Download Danfoss C67 User`s guide
Transcript
30b ECL Card settings (circuit II) A Time and date Section 17 B System information Sections 18 & 19 C Heat curve Setting ranges Section 20 Factory settings Your settings Slope 0.2 ... 3.4 0.6 See section 20 Parallel displacement -9 ... 9 K 0K See section 20 1 Limit for heating cut-out 10 ... 30 °C 20 °C See section 21 2 10 ... 150 °C min. 10, max. 50 °C See section 22 3 Room temperature influence 0 ... 99 / -99 ... 0 min. 0, max. -40 See section 23 4 Proportional band, Xp 1 ... 250 K 80 K See section 26 5 Integration time constant, Tn 5 ... 999 sec. 30 sec. See section 26 6 Running time of the motorized control valve 5 ... 250 sec. 35 sec. See section 26 7 Neutral zone, Nz 0 ... 9 K See section 26 3K Control & overviews Flow temperature, min. / max. limits