Download Carrier 38HDL024 Product data
Transcript
ARI* capacity ratings ARI CAPACITIES IN-CEILING CASSETTE APPLICATIONS 40QKB IN-CEILING CASSETTES WITH 38HDC,HDL UNITS INDOOR SECTION OUTDOOR SECTION 38HDC018 38HDL018 38HDL030 38HDL036 38HDC024 38HDL024 38HDC030 38HDC036 40QKB024 40QKB036 STD CFM 525 525 915 915 915 915 915 915 COOLING (Btuh) 18,300 17,800 29,000 34,400 24,000 24,000 30,000 33,000 TOTAL kW 1.76 1.68 2.87 3.45 2.2 2.12 3.13 3.14 SEER 11 11.4 11.1 10.5 11 11.8 10.8 10.8 EER 10.4 10.8 10.4 9.9 10.9 11.3 9.6 10.5 40QKB IN-CEILING CASSETTES WITH 38HDS UNIT INDOOR SECTION 40QKB024 OUTDOOR SECTION 38HDS024-3 STD CFM 24,000 COOLING (Btuh) 1,000 SEER 12.0 EER 11.3 CHARGE (lb) 4.1 HEATING kW 2.22 40QKE IN-CEILING CASSETTES WITH 38QR UNITS INDOOR SECTION 40QKE024 40QKE036 40QKE048 OUTDOOR SECTION 38QR018C 38QR024C 38QR030C 38QR036C STD CFM 525 980 980 1100 COOLING (Btuh) 18,000 25,000 29,000 33,000 TOTAL kW 2 2.44 2.61 3.47 SEER EER 10 10.7 11.5 10.5 9 10.2 11.1 9.5 HEATING HIGH (Btuh) 17,600 23,800 27,000 33,000 HEATING HIGH (COP) 3.04 3.34 3.27 3.3 HEATING HIGH (HSPF) 6.8 7.6 7.6 6.8 HEATING LOW (Btuh) 11,000 13,400 15,900 20,000 HEATING LOW (COP) 2 2.3 2.3 2.2 40QKE IN-CEILING CASSETTES WITH 38HDC,HDL,HDS UNITS INDOOR SECTION 40QKE024 40QKE024 40QKE036 40QKE048 ARI COP db HSPF wb — — — — — OUTDOOR SECTION 38HDC018-3 38HDL018-3 38HDS024-3 38HDC024-3 38HDL024-3 38HDC030-3 38HDL030-3 38HDC036-3,5,6 38HDL036-3 STD CFM 525 525 525 980 980 980 980 1100 1100 COOLING (Btuh) 17,800 17,800 23,000 23,800 24,000 29,800 29,000 33,800 34,800 LEGEND Air Conditioning & Refrigeration Institute Coefficient of Performance Dry Bulb Heating Seasonal Performance Factor Wet Bulb * 3-phase unit. NOTES: 1. Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: SEER 10.5 11.2 12.0 11.5 11.0 12.0 10.9 11.5 10.3 EER 10.1 10.6 10.8 8.3 11.3 10.4 10.1 9.7 10.0 CHARGE (lb) 5.8* 3.9 4.1 4.8 4.6 5.2 5.6 5.8 6.0 HEATING kW 1.8 1.8 2.0 2.7 2.7 2.7 2.7 2.7 2.7 Cooling Standard: 80 deg F db, 67 deg F wb air entering evaporator and 95 deg F db air entering condenser. High Temperature Heating Standard: 70 deg F db air entering evaporator and 47 deg F db, 43 F wb air entering condenser. Low Temperature Heating Standard: 70 deg F db air entering evaporator and 17 deg F db, 15 F wb air entering condenser. 2. Total kW is for total system, including compressor and outdoor and indoor fan motors. 3. Ratings are based on 25 ft of interconnecting refrigerant lines. 4. All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data tables for airflows at all available fan speeds. Sound ratings SOUND DATA (A Weighted) UNIT 40QKB024 40QKB036 40QKE024 40QKE036 40QKE048 SOUND PRESSURE (dBa) FAN SPEED SOUND POWER (dBa) 45.3 39.9 38.8 43.8 37.2 29.9 45.3 — — 43.8 37.2 29.9 48.1 42.9 — High Medium Low High Medium Low High Medium Low High Medium Low High Medium Low 56.3 50.9 49.8 54.8 48.2 40.9 56.3 — — 54.8 48.2 40.9 59.1 53.9 — LEGEND ARI — Air Conditioning and Refrigeration Institute dBa — Decibels on the A Scale 125 32.1 42.0 40.9 45.0 35.5 31.2 32.1 — — 45.0 35.5 31.2 40.2 45.0 — SOUND POWER DATA OCTAVE BAND (dBa) 250 500 1000 2000 4000 45.0 51.2 54.1 46.5 45.0 44.1 48.0 47.5 42.2 37.3 43.0 46.9 46.4 41.1 36.2 45.8 50.9 51.8 47.4 38.8 40.2 46.1 45.2 39.0 29.9 37.8 40.3 37.0 26.5 24.5 45.0 51.2 54.1 46.5 45.0 — — — — — — — — — — 45.8 50.9 51.8 47.4 38.8 40.2 46.1 45.2 39.0 29.9 37.8 40.3 37.0 26.5 24.5 45.8 54.8 56.0 51.5 47.7 47.1 51.0 50.5 45.2 40.3 — — — — — 8000 36.5 36.8 35.7 32.9 28.7 27.3 36.5 — — 32.9 28.7 27.3 39.8 39.8 — NOTES: 1. Sound power levels are tone corrected values taken in accordance with ARI Sound Standard 350. 2. Sound pressure data is measured 1 m away from the unit. 3