Performing Advanced Functions
SLOT
CAUTION
AVAILABLE FOR
Changing these parameters might adversely affect the ability of the device to
operate for extended periods under low solar radiation conditions.
A731
A732
A733
A733GSM
DESCRIPTION
Sets/returns the node’s sampling interval and rate.
PARAMETERS
The interval (60 - 65535) and rate (0 - 255). The interval represents the time (in
seconds) elapsed between two slots stored in the internal memory, while the rate
represents the numbers of samples used to build the average that will be stored.
RETURNS
The interval and rate.
REMARKS
GET/SET. The default interval is 900 (15 minutes) and rate is 15 (15 samples per
quarter of an hour).
REMOTE
Yes, SET only.
EXAMPLE
SLOT 900 15
9193 SLOT 0
#
SLOT
9193 SLOT 900 15 0
#
SST
AVAILABLE FOR
A731
A732
A733
A733GSM
DESCRIPTION
Sets/returns the RTU sensor’s settling time, which is the time that elapses between
powering the sensors and sampling them. Default value is 2 seconds.
PARAMETERS
The settling time in seconds.
RETURNS
The current settling time.
REMARKS
GET/SET.
REMOTE
Yes, SET only.
EXAMPLE
SST 3
9193 SST 0
#
SST
9193 SST 3 0
#
PMP
AVAILABLE FOR
A731
A732
A733
A733GSM
DESCRIPTION
Sets/returns the node’s Power Management Parameters (switches on/off the
battery charge).
PARAMETERS
The lower (switch on) and the higher limit (switch off), both in volts x 10. Standard
Values are 65 (for 6.5 Volts) for switch on and 72 (for 7.2 Volts) for switch off (for a
standard 6.2 Volt NiCd battery). From these values, other thresholds are internally
computed.
RETURNS
The lower (switch on) and the higher limit (switch off), both in volts x 10.
REMARKS
GET/SET.
31