for detailed information about the gas type and BTU
content (heating value) before operating any heater.
Tables 2.1 and 2.2 show the standard derated heating
values (4% per 1,000’ of elevation in the USA and 10%
between 2,001’ and 4,500’ elevation in Canada) of natural
and propane gases at various altitudes. If the utility is
supplying gas with heating values as shown in Tables 2.1
and 2.2, the manifold pressure should be set to 3.5 in. W.C
for natural gas and 10.0 in. W.C. for propane gas.
Derated BTU Content Gas and Manifold Pressure
Calculation
Some utility companies may derate the BTU content
(heating value) of the gas provided at altitude to a value
3
3
other than 1,050 BTU/ft for Natural Gas or 2,500 BTU/ft
for Propane Gas to allow certain heating appliances to be
used with no manifold pressure adjustments. For this
reason it is necessary that the supplying utility be contacted
Table 2.1 – Natural Gas Heating Values at
Altitude
Gas Heating Values at
Altitude (BTU/ft 3)
USA
CANADA
Altitude (ft)
0‐2,000
1,050
1,050
2,001‐3,000
929
945
3,001‐4,000
892
4,001‐4,500
874
4,501‐5,000
856
856
5,001‐6,000
822
822
6,001‐7,000
789
789
7,001‐8,000
757
757
8,001‐9,000
727
727
9,001‐10,000
698
698
Table 2.2 – Propane Gas Heating Values at
Altitude
Gas Heating Values at
Altitude (BTU/ft 3)
USA
CANADA
Altitude (ft)
0‐2,000
2,500
2,500
2,001‐3,000
2,212
2,250
3,001‐4,000
2,123
4,001‐4,500
2,080
4,501‐5,000
2,038
2,038
5,001‐6,000
1,957
1,957
6,001‐7,000
1,879
1,879
7,001‐8,000
1,803
1,803
8,001‐9,000
1,731
1,731
9,001‐10,000
1,662
1,662

 Values shown are for 3.5 in. W.C. manifold pressure , for other BTU content values (available from local utility) use Equation 2.1 to calculate manifold pressure.
 Values shown are for 10.0 in. W.C. manifold pressure , for other BTU content values (available from local utility) use Equation 2.1 to calculate manifold pressure.
 When installed at altitudes above 2,000', a pressure switch may need to be changed. Refer to Tables 3.1 through 4.2 to determine if a switch change is required.
 Gas Heating Values are derated 4% per 1,000' of elevation in the USA and 10% between 2,000' and 4,500' elevation in Canada in accordance with ANSI Z223.1
and CSA-B149, respectively.
If the heating value of the gas being supplied is different than the values shown in Tables 2.1 and 2.2, use the following equation
to determine the appropriate manifold pressure for the altitude and gas heating value being supplied.
Equation 2.1 – Manifold Pressure for Derated Gas
Where:
MPACT ManifoldPressure in.W.C. atAltitude–Manifoldpressuresettingfortheheaterbeinginstalled
BTUTBL BTU/ft3contentofgas‐obtainedfromTables2.1or2.2 whicheverisapplicable BTUACT BTU/ft3contentofgas‐obtainedfromtheutilitycompany
MPSL ManifoldPressure in.W.C. ,atSeaLevel–use3.5”W.C.forNaturalGasand10.0”W.C.forPropane
NOTE: Only the primary Manifold Pressure should be adjusted on units equipped with two-stage or modulating gas controls.
No adjustments to the Low Fire Manifold Pressure are necessary on these units.
High Altitude Pressure Switch Kit Selection
In some instances, the combustion air proving (pressure) switch may need to be changed depending upon the unit style, model
size, and installation altitude. The example selection procedure shown on the following page, along with the associated tables,
will guide the installer as to when a High Altitude Pressure Switch is required and which switch is to be used.
2