Download Daikin RQYQ8-48PY1B Specifications
Transcript
Detailed Control Functions SiBE341027 2.4.5 Electronic Expansion Valve PI Control Main electronic expansion valve control When the outdoor unit heat exchanger is performed via the evaporator, this function is used to exert PI control on the electronic expansion valve (Y1E) so that the evaporator outlet superheated degree (SH) will become constant. SH = Tg - Te SH: Evaporator outlet superheated degree (°C) Tg : Suction pipe temperature (°C) detected by the thermistor R8T. Te : Low pressure equivalent saturation temperature (°C) Subcooling electronic expansion valve control In order to make the maximum use of the subcooling heat exchanger, this function is used to exert PI control on the electronic expansion valve (Y2E or Y3E) so that the evaporator-side gas pipe superheated degree (SH) will become constant. SH = Tsh - Te SH: Evaporator outlet superheated degree (°C) Tsh: Suction pipe temperature (°C) detected by the subcooling heat exchanger outlet thermistor R5T. Te: Low pressure equivalent saturation temperature (°C) 2.4.6 Step Control of Outdoor Unit Fans Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition changes. STEP No. 0 Fan revolutions (rpm) RQYQ14PY1B RQYQ8PY1B RQYQ10PY1B RQYQ12PY1B MF1 MF2 0 0 0 0 0 RQYQ16PY1B MF1 0 MF2 0 1 2 350 370 350 370 350 370 230 380 0 0 230 380 230 380 3 4 400 450 400 460 400 460 290 375 260 345 290 375 290 375 5 6 540 610 560 710 560 710 570 720 540 690 570 720 570 720 7 760 870 1091 1061 1091 980 8 Cooling: 796 Heating: 780 Cooling: 821 Heating: 800 Cooling: 821 Heating: 800 870 1136 1106 1136 980 * Figures listed above are all those controlled while in standard mode, which vary when the system is set to high static pressure or capacity precedence mode. [Control at a low outdoor temperature during cooling] Secure the liquid pressure and circulating rate in the indoor unit through high pressure control with the outdoor fan when the outdoor temperature is low during cooling. Control the fan with the target Tc (high pressure equivalent saturation temperature) = 34°C 50 Function