Download MTD B90 Technical data
Transcript
U I A SYSTEM CONFIGURATION The heat pump controller can select configurations for 15 different types of system by setting parameter 0101. The following table describes the system configurations available. Menu Parameter 0101 Mixed zone 1 Mixed zone 2 ZONA "1" Mixed zone 3 ZONA "1" 5 High temperature High temperature High temperature DHW N-EM1 zone 1 (fan coils / zone 2 (fan coils / zone 3 (fan coils / recircu- expansion radiators) radiators) radiators) lation module ZONA "1" 5 ZONA "1" 5 ZONA "1" 5 ZONA "1" 5 5 n° T T M T T M T T M T T T T T T Mn01 0 X 0 Mn01 1 Mn01 2 X Mn01 3 X X Mn01 4 X X Mn01 5 X X X Mn01 6 X X X Mn01 7 X X X X Mn01 8 X X X X Mn01 9 X X Mn01 10 X X Mn01 11 X X X Mn01 12 X X X X Mn01 13 X X X X Mn01 14 X X X X 1 1 1 X 2 2 X 2 2 X 2 2 X X X 2 X 2 X 3 X 3 X 3 Configuration 0 does NOT require additional expansion modules Configurations from 1 to 3 require 1 additional N-EM1 expansion module Configurations from 4 to 11 require 2 additional N-EM1 expansion modules Configurations 12, 13 and 14 require 3 additional N-EM1 expansion modules The water connection and wiring diagrams for configurations from 1 to 14 are shown on the instruction sheet enclosed with the N-EM1 expansion module. The parameters required for correct system operation can be set on the A5 room controller supplied with the heat pump. The next few pages are divided into the following sections: Section 1 WATER CIRCUIT DIAGRAM Section 2 WIRING DIAGRAM Section 3 PARAMETER CONFIGURATION EN 10/2010 i-KI MTD / i-KIR MTD 51