Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
F. Start-Up Failures: This is an alarm condition. A manual reset is required to clear.
Primary
Message
Secondary
Message
Alarm Message/Primary
Cause
Additional Cause/Remedy
Failure To
Start
Low Oil Pressure
OILPD [VALUE] exceeded limit
of [LIMIT]*. Check oil pump system.
Check for closed oil supply valves.
Check oil filter. Check for low oil temperature. Check transducer accuracy.
Oil Press Sensor
Fault
OILPD [VALUE] exceeded limit
of [LIMIT]*. Check oil pressure
sensor.
Check for excessive refrigerant in oil
sump. Run oil pump manually for 5 minutes. For hermetic compressors, check
both oil pressure and cooler pressure.
For open-drive units, check calibration
of oil pressure differential amplifier
modules. Check wiring. Replace transducers if necessary.
Failure To
Start
Low Chilled
Water Flow
EVFL Evap Flow Fault: Check
water pump/flow switch.
Check wiring to flow switch. Check
through Control Test for proper switch
operation.
Failure To
Start
Low Condenser
Water Flow
CDFL Cond. Flow Fault: Check
water pump/flow switch.
Check wiring to flow switch. Check
through Control Test for proper switch
operation.
Failure To
Start
Starter Fault
STR FLT Starter Fault: Check
starter for Fault Source.
A starter protective device has faulted.
Check starter for ground fault, voltage
trip, temperature trip, etc.
Failure To
Start
Starter Overload
Trip
STR FLT Starter Overload Trip:
Check amps calibration/reset
overload.
Reset overloads, check ICR relay
before restarting machine.
Line Voltage
Dropout
V P Single-Cycle Dropout
Detected: Check voltage supply.
Check voltage supply. Check transformers for supply. Check with utility if
voltage supply is erratic. Monitor must
be installed to confirm consistent,
single-cycle dropouts. Check low oil
pressure switch.
High Condenser
Pressure
High Condenser Pressure
[LIMIT]:* Check switch 2C aux,
and water temperature/flow.
Check for proper design condenser flow
and temperature. Check condenser
approach. Check 2C auxiliary contacts
on oil sump starter. Check high pressure switch.
Excess Acceleration Time
CA P Excess Acceleration:
Check guide vane closure at
start-up.
Check that guide vanes are closed at
start-up. Check starter for proper operation. Reduce unit pressure if possible.
Failure To
Start
Failure To
Start
Failure To
Start
Failure To
Start