DE~ATlON
OF OVERALL HEAT TRANSFER BETWEEN R141b AND WATER
IN mE EV APORA TOR AND CONDENSER
The Overall Heat TransferCoefficient (U) is die heatttansferrateper unit areaof heatttansfersurface
when a temperaturedifferenceof ooe degreeexists betweendie hot and cold fluids.
In die evaporator,die refrigeranttemperatureis sensiblyconstant,but die water temperaturefalls as it
passesthrough the coils. In die condensersomedegreeof superheating~
be presentwhen the gas
entersthe condenserglasschamber. However the quantity of heat delivered due to the superheating
will be small relative to that attributableto the condensingphasechange. Examination of the high
pressureline of the cycle diagramgeneratedin ExperimentNo.9 on Page47 will confirm this.
In oroor to analysethe overall heatb'aIlSfercoefficient a representativetemperaturedifferencemust be
determinedthat representsthe driving force for heat transferbetweenthe refrigerant and the water.
The temperaturedifferenceto be usedin this caseis the "Logarithmic Mean" which is given by
where9... = Temperawre
differencebetweendie two fluids at inlet,
9..-1ot
= Temperature
differencebetweendie two fluidsat outlet.
and
A dleoreticalanalysisof dle logarithmic meantemperatmedifferencemay be found in mosttext books
on heat transferand will not dlereforebe expandedin dlis manual.
Once air free increasedie condensercooling water flow to a mid range value. The pressureat
which the condenserstabiliseswill dependupon the water inlet temperature.
(ii)
Set the evaporatorwater flow to a mid range value and allow the unit to run for approximately
15-20minutes. The time takento stabilisewill dependupon the local ambientconditionsand the
cooling water inlet temperature.
(ill) Record allllie systemparametersas illustrated in the table on Page44.