15.0 DESCRIPTION OF PARAMETERS P01 LINE VOLTAGE SELECTION This calibrates the drive for the actual applied input voltage. Set this parameter to HIGH (01) for 120, 220-240, and 460-480 Vac input, or LOW (02) for 200-208 and 380-415 Vac input. NOTE If this parameter is changed while the drive is running, the new value will not take effect until the drive is stopped. P02 CARRIER FREQUENCY This sets the switching rate of the output IGBT’s. Increasing the carrier frequency will result in less audible motor noise. Available settings are: 4 kHz, 6 kHz, 8 kHz, and 10 kHz. PARAMETER SETTING CARRIER FREQUENCY AMBIENT OR OUTPUT DERATE 01 4 kHz 40 C or 100% 02 6 kHz 40 C or 100% 03 8 kHz 40 C or 100% 04 10 kHz 35 C or 92% NOTE • The SCL/SCM drive is fully rated up to 8 kHz carrier frequency. If the 10 kHz carrier frequency is selected, the drive’s ambient temperature rating OR output current rating must be de-rated to the value shown in the table above. • If this parameter is changed while the drive is running, the change will not take effect until the drive is stopped. P03 START METHOD WARNING! Automatic starting of equipment may cause damage to equipment and/or injury to personnel! Automatic start should only be used on equipment that is inaccessible to personnel. 01 NORMAL: The drive will start when the appropriate contact is closed on the terminal strip. See Section 11 for possible control configurations. 02 START ON POWER UP: The drive will automatically start upon application of input power. 29 SM01J-e2.indd 29 2/6/2007 10:47:42 AM