3.3 Notification Appliance Circuits The 7100 provides two (2), 24 VDC Class B, Style Y notification appliance circuits. Class A, Style Z operation is accomplished by adding the Class A Option (CAOM) Module. Wiring Instructions • NAC 1 - TB1-1 (+), TB1-2 ( - ) • NAC 2 - TB1-3 (+), TB1-4 ( - ) (Polarity markings indicate the polarity of the circuit in alarm condition). Use U.L. Listed End of Line Resistor EOL-N (47K), P/N 4700-0512 Circuit Ratings • 24 VDC regulated • Max. alarm load 1.5 amp./circuit • Ground fault test impedance: 20 kOhms • 18 AWG minimum Figure 6 Notification • If synchronization of strobes is required Appliance MDL-FC Synchronization Modules must be connected. Circuit Wiring Class B, Style Y operation only Special application: See Compatibility Addendum/ P/N 9000-0427 for a list of Gamewell-FCI Approved, UL Listed notification appliances. • Supervised • Power-limited NOTE: The CAOM module is furnished with the End of Line resistor installed. 3.4 Signaling Line Circuits The 7100 provides one (1), or two (2), 24 VDC Class B, Style 4 signaling line circuits. Class A, Style 6 or 7 operation is accomplished by adding the Class A Option (CAOM) Module. See Figure 7 for Style 4 or 6 wiring, and Figure 8 for Style 7 wiring. Wiring Instructions SLC 1 - TB3-1 (+), TB3-2 ( - ) SLC 2 - TB3-3 (+), TB3-4 ( - ) (7100-2 only) (Polarity markings indicate the polarity that should be maintained throughout the circuit. Polarity must be observed on all devices connected to the circuit). Circuit Ratings 24 VDC (nominal) Current: 0.090 amp max. (supervisory) 0.097 amp max. (alarm) 0.750 amp max. (short circuit) • 40 Ohms max. line resistance NOTE: A white wire lead of The NCM-1 • 0.5 µf max. line capacitance module (if used) must be connected to earth • Ground fault test impedance: 20 kOhms ground. • 18 AWG minimum, straight lay or twisted-pair Figure 7 Signaling Line Circuit Wiring unshielded • Power-Limited • Supervised See Compatibility Addendum/ P/N 9000-0427 for a list of Gamewell-FCI Approved, UL Listed sensors and modules. 9000-0447 Rev. I Page 15 of 42