Download Siemens ET 77..UC Operating instructions

Transcript
Digital electronic modules
12.5 Parameters of the digital electronic modules
8 DI NAMUR parameters, "8 DI NAMUR" configuration
Table 12- 17 Parameters for "8 DI NAMUR"
Parameters
Range of values
Default
Applicability


enabled
disabled
disabled
Channel
Edge evaluation event
entering state1


rising edge (0-->1)
falling edge (1-->0)
rising edge (0-->1)
Channel
Encoder type



Channel disabled
NAMUR sensor
Single contact, no load
resistance
Single contact, connected
with 10 kΩ
NAMUR changeover
contact
Changeover contact,
unconnected
Changeover contact,
connected with 10 kΩ
NAMUR sensor
Channel
Time
stamping1




Pulse stretching




None
0.5 s
1s
2s
None
Channel
Group diagnostics


enabled
disabled
enabled
Channel
Diagnostics: wire break


enabled
disabled
enabled
Channel
Diagnostics: wire break


enabled
disabled
enabled
Channel
Diagnostics for chatter error


enabled
disabled
disabled
Channel
External error
(changeover contact error or
faulty encoder supply)


enabled
disabled
disabled
Channel
Chatter monitoring:
Monitoring window 2


0.5 s
1 s to 100 s (can be set in
1 s increments)
2s
Channel
Chatter monitoring: Number
of signal changeovers2
2 to 31
5
Channel
1
Can only be assigned in HW Config and if the ET 200iSP is being operated as an S7 DP slave.
2
Parameter cannot be set unless chatter error diagnostics is enabled.
ET 200iSP
Operating Instructions, 01/2010, A5E00247483-04
261