Transferring Data Using Communication Blocks Peer Cop Health Description A peer cop health operation reads selected data from the peer cop communications health table and downloads the data to the specified %MW addresses in state RAM. To program an MBP_MSTR block to perform a clear remote statistics operation, use function code 9 (see Operational Function Codes, p. 151). Note: Peer cop health is operational only when a peer cop-based I/O scanner has been configured. The peer cop communications health table is 12 words long; MBP_MSTR indexes these words with the numbers 0 ... 11. Network Implementation Control Block Usage for Modbus Plus 33002479 06 07/2008 A peer cop health operation can be performed only on Modbus Plus networks. Register Meaning CONTROL[1] 9 = peer cop health CONTROL[2] indicates the error status. CONTROL[3] Number of words wanted by the peer cop table (1...12) CONTROL[4] First word to be read from the peer cop table, where 0 = the first word and 11 = the last word) CONTROL[5] Routing address 1 If this is the second of two local nodes, set the value in the high byte to 1. 177