Download Siemens RDG Technical data
Transcript
The Economy setpoints are accessible at the service level (P11, P12); the Protection setpoints at the expert level (P65, P66). 3.3.2 Setting and adjusting setpoints Room temperature setpoints can be – set during commissioning – adjusted during runtime KNX R Comfort basic setpoint Comfort setpoint The source can be – the local HMI – a tool – a central control unit The thermostat stores the setpoints – in EEPROM in the form of parameters – in the runtime memory The table below shows the interrelations: Setpoint setting Commissioning – HMI – Tool download Comfort basic setpoint Dead zone Comfort 1) Setpoint Economy Heating Setpoint Economy Cooling Setpoint Protection Heating Setpoint Protection Cooling Input LTE mode Input S-mode Setpoints Heating Setpoints Cooling Setpoints Heating Setpoints Cooling Comfort basic setpoint Current runtime setpoints in thermostat Comfort setpoint Economy Heating Economy Cooling Protection Heating Protection Cooling Effective room operating mode Stored in EEPROM of thermostat Setpoint adjustment Input LTE mode 2) Setpoint shift H Setpoint shift C Setpoint shift H Setpoint shift C Input S-mode 3) Comfort setpoint P08 Comfort basic setpoint P33 Dead zone Comfort 1) P11 Economy Heating P12 Economy Cooling P65 Protection Heating P66 Protection Cooling New current runtime setpoints in thermostat Local operation 3) Rotary knob Comfort setpoint Economy Heating Economy Cooling Protection Heating Protection Cooling Current setpoint (used by the thermostat for temperature control) 1) Only required for heating AND cooling applications (see section 3.6.10) 2) LTE mode: the shift is added to the local shift 3) S-Mode: the last intervention wins, either S-Mode input or local operation 21 / 86 Siemens Building Technologies RDG100KN Basic documentation Functions CE1P3191en 22 Jun 2010