Download CPS SCA23KTL-DO Technical data
Transcript
install an individual miniature circuit-breaker between the dry contact and the power distribution grid. Dry contact communication cable connection: a.) Knock out the holes for suitable cable conduits of 3/4 inch. b.) Put the dry contact communication cable through the cable conduit and inside the wiring box. c.) Use double-layer insulated cables. Strip the cables according to the following requirements. Tool: Wire stripping pliers D A L2 L1 Figure 3-32 Wire stripping Table 3-11 Cable set-up Position Description Value Cable type Double-layer insulated cable D Outer diameter 4.5 mm~ 6 mm A Cross-section area of conductor 0.2 mm²~ 0.75 mm² L1 Length of stripped outer wire skin Maximum 15mm L2 Length of stripped inner wire skin Maximum 7 mm 37