Grid management 4.2 Static grid support 3. Frequency derating with hysteresis and without start frequency Figure 4-8 Active power control according to frequency P=f(f) with hysteresis and start frequency Contrary to active power control according to frequency P=f(f) with hysteresis and start frequency, the second limit frequency f2 is not required. The inverter generally no longer follows the curve in the case of frequency derating, and instead remains at the minimum calculated output power P (determined via the curve) until the final frequency for resuming normal operation f3 (parameterizable) has been undershot. Only one mode is parameterized for frequency-dependent active power reduction. You set all parameters here, regardless of which mode is used. Parameterization of a minimum holding power A minimum holding power can be parameterized additionally for modes 1 and 3. Some Grid Codes demand this. If this function is activated, the inverter will not reduce the output power below the parameterized holding power. If the frequency f nevertheless continues to rise, the inverter will be switched off when the frequency point fH is reached. Note The functions can be deactivated if required. PVS 600Series 42 Operating Instructions, 08/2014, A5E03467293-003