Download Carrier 38BYG Specifications
Transcript
38BYC, 38BYG 12 SEER SpMit System Heat Pump HEATUNG & COOUNG %isitx__ _.¢arrier.com Installation and Start-Up NOTE: Read installation. This symhoi the entire instruction --> indicates a change SAFETY Improper or installation, use can conditions damage. installer when Consult a qualified installer_ packaged with codes. Have extinguisher Wear Use you manuals, this symhol the signal glasses, your instructions protective cloth t:br brazing Read these clothing, operations. instructions thor- included in literature codes and National A98525 requirements. on the unit words or The qualified Fig. 1--Mode{ This is the safety-alert be alert to the potential Understand agency, kits or accessories local building [br special other installing. or cautions informatiom see when safety available. (?ode (NEC) safety service or or property to the individual quenching to the unit. Consnh Recognize When Refer and _\_llow all warnings Electrical injury, or assistance. the kits or accessories gloves. the maintenance, shock, must use _hctory=authorized this product. all safety and attached personal for infornmdon and work fire service, electrical death, or agency oughly fire, may cause modi_}-ing Follow alteratiom explosion, or branch starting since the last issue. which distributor before CONSIDERATIONS adjustment, cause manual and for personal DANGER, symbolz_ in instructions could injury result identify or death. or in personal unsafe practices injury. signifies injury or death. which would and CAU= injuw or product and property suggestions which will result hazards (AUTION result 4 Leave some to personal When passing with RTV 6. Avoid which is used in minor 5 joists, direct robing 9. When that gas pulsations fiom h Locate unit away where 2. Ensure fiom window< unit operation sounds patios, may disturb that vapor- and liquid-robe capacity When outdoor indoor diameters decks, and so forth customer unnecessary tubes Manufacturer reserves PC 101 as directly are appropriate as possible to by avoiding and bends. the right Catalog absorb the wall, seal opening based with water caulk. (See Fig. 2.) pipes, duct work, floor and walls. insulation of robing straps is pliable straps using charge Maximun_ applications Always existing coil or fan coil units. which liquid including and metal sleeves indoor unit, charge fbr operation connected by 15 For proper charging with fi of unit opera- information line size is 3/8-im located O.D. fc_r all long line. a liquid field service Always by using robing. using install are 1 in. wide (See Fig. 20 to ihctory-approved system refrigerant same size when or factoo'-accesso<v INPORTANT: sur- of insulation. unit is connected unit contains unit of the IMPORTANT: and completely insulation. from insulation to shape tion, check refi'igerant on control box cover. system rams outdoor residential of unit 3. Rm_ refrigerant hanger field-supplied of equipment silicon use hanger bent to confbrm in the living area has been traced to installation to unit tube. necessary, 10. Isolate RECOMMENDATBONS improper and robes through contact robing vapor con_bm_ to shape Be%re installing, modif}'ing, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning tahet. Electrical shock can cause personal injury or death. cases noise structure (See Fig. 20 rounds In some refi'igerant or other pliable wall studs, floors, 8. Ensure or operation. NOTE: between 7. Do not suspend refiigerant tubing fi'om joists and studs with a rigid wire or strap that comes in direct contact with robing. damage. NOTE is used to highlight in enhanced installation, reliability, iNSTALLATiON slack vibration WARNING, WARNING 38BYG . TION. These words are used with the saf_b_-alert symbol. DANGER identifies the most serious hazards which will result in severe personal Instructions use line filter drier on line sets and or existing a filter direr on burnout insurring obligations, any indoor unit replacements. to dissontinue, No. 533-80078 or change at any Printed time, in USA specifications Form or designs 38BYC-3SI without notise Pg 1 and without 11-02 Replaces: 38BYC-2SI I NOTE: Avoid contact between tubing and structure _-- OUTDOOR WALL--_ -_. 1 INDOOR WALL_" CAULK C lq/N 7/_ vAPOR 1 TUBE SULATi THROUGH THE WALL HANGER STRAP*_ (AROUNDVAPOR_ TUBE ONLY) _,,\ l _lr'f--JOIST /_ INSULATION I I 3/8"D (953) TIEDOWN ............................. () KNOCKOUTS i __.-VAPOR r' MtN.--I TUBE L I_ B (2) PLACES .I A94199 LIQUID TUBE Dimensions On.) SUSPENSION UNIT SRZE NINIMUM MOUNTING-PAD DIMENSIONS TIEDOWN A B C 018-024 22-112 X 22-1/2 3-11116 18-1/8 14-3/8 030°060 30 X 30 6-1/2 23-1/2 20 A94028 Fig. 2--Connecting Tubing Installation _NSTALLATION Step l--Check L NPA(K Move uniL Equipment Fig. 3--Mounting and Job On rooftop surface. Remove carton, taking Step is damaged company or incomplete. prior to installation Locate unit rating plate panel. It contains int'ornaation Check rating to be sure unit matches Step plate 2--Bnstall [f conditions needed On A Solid, or local codes should Level require be used the unit in unit base pan. Refer to unit mounting applications, a load bearing strocture. Arrange and minimize codes mount and fastened transmission governing rooftop through of vibration 3--Clearance pattern in Fig. 3 to adequately to building. set fi'om support unit Consult ÷ 2° (÷ 3/8 local inJft) When installing, allow refrigerant piping, service end of unit and 48 in above uniL For proper airflow, so water, snow, space for or ice from roof ambient operating outdoor in cooling ambient operating mode in cooling ambient is 55°F, mode in heating is mode Allow roof Unit of water and ice in base pan may cause damage. In areas where prolonged freezing temperatures are encountered, elevate unit per local climate and code requirements to provide clearance above drainage airflow 30-in or eaves estimated snowfidl level and ensure adequate of unit Step 6--Remove TXV Indoor AccuRater® Piston and Install per cleaIance, clearance to proper unit operation with field supplied with evaporator coils having and reliability, hard shutoff capiltaQ" TXV units must be Do not install robe metering devices or pistons. a 6=in clearance or* 1 side of unit and 12 in on all remaining sides must be maintained, Maintain a distance of 24 in between units on unit above or _?ame. Place unit and robing wiring, directly operating outdoor 5--Elevate installed Position outdoor Accumulation For and service 6 in. Ambient 125°F The maximum is 66°F, equipment Requirements sufficient at least to pad, applications. NOTE: Unit must be level to within compressor manufacturer specifications. unit knockouts Roof mounted units exposed to winds above 5 mph may require wind baft'les to achieve adequate defrost. Consult Low Ambient Guideline for wind baffle construction. Step 4-==Operating and the maximum Step Pad on level platform members unit. hole location. wall and isolate supporting install be attached provided On rooftop on unit service Mounting base pan size and knockout locate job specifications. bolts unit above if shipment to properly tiedown to detem_ine applications, The minimum with shipping Unit to Pad care not to damage ]:NSPECT EQUIPMENT File claim LOCATIONS Site UNIT to final location, KNOCKOUT cannot Pall For TXV kit part number and charging instructions, refer to TXV label in outdoor unit If indoor unit (fire coil) comes f_cto_ equipped with a bi-flow hard shutoff TXV, no TXV change is required, If TXV installation indoor coil is required, Re_r to Figs 1_ Install suction 2. Install liquid 3. Connect remove existing AccuRater_ t'rom 4 and 5 and install TXV kit as _bllows: robe adapter_ flareoto-sweat external feeder tubes, there is a 3/%in. O.D. stub robe approximately adapter. equalizer robe to fitting on suction robe of suction robe adapter. f 4. Position sensing adapter. Secure 5. Insulate d. Leak bulb using on horizontal supplied bulb aRer installation. check 2 in. tong. (See Fig. 60 The defrost thermostat should be located on stub mbe_ Note that there is only 1 stub robe used with liquid header, and on most units it is the bottom circuit_ portion STUB TUBE hardware. (See Fig. 5.) all connections. DEFROST THERMOSTAT A97517 BULB Fig. 6--Defrost UALIZER TUBE Step 9--Make Relieve repair EXPANSION VALVE Use Piping pressure Thermostat Connections and recover or final unit disposal all service including ports solenoid Location all refi'igerant before to avoid personal and open all flow system ir_.iuI?' or death. control devices, valves. A88382 Fig. 4--Typical TXV Insta!lation If ANY refrigerant robing is buried, provide a 6 in. vertical rise at service valve, Ret'rigerant robing lengths up to 36 in, may be buried without further special consideration. For lengths longer than 36 in., refer to Application Guideline and Service Manual Residential Split System Air ( onditioners and Heat Pumps, O'CLOCK 2 SENSING L-_'S UCTIO N To prevent 8 O'CLOCK 4 O'CLOCK 7_ IN. OD & SMALLER LARGER THAN damage to unit or service valves obsela'e the wet or use a heatosink fbllowing: 7_ IN. OD *Use a brazing shield *Wrap service material valves with cloth A81032 Outdoor Fig. 5--PositioNng Step 7--Check (beck outdoor Outdoor of Sensing AccuRater® Bulb units may be connected robing package Remove Piston retainer and check piston size with n_atching rating plate. Step 8--Check Defrost Thermostat (heck defiost thermostat to ensure securely attached and feeder robe nm'uber into outdoor listed on outdoor valve unit coil located and refrigerant For robing requirements tial capacity and recommendations per_brmance losses in the Residential for field Guideline tubing will equivalent accessory requirements For buried Residential line applications Split System Buried it is properly There is a liquid header going on liquid service to indoor size and condition Application unit piston or field-supplied line applications section using accesso_ grade robing of coll'ect beyond 50 it, substan- can occur Following the Split System Long-Line redtlce these losses. line length Refer Ret'cr to Table to Table greater than 36 in., refer to Table 2 and Buried Line Application Guideline. may not exceed 100 t't. with a brass distributor If refrigerant tubes or indoor coil are exposed to atmosphere, must be evacuated to 500 microns to eliminate contamination At the end of 1 of the moisture in the system 1 2 _br they and Table 1--Refrigerant UNIT SiZE Connections And Recommended LBQUID Diameter Tube Diameter Connection Connection Liquid= And Vapor=Tube VAPOR Diameter Diameters (in.) VAPOR (LONG LINE) Connection Diameter Tube Diameter Tube Diameter 018 3/8 3/8 5/8 5/8 5/8 3/4 O24 3/8 3/8 3/4 3/4 3/4 3/4 030, 036 O42 3/8 3/8 3/4 3/4 3/4 7/8 3/8 3/8 7/8 7/8 7/8 1-1/8 048, 060 3/8 3/8 7/8 1-1/8 7/8 1-1/8 NOTES: 1 Tube diameters are for lengths up to 50 ft. For tubing _engths greater than 50 ft horizontal, and Service Manual -- Air Conditioners and Heat Pumps. 2 Do not apply capillary tube indoor coils to these units OUTDOOR E_IT INDOOR indoor field-supplied or REFRIGERANT Connect cmTect unit system of same f_cto_ for maxin-mn_ service APPROVED attention secure unit contains with charge TO FACTORY UNIT Outdoor tion CONNE(TED refrigerant size when accesso_ charge fbr opera- connected robing. by Check Step robing to feeder tubes, making 10--Nake Electrical to fittings rei'rigerant on outdoor unit 1.) Lse refi'igerant vaporgrade and liquidrobing Be sure field wiring complies and electrical and voltage codes, on unit rating plate NOTE: abuse 7) Connect refi'igerant and liquid-service and tea@ cloth, holding sweat/flare robing valves. for brazing. or non-silver requirements. bearing This check are closed wrapping service to service brazing tubing should in liquid to vah'e on outdoor Selwice valves After Refi'igerant leak testing. piston provided to fittings robing set can be brazed bearing outdoor adapter service (See Fig unit vapor- valve with a wet silver Consult local code and indoor coil are now ready include for all field and fi_cto_" joints. Operation pem_issible Lse of unit GROUND Remove access unit occur. metal conduit Connect Route ADAPTER unit has not shifted during against each other Valve shipment. or any sheet Do not or below disconnect switch and Ensure metal. tubes are Pay close Failure wire power to 440-14 of NEC. to unit wiring. Extend hole provided injury or unbroken if an electrical may consist wires and into unit of electrical in accordance with to fbllow this warning fhult wire or existing can result in an AND POWER to ground wiring connection to contactor in control as shown box in Fig for 8. WIRING wires through control wiring. for wiring WIRES specific contloi wiring See Them_ostat unit combinations grommet and Installation (See Fig. 9) Use No. 18 AWG color coded, insulated (35_>C mininmm) wire. If thermostat is located more than 100 ft fi'om unit, as measured along the contlol on both indoor of adequate size per disconnect within sight fire, or death control leads Instractions A97512 robbing above an uninterropted installed (ONTROL 24v connect have ground GROUND (ONNE(T and outdoor constitutes WIRES wiring personal when ground safety not between power must The shock, Connect tubing only POWER through codes electric STRAINER fuctory line voltage may fluctuate panel to gain access cabinet should CONNE(T to be certain of circuit- See unit rating plate from unit, per Section AND to minimize electrical PISTON RETAINER (beck wire accessible ROUTE PISTON mMPORTANT: on improper where voltage copper from and readily ground Fig. 7--Liquid-Service fbr recommended NOTE: Install branch circuit disconnect NE( to handle unit stmling cun'ent Locate The SWEAT/FLARE shown fbr convction limits. from disconnect control box PISTON "_'_ limits device. and could affkct unit reliability NOTE: unit company plate fire, safkty, is within fi'om facto_ valve using either material. to system See unit rating install unit in system retainer power to unit with local and national ( ontact tocal power voltage. protection plastic are Connections To avoid personal injmy or death, do not supply with compressor terminal box cover removed. (See Table and connect sure wire ties on f_eder tubes and tight improper vah'e Guideline efficiency. SWEAT CONNE(TION Remove consult the Application 15 ft of TUBING valves. or greater than 20 fl vertical differential, to avoid All excessive wiring incoming must power voltage wires, use No. 16 AWG voltage &op be NEC Class leads 1 and must color coded wire be separated from Tab{e 2--Accessory Usage REQUIRED FOR LOW-AMBiENT APPLICATBONS (BELOW 55°F} Yes REQUIRED FOR LONG-LINE APPLICATIONS* (OVER 50 FT) Yes REQUIRED FOR BURRED LINE APPMCATBONSt (OVER 3 FT) Yes Evaporator Freeze Thermostat Accumulator Yes No No No No Yes Compressor Start-Assist Capacitor and Relay MotorMaster® Control, or Low-Ambient Pressure Switch Yes Yes Yes Yes No No Wind Baffle See low-ambient instructions No No Unit Risers Recommended No No ACCESSORY Crankcase Heater Liquid-Line Solenoid Valve or Nard-Shutoff TXV BaR-Bearing See Long-Line Application Guideline No Fan Motor Yes_: Yes No No * For tubing line sets between 50 and 175 ft, refer to Application Guideline and Service Manual -- Air Conditioners and Heat Pumps. ? For buried line applications, refer to Application Guideline and Service ManuN -- Air Conditioners and Heat Pumps $ Required for low-ambient controller (full-modulation feature) and MotorMaster@ Control only. Step 13--Start-Up DISCONNECT PER N. E. C. AND/OR LOCAL CODES e CONTACTOR FIELD POWER 1 To prevent compressor damage or personal injnry, observe the following: *Do not overcharge system with refi'igerant, *Do not operate unit in a vacuum or at negative pressure, *Do not disable low-pressure switch In scroll compressor applications: *Dome tempe*amres may be hot, C)° C) WIRING C)oC) FIELD GROUND Q WIRING GROUND LUG ] A9f05g Fig. 8--Line "Use t'urnace former trans%rmer, for control NOTE: Use of available mum 40va power capacity ensure forth. wires 11--Compressor When equipped outdoor longer fhctolw are secured are not in contact Step trans- *Back-seating may exceed the mini- total transformer load- or split the load with an wiring and properly. wire Check with tubing, Crankcase with a crankcase sheet connections to wire routing to metal and so Heater heater, fi/rnish power to heater a of 24 hr bet'ore starting unit To f_lrnish power to heater thermostat to OFF and close electrical disconnect [o unit personal ir{jury clothing, and gloves tke t'ollowing: valves. removing when seix'ice wear handling valves safety glasses, refi'igerant are not equipped Fully back seat (counterclockwise) gage=port *Front=seating valves, protective and obsma'e with Schrader valve stem befbre cap service valves are equipped with Schrader as required. (heck terminations minimum only, set 24v accessories the transfbrmer ensure or accesso_ minimum. Determine tlansformer IMPORTANT: 24vi40va requirement. ing and increase accessory fbn coil transfom_er, power, To prevent Power Connections A crankcase heater is required if refi'igerant robing is than 50 ft Step 12--install EtectricN Refer to the individual series when installing. Accessories instrnctions packaged with kits oi" acces= Federal Regulations require that you do not vent retiigerant to atmosphere, Recover during system repair or final unit disposal, Follow these steps to properly pumpdown negative suction pressu*e a system and avoid 1 Fully back seat (open) tiquid- and vapor-robe so*vice valves 2 l_nit is shipped with valve stem(s) fiont seated (closed) and caps installed Replace stem caps after system is opened to refrigerant flow, Replace caps f_nger-tight and tighten with wrench an additional 1/12 turn, 3 (lose electrical disconnects to energize system, 4, Set room is below them_ostat 5, Set room them_ostat o1" A'LTO Check to HEAT outdoor Be sure set point or COOL and fire control as desired. Operate unit fbr to ON 15 minutes charge. supplied board may to indoor be equipped upon with any interruption position. Circuit and outdoor them_ostat R=Y motor and compressor relay, starting When thermostat energizes circuit. units, NOTE: If indoor relay. open, and motors should is satisfied, and relay. The defi'ost contlol field=selectable trans*brmer starting on high its contacts unit is equipped R=O, R=¥, switching contactor, Compressor runs an additional circuits valve, R-G energizes motor is satisfied, and blower makes reversing indoor=blower contactor the blower its contacts thermostat All heaters between minutes. is deflost indoor energized and open, and defrost and defi'ost mode is identical outdoor=_im stops and unit=blower wamaing thermostat circuit and bring de-energizing stop. conditioned stop. 2. Disconnect board. factoQ set at 90 start only when contactor mode except heat is turned thermostat to outdoor is that outdoor=fan on to continue must be closed. This can outdoor=Jim unit. motor (See Fig. 10.) Tape TYPICAL FAN COIL HP THERMOSTAT a time period as %llows: 1. Turn off power efficiency. which includes edge) space. defi'ost, the defiost relay circuit, system at board is closed. to cooling second-stage be accomplished the should cycle flaermostat motor To initiate with a time=delay timer control located (30, 60, or 90 minutes), Defi'ost de=energizing 90 sec to increase cycles it to cooling speed. and motors is a time/temperature (quick=connects The electronic Circuit R=O energizes of outdoor When 5-minute ( OOLING On a call _br cooling, setting close to complete electric heat. of power. energized. R-G. fi_lls below DEFROST timer that may be initiated power temperature (field=installed option), contacts on second bank of supplemental contactor OF OPERATION Defi'ost=control lockout With mode, temperature, temperature system=refi'igerant SEQUEN(E NOTE: to desired indoor=ambient lead [i'om lead to prevent OF2 on control grounding. HEAT PUMP m 24 VAC HOT 24 VAC COM HEAT F_ ,a--D ---q4S STAGE E_ COOL/HEAT STAGE 1 INDOOR FAN RVS COOLINC E_ EMERGENCY HEAT (See Thermostat * IF AVAILABLE A02325 Fig. g--Generic Wiring Diagram Insta{iation Instructions for wiring specific unit combinations.) LEGEND 24-V FACTORY WIRING 24-V FIELDWIRING FIELDSPLICECONNECTION ODT OUTDOOR THERMOSTAT EMERGENCY SUPPLEMENTAL HEAT RELAY HEAT RELAY A97413 HEATING On a call for heating, thermostat makes (ircuit contactor, starting R=¥ compressor. blower Should energizes Circuit motor R-G energizes R=¥ outdoor=_im indoor-blower and R-G motor relay, and starting on high speed. temperature continue second-stage room=them_ostat relay, bringing on first bank providing circuits electrical potential 3, Restart unit in heating mode, allowing[i'ost outdoor coil. 4. After a few minutes should drop proximately to £fll, R=W2 bulb, Circuit of supplemental to second heater is made through 5. Short R-W2 energizes a electric heat and relay (if used) If below in heating closing mode, point to accumulate on liquid-line of defiost temperature thermostat (ap= 30°F). between speed=up &iver. (See Fig. 1/256th of original 10) terminals This with reduces the time. (See Table 3.) a flat=blade timing screw- sequence to EXAMPLE: To calculate 25 ft additional charge 15 ft 10 ft X 06 Units installed with cooling subcooling 1 required ozi[_ for a 25 k line set: 6 oz of additional mode TXV require charge charging with the method. Operate unit a minimum of 10 minutes befbre checking charge. 2. Measure liquid service=valve gage to service 3. Measure pressure by attaching an accurate port. liquid-line temperature thermistor type or electlonic outdoor coil. by attaching them_ometer 4. Refkr to unit rating plate for required an to liquid subcooting accurate line near temperature. 5. Refkr to Table 4. Find the point where required subcooling temperature intersects measured liquid service=valve pressure. 6. To obtain liquid-line required pressure, subcooling temperature add refrigerant at a specific if liquid-line is higher d-_an indicated or reclaim refrigerant lower. Allow a tolerance of ÷ 3_T. temperature if temperature is CES0110063, CES0130024 TaNe 4--Required Liquid=Line Temperature (°F) A91444 LIQUID PRESSURE AT SERVICE VALVE (PSIG) 134 5 10 15 20 71 66 61 56 t41 74 69 64 59 148 77 72 67 62 186 80 75 70 65 163 83 78 73 68 t71 86 81 76 71 t79 89 84 79 74 187 92 87 82 77 19G 95 90 85 80 remove 205 98 93 88 83 tem_inate 214 101 96 91 86 223 104 99 94 89 of time 233 107 102 97 92 valve 243 110 105 100 95 253 113 108 103 98 264 116 111 106 101 274 119 114 109 104 288 122 117 112 107 297 125 120 115 110 309 128 123 118 113 321 131 126 121 116 331 134 129 124 119 346 137 132 127 122 389 140 135 130 125 Tab{e 3--Defrost Control SpeedupTiming Sequence 30=minute cycle MBNIMUN (MRNUTE$} 27 50=minute cycle 45 90=minute cycle 81 t0=minute cycle 8 minutes 9 PARAMETER MAXIMUM (MINUTES) 33 you screwdriver nom_al NOTE: Length of defiost it takes to remove has shire& 7. Unit will remain or until defrost temperature in defrost thermostat of liquid 8. Turn off power Step 14--Check Factory charge cooling mode. in heating plate respectively cycle control will in approximately is dependent upon 2 sec. length fiom test pins aker reversing for remainder reopens of defrost-cycle at approximately unit and reconnect time 80°F coil _hn motor lead (See Fig. 10.) on unit rating ret'cr to Cooling mode, charge ÷ 0.6 board. is shown Only refer to Heating plate. To check Procedure. Check charge To check in charge (7hart Procedure. HEATING or subcooling=charging must be weighed ozi['t of 3/8-in. liquid CHE(K CHAR7 PROCEDURE To check system operation dtlring Heating Check (;hart on outdoor unit PROCEDL RE If superheat= favorable, othep.vise, position, Charge COOLING=ONLY NOTE: change line. to outdoor to OF2 on control Control valve cycle screw&iver 2 sec 1 sec 5.5 immediately; defrost 21 sec 11 reversing 10=minute 12 sec 99 4.5 hear 7 sec 55 Fig. 10--Defrost 6. When SPEEDUP (NOMINAL) REQUIRED SUBCOOLING TEMPERATURE (°F) in accordance line above conditions are not a correct relationship with unit rating air temperature or below temperature 15 ft exists entering do not match not be con'ect. between indoor heating cycle, refer to the This chart indicates whether system and outdoor on chart, system Do not use chart to adjust operating units. pressure If pressure ret'rigerant charge refrigerant charge. and and may NOTE:Whencharging is necessawduringheating season, charge must beweighed inaccordance withunitrating plate ÷ 0.6 oziftof3/8-in. liquidlineabove orbelow15ft respectively. EXAMPLE: Tocalculate additional charge required fora25 ft line set: 25 fi 15 ft 10 ft X 0.6 ozit't Step 15--Final 2. Tighten Copyright 2002 Before CARRIER Manufacturer B°°k Tab 1h_ 15al 5a reserves PC 101 job, be sure to do the fbltowing: Corp. the _ 7310 right catalog W. Morris St to discontinue, No. failure, Frequency caps to 1i12=mm 533-80078 past finger-tight. • Indianapolis. or AND Explain system requirements outlined Checklist and place operation in manual. in customer MAINTENANCE change high per%m_ance periodic and to minimize maintenance must possible be perfbm_ed areas, of maintenance such as coastal may vary depending upon at any time, in USA geographic applications IN 46231 Printed equip= on this equipment and covers. valve=stem with owner Installation CARE ment leaving Manual maintenance 4. Fill out Dealer file. For continuing fitsten all panels service L ser's and periodic charge Checks mNPORTANT: 1. Securely 6 oz of additional 3. Leave 38byc3si specifications Form or designs 38BYC-3SI without notice Pg 8 and without 11-02 incurring obligations. Replaces: 38BYC-2SI