Download Samsung AA68-03265A-00 Specifications

Transcript
Control Systems
9,
Building management system
1. LonWorks Gateway
MIM-B18N
12) Detail description of network variable
(1) Indoor unit/ ERV/ AHU kit object
1-4. nviFanStatus
1-8. nviOccOpMode
ƒ Description : Setting fan swing and speed
ƒ SNVT : SNVT_switch
ƒ Operation
ƒ Description : Setting cooling only mode/ heating only mode
ƒ SNVT : SNVT_switch
ƒ Operation
Value
State
Value
State
Operation
Auto
0
-
0.0
0
Unlock
-
Low
1
-
1.0
1
Cooling only
-
2.0
1
Heating only
-
Mid
2
-
High
3
-
Eco
4
-
1-9. nviCoolTempLock
ƒ Description : Setting the low temperature limit
ƒ SNVT : SNVT_switch
ƒ Operation
Turbo
5
-
Auto
Any > 5
-
Stop
-
0
Value
State
Operation
Remark
Up-Down
-
1
18~30
0
Unlock
-
18~30
1
Lock
-
1-5. nviERVMode
1-10. nviHeatTempLock
ƒ Description : ERV mode
ƒ SNVT : SNVT_count
ƒ Operation
ƒ Description :Setting the high temperature limit
ƒ SNVT : SNVT_switch
ƒ Operation
Value
Operation
Remark
0
Auto
Auto ventilation mode
1
H/R
Heat exchange ventilation mode
2
Air purification
Air purification mode
3
Sleep
Sleep mode
4
Normal
By-pass mode
Value
State
Operation
Remark
16~30
0
Unlock
-
16~30
1
Lock
-
2-1. nvoSpaceTemp
ƒ Description : Display indoor temperature
ƒ SNVT : SNVT_temp_p
ƒ Operation : -10ºC ~ 50ºC
1-6. nviFilterReset
2-2. nvoApplicMode
ƒ Description : Filter reset command
ƒ SNVT : SNVT_switch
ƒ Operation
Remark
ƒ Description : Display operating mode
ƒ SNVT : SNVT_hvac_mode
ƒ Operation
Value
State
Operation
0.0
0
No Alarm
-
Hvac_t
Operation
Remark
100.0
1
Alarm
-
1
Heat
-
3
Cool
-
6
Off
-
9
Fan
-
14
Dry(dehumid)
0
Auto
Review needed (VOC on
deleting Auto mode)
1-7. nviUserLockout
ƒ Description : Setting the restriction of remote control use
ƒ SNVT : SNVT_switch
ƒ Operation
118
Remark
Value
State
Operation
Remark
0.0
0
Unlock
-
100.0
1
Level 1
-
2-3. nvoSetpoint
100.0
2
Lock
-
ƒ Description : Display desire temperature
ƒ SNVT : SNVT_temp_p
ƒ Operation
Auto/Cool/Dry
18 ~ 30ºC
Heat
16 ~ 30ºC