Download Cognex finger kg Technical data
Transcript
I/O Modules Process Data Architecture for MODBUS/TCP • 145 750-634 The above Incremental Encoder Interface module has 5 bytes of input data (6 bytes in cycle duration measurement mode) and 3 bytes of output data. The following tables illustrate the Input and Output Process Image, which has 4 words mapped into each image. Word alignment is applied. Input Process Image Offset Byte Destination High Byte Low Byte 0 - S 1 D1 D0 2 - (D2)*) 3 D4 D3 Remark not used Status byte Counter word not used (Periodic time) Latch word ) * If cycle duration measurement mode is enabled in the control byte, the cycle duration is given as a 24-bit value that is stored in D2 together with D3/D4. Output Process Image Offset Byte Destination High Byte Low Byte 0 - C 1 D1 D0 2 - - 3 - - Remark not used Control byte Counter Setting word not used 750-637 The above Incremental Encoder Interface Module has a total of 6 bytes of user data in both the Input and Output Process Image (4 bytes of encoder data and 2 bytes of control/status). The following table illustrates the Input and Output Process Image, which have 4 words mapped into each image. Word alignment is applied. Input and Output Process Image Offset WAGO-I/O-SYSTEM 750 ETHERNET TCP/IP Byte Destination Remark High Byte Low Byte 0 - C0/S0 Control/Status byte of Channel 1 1 D1 D0 Data Value of Channel 1 2 - C1/S1 Control/Status byte of Channel 2 3 D3 D2 Data Value of Channel 2