1. Specifications
1-11 Installation Instructions
■ Electrical Wiring
• Indoor Unit
Type
(F) Power Supply
2.5 mm2
Time Delay Power Supply Terminal Base
Fuse or
Capacity
Max. Wire
Circuit
Diameter
Capacity
X, S, AS, T, U, SL
245 m
15 A
50 A
14 mm2 (AWG#6)
K
588 m
15 A
25 A
5.5 mm2 (AWG#10)
D
89 m
15 A
50 A
14 mm2 (AWG#6)
Control Wiring
(C) Inter-Unit Control Wiring
0.75 mm2 (AWG#18)
Use Shielded Wiring
Max. 1000 m
1)
(D) Remote Control Wiring
0.75 mm2 (AWG#18)
(E) Control Wiring For Group Control
0.75 mm2 (AWG#18)
Max. 500 m
Max. 500 m
NOTE
Refer to the Wiring System Diagrams (Ref. next
page) for the meaning of “A”, “B”, “C”, “D”, “E”,
and “F” in the above tables.
2)
Inter-Unit Control Wiring (c) has no polarity.
But for other wiring, respect polarity.
Be sure to connect as shown in the Wiring System Diagram.
3)
The basic connection diagram of the indoor unit
shows the 8P terminal board, so the terminal
boards in your equipment may differ from the
diagram.
4)
8P terminal board
5P terminal board + 3P terminal board
1
1
2
U1
U2
R1
R2
R3
1(L)2(N)
Power
supply
R1 R2 R3
Remote
U1 U2 controller
Inter-unit
control wiring
0511_M_I
1
2
3
4
5
1(L)2(N) 4 5
1 2 3
Power
Inter-unit
Remote
supply control wiring controller
0512_M_I
Only for K type
In accordance with conformity of EC Directive No.
89/336/EEC, when connecting power supply, it
should be considered guidance showing below.
*
*
2
Do not share a common installation group with
other equipment.
Be sure that supply network impedance is
sufficiently low ( ZSYS
RΩ).
It may be necessary to consult the power
supply authority before connection of the air
conditioner to a low-voltage public network.
I I[
3
R407C Models
Models
RΩ
Remarks
25 type (3 phase) —
Not necessary to consider supply network impedance
36 type (3 phase) 0.192 Conforms to the local code
48 type (3 phase) 0.167 Ditto
25 type (1 phase) 0.126 Ditto
4
5
I - 105