Download Samsung AA68-03265A-00 Specifications
Transcript
4) Connection diagram f MIM-B16(PIM) should be connected separately with outdoor units or controllers. For power distribution On/Off controller PIM BACnet Gateway BMS (BACnet) Power line R1-R2 F1-F2 R1-R2 F1-F2 Electrical substation Watt-hour meter R1-R2 F1-F2 5) Wiring (CH = Channel) R1 R2 F1 F2 R1 R2 BUILDING MANAGEMENT SYSTEM F1 F2 (1) Connecting outdoor unit directly • Maximum 16 outdoor units can be connected to each channel • Total 80 outdoor units can be connected (2) Connecting On/Off controller • Maximum 15 On/Off controller can be connected to each channel ; Note BACnet Gateway can connect outdoor unit and On/Off controller at the same time. Outdoor unit and On/Off controller can be connected to 1 communication channel at the same time. 125