P frost T (pump frost protection temperature)
Circuit
Setting range
Factory setting
1
OFF / -10 ... 20 °C
2 °C
Frost protection, based on the outdoor temperature:
When the outdoor temperature is below the set temperature in ‘P frost T’,
the controller automatically switches ON circulation pump X3 to protect
the system.
OFF:
If the outdoor temperature sensor is not connected and the factory
setting has not been changed to 'OFF', the circulation pump X3 is
always ON.
No frost protection.
-10 ... 20: Circulation pump X3 is ON when the outdoor
temperature is below the set value.
11027
Room T diff. — A214.3 / A314.3
Circuit
Setting range
Factory setting
1
–9.0 ... –0.5 K
–2.0 K
The relay 3 (X3) can be activated when the room temperature gets lower
than the desired room temperature.
Relay X3 is activated when the difference between the actual room
temperature and the desired room temperature is bigger than the set value.
Relay X3 is deactivated when the actual room temperature becomes higher
than the desired room temperature.
–9.0 ... –0.5
Under normal conditions, your system is not frost protected if your
setting is below 0 °C or OFF.
For water-based systems, a setting of 2 °C is recommended.
In order to activate the relay X3 in relation to room temperature
difference, the code setting in 'Optional function' must be "3".
Room temp.
°C
Room T diff.
Desired room temp.
Set the desired temperature difference.
Actual room temp.
ON
OFF
Relay X3
Time