Download Siemens SIMATIC PC Adapter TS Adapter Specifications
Transcript
Specifications 9.8 Standards, Approvals, Certificates, Guidelines, Labels and Declarations FM approval Factory Mutual Approval Standard Class Number 3611, Class I, Division 2, Group A, B, C, D, T4A. Class I, Zone 2, Group II C, T4. WARNING Injury to persons or damage to property may occur. In potentially explosive atmospheres there is a risk of injury to persons or damage to property if you connect or disconnect a live electrical circuit (such as connectors, fuses, switches) when a TS Adapter IE is in operation. Do not disconnect live circuits, except where the risk of explosion can be safely excluded. For use under FM conditions, the TS Adapter IE must be installed in a cubicle with minimum IP54 protection to IEC 60529. Safety requirements for mounting The TS Adapter IE is "open equipment" in accordance with the IEC 61131-2 standard, and an "open type" in accordance with UL / CSA certification. The alternative installation methods described below are stipulated in order to ensure safe operation with respect to mechanical strength, flame resistance, stability and touch protection: ● Installation in a suitable cabinet ● Installation in a suitable cubicle ● Installation in an appropriately equipped closed switchroom. Compliance with installation guidelines The installation guidelines and safety instructions set out in this manual must be observed during commissioning and operation. Connecting peripherals Interference immunity requirements are met when connected to an industrial standard PC/modem in accordance with EN61000-6-2:2005. 94 TS Adapter IE Manual, 06/2008, A5E00977705-02