Download Chloride LPBP610-2 Specifications
Transcript
Planning for Communications and Data Cables NOTE A dedicated phone line provides the most reliable service. RSN calls routed through a PBX might be slow due to the load on the PBX, or might not complete successfully because the calls can become disconnected. If you must use a PBX, do not route the telephone extension through a switchboard; instead, provide a direct-dial analog number. Table 4-1 describes component location considerations due to standard cable lengths. Table 4-1. Cable Length and Component Location Considerations Cable Length Component 1 Component 2 Consideration Due to Shortest Cable PC console ftServer V 100, V 200, or V 400 system Locate the system console less than 25 ft. away from the host due to the length of the null modem cable (B20253-25) provided by Stratus. 25 ft. (7.62m) RSN console server (Internet or dialup) ftServer V 100, V 200, or V 400 system Locate the RSN console server less than 20 ft. away from the host due to the length of the Ethernet cable (B000919-20 or B000925-20) provided by Stratus. 20 ft. (6.10m) RSN modem (if present) AA-E96600 RSN dialup console server Locate the RSN modem less than 10 ft. away from the RSN console server due to the length of the full modem cable (B10102-10) provided by Stratus. 10 ft. (3.05m) UPS units ftServer V 100, V 200, or V 400 system Locate each UPS unit less than 12 ft. away from the PDUs in the host due to the length of each PDU AC input cord provided by Stratus. 12 ft. (3.65m) 4-6 Stratus ftServer V 100, V 200, and V 400 Systems: Site Planning Guide (R543)