Download WarmFlow COMBI 70 Technical data
Transcript
6.5 Remote Timers for Combis 6.5.1 Installation of a remote two channel programmer (option 1) Permanent Live Supply The boiler must be supplied with a permanent live mains supply via a fused isolator connected to the boiler 3 pin mains plug into the control panel. Failure to connect a permanent live to the boiler will prevent the programmer, boiler mains lamp and pump overrun thermostat from operating. It will also disable the built-in frost protection of a Kabin Pak Combi. Connecting the Programmer Inside the boiler control panel, remove the purple, white and brown wires connecting the CH and HW switches to the 6 pin connector of the terminal block. Connect the programmer to the 6 pin connector via a 5 core cable as shown ensuring the earth is connected to one of the earth posts inside the control panel. On Kabin Pak models, ensure the frost thermostat connections to pins 3 and 6 are left in place. Connecting the programmer in this manner will bypass the CH and HW on/off switches on the boiler control panel. The boiler and programmer will both be powered from the boiler 3 pin mains plug, so only one mains connection is required. The neutral connection to the 3-pin plug on the control panel must be the sole mains neutral connection to the appliance. Page 42