Wiring and assembly
5.4 Wiring the ET 200S
4. Strip the insulation from the ground wire (from 6 mm to 25 mm2), and insert it in the
ground connection terminal (under the conductor rail). Tighten the ground connection
terminal (2 Nm to 2.5 Nm).
5. Attach the other end to the ground bus.
1
5
2
4
①
Shield terminal
②
Insulation material removed
③
Cable to the encoder
④
Cable to the ground bus
3
⑤
Ground connection terminal
Figure 5-7
Connecting cable shields
Note
To stabilize the shield connection, you must mount and screw in at least one shield
terminal above the shield connection element.
86
ET 200S
Operating Instructions, 08/2008, A5E00515771-06