Commissioning
6.2 Commissioning on PROFIBUS DP
6.2.2
Commissioning and startup of ET 200S on PROFIBUS DP
6.2.2.1
Setting the PROFIBUS Address
Introduction
The PROFIBUS address is used to specify the address of the ET 200S distributed I/O
system on PROFIBUS DP.
● The PROFIBUS DP address for the ET 200S is set on the interface module or COMPACT
module by means of DIP switches. The DIP switches are to be found on the front of the
interface module, protected by a sliding window.
● Valid PROFIBUS DP addresses are 1 to 125.
● Each address can be assigned only once on PROFIBUS DP.
Requirements
Address setting is not yet assigned on PROFIBUS DP.
Required tools
3-mm screwdriver
ET 200S
Operating Instructions, 08/2008, A5E00515771-06