ACH550 User's Manual
Code
Description
1606
LOCAL LOCK
0...8, -1...-6
Defines control for the use of the HAND mode. The HAND mode
allows drive control from the control panel.
• When LOCAL LOCK is active, the control panel cannot change to
HAND mode.
0 = NOT SEL – Disables the lock. The control panel can select HAND
and control the drive.
1 = DI1 – Defines digital input DI1 as the control for setting the local
lock.
• Activating the digital input locks out local control.
• De-activating the digital input enable the HAND selection.
2...6 = DI2…DI6 – Defines digital input DI2…DI6 as the control for
setting the local lock.
• See DI1 above.
7 = ON – Sets the lock. The control panel cannot select HAND, and
cannot control the drive.
8 = COMM – Defines bit 14 of the Command Word 1 as the control for
setting the local lock.
• The Command Word is supplied through fieldbus communication.
• The Command Word is 0301.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the control for
setting the local lock.
• De-activating the digital input locks out local control.
• Activating the digital input enable the HAND selection.
-2...-6 = DI2(INV)...DI6(INV) – Defines an inverted digital input DI2…DI6
as the control for setting the local lock.
• See DI1(INV) above.
1607
PARAM. SAVE
0=DONE, 1=SAVE
Saves all altered parameters to permanent memory.
• Parameters altered through a fieldbus are not automatically saved
to permanent memory. To save, you must use this parameter.
• If 1602 PARAMETER LOCK = 2 (NOT SAVED), parameters altered from
the control panel are not saved. To save, you must use this
parameter.
• If 1602 PARAMETER LOCK = 1 (OPEN), parameters altered from the
control panel are stored immediately to permanent memory.
0 = DONE – Value changes automatically when all parameters are
saved.
1 = SAVE – Saves altered parameters to permanent memory.
Parameter listing and descriptions
Range
209