3.5 Additional functions Heating / cooling changeover via bus The heating / cooling changeover information can be received via bus. This is only possible if the control sequence is set to automatic heating / cooling changeover (parameter P01 = 3) and no local input X1, X2, D1 is assigned with this function. K NX In the absence of the required information (e.g. due to problems with data communication, power failure, etc.), the thermostat operates in the last valid room operating mode (heating or cooling). R Heating/cooling changeover Automatic heating / cooling changeover via changeover sensor If a cable temperature sensor (QAH11.1 + ARG86.3) is connected to X1 / X2, and parameter P38 / P40 is =2, the water temperature acquired by the changeover sensor is used to change over from heating to cooling mode, or vice versa. When the water temperature is above 28 °C (parameter P37), the thermostat changes over to heating mode, and to cooling mode when below 16 °C (parameter P36). If the water temperature is between the 2 changeover points immediately after power-up, the thermostat starts in heating mode. The water temperature is acquired at 30-second intervals and the operating state is updated accordingly. M 16 M Tw[°C] 28 Cooling mode Operating mode Tw Water temperature Changeover switch Heating mode The QAH11.1 cable temperature sensor for automatic heating / cooling changeover can be replaced by an external switch for manual, remote changeover: X2 M T QAH11.1 X2 M 3076Z03 Contact open heating mode Contact closed cooling mode T °C The sensor or switch can be connected to input terminal X2 or X1 or D1 (switch only), depending on the commissioning of the inputs (P38, P40, P42). See also section 3.9 “Multifunctional input”. Manual heating / cooling changeover If manual heating / cooling changeover is commissioned (P01 = 2), then heating / cooling mode cannot be changed via bus / changover sensor / switch; it will remain in the last mode as selected locally via button. External / return air temperature sensor The thermostat acquires the room temperature via built-in sensor, external room temperature sensor (QAA32), or external return air temperature sensor (QAH11.1) connected to multifunctional input X1 or X2. Inputs X1 or X2 must be commissioned accordingly. See section 3.9 “Multifunctional input”. 25 / 86 Siemens Building Technologies RDG100KN Basic documentation Functions CE1P3191en 22 Jun 2010