Hot Standby
Power Up and
Ethernet
Services
The following table shows how the status of an NOE service is affected by the
Modicon Quantum Hot Standby with Unity HSBY state.
HSBY State
Unassigned
318
Status of NOE Services
Client Services
Client/Server
Services
Server Services
I/O Scanner Global Data
Modbus
Messaging
FTP
SNMP
HTTP
Run
Run
Run
Run
Run
Run
Primary CPU Run
Run
Run
Run
Run
Run
Secondary
Stop
Stop
Run
Run
Run
Run
Offline
Stop
Stop
Run
Run
Run
Run