Download Viessmann WB2B Technical data
Transcript
Control Technology Outdoor Reset Programming Unit (continued) Connecting the boiler control to a LON system Vitocom LON Communication Module (accessory) must be connected. Installation Instructions LON Communication Module Note: Data transfer via LON can take several minutes. Single-boiler system with Vitotronic 200-H, HK1M and Vitotronic 200-H, HK1S mixing valve controls and Vitocom LON communication module Set up the LON participant numbers and other functions via coding level 2 (see table below). Note: In the same LON system, a number cannot be allocated twice. Only one Vitotronic may be programmed as fault manager. Boiler Control Unit 5418 911 v1.6 LON Vitotronic 200-H (e.g. HK1M mixing valve control) Vitotronic 200-H (e.g. HK1S *1 multiple mixing valve control) Vitocom *1 LON communication module LON LON Participant no.1 Code ”77:1” Participant no.10 Code ”77:10” Participant no.11 Code ”77:11” Participant no.99 Control unit is fault manager Code ”79:1” Control unit is not fault manager Code ”79:0” Control unit is not fault manager Code ”79:0” Device is fault manager Control unit transmits the time Code ”7b:1” Control unit receives the time Set code ”81:3” Control unit receives the time Set code ”81:3” Device receives the time Control unit transmits outdoor temperature Set code ”97:2” Control unit receives outdoor temperature Set code ”97:1” Control unit receives outdoor temperature Set code ”97:1” -- LON participant fault monitoring Code ”9C:20” LON participant fault monitoring Code ”9C:20” LON participant fault monitoring Code ”9C:20” -- *1 Refer to separate Installation Instructions of accessories. 33