A ir f low ( C MM) Corrected Air Flow Capacity Input Cooling Heating 1.3 1.2 Correction factor 1.1 Correction factor Hi Lo 100 1.0 0.9 0.8 12 16 20 24 28 1.1 1.0 0.9 32 Air flow (CMM) 0.8 12 16 20 24 28 Air flow (CMM) PEAD-RP60GA 88 32 PEAD-RP71GA 8-9. PEA-RP·EA 8-9-1. Fan performance and corrected airflow PEA-RP71EA Corrected Airflow 1.05 Correction factor Fan Performance Recommended range Hi 150 1.0 0.95 0.9 1.2 100 50 0 15 17 20 17 20 25 30 25 30 Airflow (CMM) Lo Correction factor External static pressure(Pa) (1Pa = 0.1mmAq) 200 25 30 35 Airflow (CMM) Heating 1.15 1.1 1.05 1.0 0.95 17 20 Airflow (CMM) 89 Capacity Input Cooling NOISE CRITERION CURVES 9 MFZ-KA25VA MFZ-KA35VA Super High SPL(dB(A)) COOLING 37 HEATING 37 Super High OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR Test conditions, Cooling : Dry-bulb temperature 27°CWet-bulb temperature 19°C Heating : Dry-bulb temperature 20°CWet-bulb temperature 15°C 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 FAN SPEED FUNCTION LINE 4000 SPL(dB(A)) COOLING 38 HEATING 38 8000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz MFZ-KA50VA FAN SPEED FUNCTION Super High SPL(dB(A)) COOLING 43 HEATING 44 LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR Test conditions, Cooling : Dry-bulb temperature 27°CWet-bulb temperature 19°C Heating : Dry-bulb temperature 20°CWet-bulb temperature 15°C 90 80 70 INDOOR UNIT NC-70 MICROPHONE 60 WALL NC-60 1m 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 LINE Test conditions, Cooling : Dry-bulb temperature 27°CWet-bulb temperature 19°C Heating : Dry-bulb temperature 20°CWet-bulb temperature 15°C 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR FAN SPEED FUNCTION 8000 BAND CENTER FREQUENCIES, Hz 90 1m 8000 <50Hz> SLZ-KA25VAL SLZ-KA25VA NOTCH SPL(dB) High 37 Medium 31 Low 28 LINE NOTCH SPL(dB) High 38 Medium 33 Low 29 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 20 63 125 250 NC-20 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 10 <50Hz> SLZ-KA35VAL SLZ-KA35VA 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz <50Hz> SLZ-KA50VAL SLZ-KA50VA NOTCH SPL(dB) High 39 Medium 34 Low 30 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) UNIT 80 CEILING 70 NC-70 60 NC-60 1.5m 50 NC-50 40 NC-40 MICROPHONE 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. 91 NOISE CRITERION CURVES SEZ-KD25VA(L) NOTCH External static pressure: 5Pa High Middle Low SPL(dB) 29 25 22 LINE SEZ-KD25VA(L) External static pressure: 15Pa 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 NC-20 125 250 500 1000 2000 4000 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 SEZ-KD25VA(L) External static pressure: 35Pa NOTCH SPL(dB) High 31 Middle 28 Low 24 LINE 500 SEZ-KD25VA(L) External static pressure: 50Pa 1000 2000 4000 8000 NOTCH SPL(dB) High 33 Middle 29 Low 25 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 BAND CENTER FREQUENCIES, Hz 90 10 NC-20 125 BAND CENTER FREQUENCIES, Hz 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 30 Middle 26 Low 23 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 BAND CENTER FREQUENCIES, Hz NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. 92 SEZ-KD35VA(L) External static pressure: 5Pa NOTCH SPL(dB) High 33 Middle 28 Low 23 LINE SEZ-KD35VA(L) External static pressure: 15Pa 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 NC-20 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 80 10 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 SEZ-KD35VA(L) External static pressure: 35Pa NOTCH SPL(dB) High 34 Middle 29 Low 24 LINE 500 SEZ-KD35VA(L) External static pressure: 50Pa 1000 2000 4000 8000 NOTCH SPL(dB) High 35 Middle 31 Low 25 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 BAND CENTER FREQUENCIES, Hz 90 10 NC-20 125 BAND CENTER FREQUENCIES, Hz 20 LINE 90 90 20 NOTCH SPL(dB) High 33 Middle 28 Low 23 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 BAND CENTER FREQUENCIES, Hz NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. 93 SEZ-KD50VA(L) External static pressure: 5Pa NOTCH SPL(dB) High 36 Middle 33 Low 29 LINE SEZ-KD50VA(L) External static pressure: 15Pa 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 NC-20 125 250 500 1000 2000 4000 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 SEZ-KD50VA(L) External static pressure: 35Pa NOTCH SPL(dB) High 38 Middle 35 Low 31 LINE 500 SEZ-KD50VA(L) External static pressure: 50Pa 1000 2000 4000 8000 NOTCH SPL(dB) High 39 Middle 36 Low 32 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 BAND CENTER FREQUENCIES, Hz 90 10 NC-20 125 BAND CENTER FREQUENCIES, Hz 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 37 Middle 34 Low 30 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. 94 SEZ-KD60VA(L) External static pressure: 5Pa NOTCH SPL(dB) High 37 Middle 33 Low 29 LINE SEZ-KD60VA(L) External static pressure: 15Pa 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 NC-20 125 250 500 1000 2000 4000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz SEZ-KD60VA(L) External static pressure: 35Pa NOTCH SPL(dB) High 39 Middle 35 Low 31 LINE 500 SEZ-KD60VA(L) 1000 2000 4000 8000 NOTCH SPL(dB) High 39 Middle 36 Low 32 LINE 90 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 External static pressure: 50Pa 80 10 NC-20 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 38 Middle 34 Low 30 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 8000 63 BAND CENTER FREQUENCIES, Hz 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. 95 SEZ-KD71VA(L) External static pressure: 5Pa NOTCH SPL(dB) High 39 Middle 34 Low 29 LINE SEZ-KD71VA(L) External static pressure: 15Pa 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 NC-20 125 250 500 1000 2000 4000 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 SEZ-KD71VA(L) External static pressure: 35Pa NOTCH SPL(dB) High 41 Middle 36 Low 31 LINE 500 SEZ-KD71VA(L) External static pressure: 50Pa 1000 2000 4000 8000 NOTCH SPL(dB) High 42 Middle 37 Low 32 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 BAND CENTER FREQUENCIES, Hz 90 10 NC-20 125 BAND CENTER FREQUENCIES, Hz 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 40 Middle 35 Low 30 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 BAND CENTER FREQUENCIES, Hz 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz Aux. duct 96 test unit 1m 2m Measurement location 1.5m NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. SEZ-KC25VA <50Hz> NOTCH SPL(dB) High 36 Low 25 70 High speed OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa Low speed 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 Appro Approximate minimum audible limit on continuous noise 0 63 125 250 500 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCIES (Hz) Aux.duct 2m 1.5m 1m Measurement location NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. 97 <50Hz> SEZ-KA35VA NOTCH SPL(dB) High 35 Low 30 LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 10 NOTCH SPL(dB) High 39 Low 31 LINE 90 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 20 <50Hz> SEZ-KA50VA 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz <50Hz> SEZ-KA60VA SEZ-KA71VA NOTCH SPL(dB) High 43 Low 32 LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 UNIT 80 70 NC-70 60 NC-60 External static pressure 30Pa 50 1.5m NC-50 40 MICROPHONE NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. 98 PLA-RP35BA NOTCH SPL(dB) High 31 Medium1 29 Medium2 28 Low 27 LINE PLA-RP50BA 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz PLA-RP60BA NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 LINE 500 PLA-RP71BA PLA-RP71BA2 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 1000 2000 4000 8000 NOTCH SPL(dB) High 34 Medium1 32 Medium2 30 Low 28 LINE 90 80 10 NC-20 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 BAND CENTER FREQUENCIES, Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 99 4000 8000 NOTCH SPL(dB) High 31 Medium1 29 Medium2 28 Low 27 PLA-RP35AA LINE PLA-RP50AA PLA-RP60AA 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 BAND CENTER FREQUENCIES, Hz 125 NC-20 250 500 1000 CEILING OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 1.5m 70 NC-70 MICROPHONE 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 125 NC-20 250 500 1000 2000 8000 UNIT 80 63 4000 LINE 90 10 2000 BAND CENTER FREQUENCIES, Hz NOTCH SPL(dB) High 34 Medium1 32 Medium2 30 Low 28 PLA-RP71AA 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 20 NOTCH SPL(dB) High 33 Medium1 31 Medium2 29 Low 28 4000 8000 BAND CENTER FREQUENCIES, Hz 100 PEAD-RP35JA(L) External static pressure 35Pa 80 70 2m 2m Aux.duct NC-70 1.5m OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) Ceiling concealed High Middle Low 60 NC-60 Measurement location 50 NC-50 Noise level at anechoic room (Low-Middle-High) Unit: dB(A) 40 NC-40 Exrernal static pressure Model 30 35Pa NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 50Pa 70Pa 100Pa 150Pa PEAD-RP35JA(L) 23-26-29 23-27-30 24-28-31 26-29-33 29-33-37 PEAD-RP50JA(L) 25-30-34 26-31-35 28-32-36 29-33-37 31-35-39 PEAD-RP60JA(L) 25-28-32 25-29-33 26-30-34 27-31-35 29-34-38 PEAD-RP71JA(L) 25-29-34 26-30-34 27-31-35 28-32-36 30-35-39 8000 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa 80 70 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 External static pressure 100Pa NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 500 1000 2000 80 60 0 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 20 125 4000 8000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 NC-20 10 0 8000 High Middle Low 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 8000 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz 101 High Middle Low 4000 8000 PEAD-RP50JA(L) External static pressure 35Pa 70 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz 70 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 2000 4000 8000 4000 8000 BAND CENTER FREQUENCIES, Hz 102 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 20 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 125 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa NC-20 10 0 8000 High Middle Low 4000 8000 PEAD-RP60JA(L) External static pressure 35Pa 70 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz 70 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 2000 4000 8000 4000 8000 BAND CENTER FREQUENCIES, Hz 103 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 20 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 125 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa NC-20 10 0 8000 High Middle Low 4000 8000 PEAD-RP71JA(L) External static pressure 35Pa 70 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 BAND CENTER FREQUENCIES, Hz 70 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 2000 4000 8000 4000 8000 BAND CENTER FREQUENCIES, Hz 104 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 20 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 125 BAND CENTER FREQUENCIES, Hz High Middle Low External static pressure 50Pa NC-20 10 0 8000 High Middle Low 4000 8000 Noise level at an echoic room (Low-High) Unit : dB(A) External static pressure 130Pa 70Pa 30Pa 38-44* 36-40 36-40 38-44* - Model PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA 37-41 39-46* - - 37-41 40-45* PEAD-RP71EA * Optional motor OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa PEAD-RP35EA2 PEAD-RP50EA (External static pressure 30Pa) 70 OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa PEAD-RP35EA2 PEAD-RP50EA 70 High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 0 Approximate minimum audible limit on continuous noise 63 125 250 500 1000 2000 4000 8000 High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 0 Approximate minimum audible limit on continuous noise 63 OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa (External static pressure 30Pa) NC60 50 NC50 40 NC40 30 NC30 20 NC20 Approximate minimum audible limit on continuous noise 63 125 250 500 1000 2000 4000 500 PEAD-RP60EA High Low 0 250 70 60 10 125 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20MPa PEAD-RP60EA 70 (External static pressure 70Pa) 8000 OCTAVE BAND CENTER FREQUENCIES (Hz) (External static pressure 70Pa) High Low 60 NC60 50 NC50 40 NC40 30 NC30 20 NC20 10 0 Approximate minimum audible limit on continuous noise 63 125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCIES (Hz) 105 8000 PCA-RP50KA NOTCH SPL(dB) 40 High 37 Medium1 34 Medium2 32 Low PCA-RP60KA LINE 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 10 LINE 90 90 20 NOTCH SPL(dB) High 40 Medium1 37 Medium2 35 Low 33 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 10 8000 63 125 BAND CENTER FREQUENCIES, Hz PCA-RP71KA NOTCH SPL(dB) High 41 Medium1 39 Medium2 37 Low 35 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 90 80 70 NC-70 ceiling 1m 60 NC-60 1m about 1.4m 50 NC-50 MICROPHONE 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz 106 unit ceiling 1m 1m unit about 1.4m MICROPHONE PCA-RP50GA NOTCH SPL(dB) 42 High 40 Medium1 38 Medium2 37 Low LINE PCA-RP50GA2 PCA-RP60GA PCA-RP71GA 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 BAND CENTER FREQUENCIES, Hz PEA-RP71EA NOTCH SPL(dB) High 55 Low 52 LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 500 1000 UNIT 1m 1m MICROPHONE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 10 125 NC-20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 250 500 1000 2000 4000 BAND CENTER FREQUENCIES, Hz 2000 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 43 Medium1 41 Medium2 39 Low 37 NC-20 8000 107 External static pressure 125Pa 4000 8000 SUZ-KA35VA SUZ-KA35VAH SUZ-KA25VA SUZ-KA25VAH High Med. SPL(dB(A)) COOLING 46 HEATING 46 High Med. OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) Test conditions, Cooling : Dry-bulb temperature 35°CWet-bulb temperature (24°C) Heating : Dry-bulb temperature 7°CWet-bulb temperature 6°C 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 FAN SPEED FUNCTION LINE 500 1000 2000 4000 High SPL(dB(A)) COOLING 53 HEATING 55 LINE NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 1m Test conditions, Cooling : Dry-bulb temperature 35°CWet-bulb temperature (24°C) Heating : Dry-bulb temperature 7°CWet-bulb temperature 6°C 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 60 MICROPHONE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 125 NC-20 250 500 1000 2000 4000 LINE NC-70 500 1000 OUTDOORUNIT FAN SPEED FUNCTION 63 48 2000 4000 BAND CENTER FREQUENCIES, Hz SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA 10 HEATING 70 10 8000 BAND CENTER FREQUENCIES, Hz 20 47 80 NC-20 250 SPL(dB(A)) COOLING Test conditions, Cooling : Dry-bulb temperature 35°CWet-bulb temperature (24°C) Heating : Dry-bulb temperature 7°CWet-bulb temperature 6°C 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) FAN SPEED FUNCTION 8000 BAND CENTER FREQUENCIES, Hz 108 8000 10 OPTIONAL PARTS 10-1. INDOOR UNIT Part Name Remote sensor Multiple remote controller adapter Applicable model Remote on/off adapter Model Name PAC-SE41TS-E PAC-SA88HA-E(1pc.) PAC-725AD(10pcs.) PAC-SE55RA-E Remote operation adapter PAC-SF40RM-E MA & contact terminal interface Anti-allergy enzyme filter(Air cleaning filter) Drain pump Wireless remote controller Signal receiver unit Air filter Decoration panel Decoration panel with wireless remote controller Decoration panel with wired remote controller Automatic filter elevation panel i-see sensor corner panel Wireless signal receiver Space panel Air outlet shutter plate Multi-function casement Flange for fresh air intake High-efficiency filter element (PAC-SH53TM-E is needed.) Multi-functional casement High-efficiency filter element (PAC-SG03TM-E is needed.) Grille + Wireless remote controller Grille + Wired remote controller Air outlet shutter plate (20 set, 2pcs/set) Wireless remote controller kit MAC-397IF-E MAC-415FT-E PAC-KE07DM-E PAR-SL9CA-E PAR-SA9CA-E PAC-1000FT PLP-6BA PLP-6BALM PLP-6BAM PLP-6BAJ PAC-SA1ME-E PAR-SA9FA-E PAC-SH48AS-E PAC-SH51SP-E PAC-SH53TM-E PAC-SH65OF-E PAC-SH59KF-E PAC-SG03TM-E PAC-SG01KF PLP-6AALM PLP-6AAMD PAC-SG06SP-E PAR-SL99B-E PAR-SL94B-E PAC-SH20DM-E PAC-SH21DM-E PAC-SH83DM-E PAC-SH85DM-E PAC-SH84DM-E PAC-SE80KF-E PAC-SE81KF-E PAC-SH88KF-E PAC-SH89KF-E PAC-SK005MT-F PAC-KE03DM-F PAC-SK010DK PAC-KE92TB-E PAC-KE93TB-E All models excpet wireless remote controller use model All models MFZ-KA·VA SEZ-KD·VA(L) SEZ-KC25VA SEZ-KA35/50/60/71VA SEZ-KA·VA Drain pump High-efficiency filter Motor (for high external static pressure) Drain pump Insulation kit Filter box All models except MFZ-KA·VA PLA-RP·BA(2) PLA-RP·AA PCA-RP·GA(2) PCA-RP·KA PCA-RP50, 60GA(2) PCA-RP71GA PCA-RP50KA PCA-RP60KA PCA-RP71KA PCA-RP50GA(2) PCA-RP60, 71GA PCA-RP50KA PCA-RP60, 71KA PEAD-RP71EA PEAD-RP·EA, EA2 PEAD-RP·GA PEAD-RP35, 50JA(L) PEAD-RP60, 71JA(L) 10-2. OUTOOR UNIT Part Name Drain socket Drain socket assembly Model Name MAC-851DS MAC-811DS 109 Applicable model SUZ-KA25, 35VA SUZ-KA50, 60, 71VA HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING Distributed in Oct. 2009 No.OCS03 REVISED EDITION-C Distributed in Nov. 2007 No.OCS03 REVISED EDITION-B Distributed in May 2007 No.OCS03 REVISED EDITION-A Distributed in May 2006 No.OCS03 PDF 8 Made in Japan CO., LTD. PDF 6 PDF 7 PDF 7 New publication, effective Oct. 2009 Specifications subject to change without notice.