D9412G/D7412G/D7212G
System Wiring Diagrams, Issue A
4.7
D7212G Control Panel, 1 of 3
If required by local AHJ,
connect D113 Battery Lead
Supervision Module.
BAT 2-
-
+
D126
or
D1218
-
D113
CHGR-
BAT 2+
VAUX+
BAT 1-
SUPV
BAT 1+
CHGR+
To Battery Negative
To AUX+
To Point Input
To Battery Positive
+
D126
or
D1218
Optional
D122 Dual
Battery Harness
As
Required
-
+
-
D126
or
D1218
D1640
16.5 V, 40 VA
60 Hz
Transformer
+
D126
or
D1218
D8004 Transformer
Enclosure as
required by AHJ
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
P
S
D7212G
+ AUX POWER
See D113 for
BATT SUPV
D126
Battery
12 V, 7 Ah
or
D1218
12 V, 17.2 Ah
or 18.0 Ah
D8132
Battery
Charger
P
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
D126
Battery
12 V, 7 Ah
or
D1218
12 V, 17.2 Ah
or 18.0 Ah
RELAY A
D192A/C/G
RELAY B
AUX PWR
OR
ALARM TRIG
RELAY C
COM
SUPV IN
P+
S
-
PROGRAMMABLE
ALARM OUTPUTS
Terminals
7 & 8
Requires Optional
Model D136 Relay
In ALT ALARM
& SW AUX
COMMON
ALARM CKT
Optional
BATTERY NEGATIVE ONLY
EARTH GROUND
P
GROUND FAULT DETECT
Enabled
Disabled
S
Listed
Audible
Signaling
Devices
rated at 10.2
to 13.8 VDC
(Do not use
vibrating
type horns)
Point 1 Point 2
Point 3 Point 4
GROUND START
P
LOOP START
GND START
S
GROUND START
RED PHONE
Requires Relay
LED
Model D136 in O N WHEN
Ground
C OMMUN ICATING
Start Socket
O FF WHEN IDLE
11
12
13
14
15
16
Point 8
GND FAULT
Detect
D
E
I
N
S
A
A
B
B
L
L
E
E
PROG
PROG
CONN
CONN
GRN
C900
To
RJ31X
Jack
EOL Device 15-03130-001
All external connections except terminal 5
(Battery Positive) are inherently power limited.
RJ31X
Primary
Phone Line
To Earth Ground
P = Power Limited
S = Supervised
Figure 8: D7212G System Wiring Diagram, 1 of 3
D9412G/D7412G/D7212G Installation & Troubleshooting Quick Reference Guide
© 2004 Bosch Security Systems, Inc.
Page 29
43700F