ARI* capacity ratings
ARI CAPACITIES IN-CEILING CASSETTE APPLICATIONS
40QKB IN-CEILING CASSETTES WITH 38HDC,HDL UNITS
INDOOR SECTION
OUTDOOR SECTION
38HDC018
38HDL018
38HDL030
38HDL036
38HDC024
38HDL024
38HDC030
38HDC036
40QKB024
40QKB036
STD CFM
525
525
915
915
915
915
915
915
COOLING (Btuh)
18,300
17,800
29,000
34,400
24,000
24,000
30,000
33,000
TOTAL kW
1.76
1.68
2.87
3.45
2.2
2.12
3.13
3.14
SEER
11
11.4
11.1
10.5
11
11.8
10.8
10.8
EER
10.4
10.8
10.4
9.9
10.9
11.3
9.6
10.5
40QKB IN-CEILING CASSETTES WITH 38HDS UNIT
INDOOR SECTION
40QKB024
OUTDOOR SECTION
38HDS024-3
STD CFM
24,000
COOLING (Btuh)
1,000
SEER
12.0
EER
11.3
CHARGE (lb)
4.1
HEATING kW
2.22
40QKE IN-CEILING CASSETTES WITH 38QR UNITS
INDOOR
SECTION
40QKE024
40QKE036
40QKE048
OUTDOOR
SECTION
38QR018C
38QR024C
38QR030C
38QR036C
STD
CFM
525
980
980
1100
COOLING
(Btuh)
18,000
25,000
29,000
33,000
TOTAL
kW
2
2.44
2.61
3.47
SEER
EER
10
10.7
11.5
10.5
9
10.2
11.1
9.5
HEATING
HIGH (Btuh)
17,600
23,800
27,000
33,000
HEATING
HIGH (COP)
3.04
3.34
3.27
3.3
HEATING
HIGH (HSPF)
6.8
7.6
7.6
6.8
HEATING
LOW (Btuh)
11,000
13,400
15,900
20,000
HEATING
LOW (COP)
2
2.3
2.3
2.2
40QKE IN-CEILING CASSETTES WITH 38HDC,HDL,HDS UNITS
INDOOR SECTION
40QKE024
40QKE024
40QKE036
40QKE048
ARI
COP
db
HSPF
wb
—
—
—
—
—
OUTDOOR SECTION
38HDC018-3
38HDL018-3
38HDS024-3
38HDC024-3
38HDL024-3
38HDC030-3
38HDL030-3
38HDC036-3,5,6
38HDL036-3
STD CFM
525
525
525
980
980
980
980
1100
1100
COOLING (Btuh)
17,800
17,800
23,000
23,800
24,000
29,800
29,000
33,800
34,800
LEGEND
Air Conditioning & Refrigeration Institute
Coefficient of Performance
Dry Bulb
Heating Seasonal Performance Factor
Wet Bulb
* 3-phase unit.
NOTES:
1. Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
SEER
10.5
11.2
12.0
11.5
11.0
12.0
10.9
11.5
10.3
EER
10.1
10.6
10.8
8.3
11.3
10.4
10.1
9.7
10.0
CHARGE (lb)
5.8*
3.9
4.1
4.8
4.6
5.2
5.6
5.8
6.0
HEATING kW
1.8
1.8
2.0
2.7
2.7
2.7
2.7
2.7
2.7
Cooling Standard: 80 deg F db, 67 deg F wb air entering evaporator and
95 deg F db air entering condenser.
High Temperature Heating Standard: 70 deg F db air entering evaporator and
47 deg F db, 43 F wb air entering condenser.
Low Temperature Heating Standard: 70 deg F db air entering evaporator and
17 deg F db, 15 F wb air entering condenser.
2. Total kW is for total system, including compressor and outdoor and indoor fan
motors.
3. Ratings are based on 25 ft of interconnecting refrigerant lines.
4. All system ratings are based on fan coil units operating at high fan speed.
Consult Physical Data tables for airflows at all available fan speeds.
Sound ratings
SOUND DATA (A Weighted)
UNIT
40QKB024
40QKB036
40QKE024
40QKE036
40QKE048
SOUND PRESSURE
(dBa)
FAN SPEED
SOUND POWER
(dBa)
45.3
39.9
38.8
43.8
37.2
29.9
45.3
—
—
43.8
37.2
29.9
48.1
42.9
—
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
High
Medium
Low
56.3
50.9
49.8
54.8
48.2
40.9
56.3
—
—
54.8
48.2
40.9
59.1
53.9
—
LEGEND
ARI — Air Conditioning and Refrigeration Institute
dBa — Decibels on the A Scale
125
32.1
42.0
40.9
45.0
35.5
31.2
32.1
—
—
45.0
35.5
31.2
40.2
45.0
—
SOUND POWER DATA OCTAVE BAND (dBa)
250
500
1000
2000
4000
45.0
51.2
54.1
46.5
45.0
44.1
48.0
47.5
42.2
37.3
43.0
46.9
46.4
41.1
36.2
45.8
50.9
51.8
47.4
38.8
40.2
46.1
45.2
39.0
29.9
37.8
40.3
37.0
26.5
24.5
45.0
51.2
54.1
46.5
45.0
—
—
—
—
—
—
—
—
—
—
45.8
50.9
51.8
47.4
38.8
40.2
46.1
45.2
39.0
29.9
37.8
40.3
37.0
26.5
24.5
45.8
54.8
56.0
51.5
47.7
47.1
51.0
50.5
45.2
40.3
—
—
—
—
—
8000
36.5
36.8
35.7
32.9
28.7
27.3
36.5
—
—
32.9
28.7
27.3
39.8
39.8
—
NOTES:
1. Sound power levels are tone corrected values taken in accordance with ARI
Sound Standard 350.
2. Sound pressure data is measured 1 m away from the unit.
3