14 | Sequence of Operation
SM CS Series Heat Pump
UPM Sequence of Operation (SOO) Flow Chart
Y1=1
NO
YES
Power/Switchs/Sensor
Status Check
V > 18VAC
NO
Lockout Can Be Set To
4 Via Dip Switch
YES
HPC = 1
Blink Code On Status LED
Soft Lockout
Record Alarm
Start Counter (If Applicable)
NO
COUNT = 2
YES
NO
YES
YES
LPC = 1
Start Timer
NO
NO
YES
FRZ > TEMP
LIM
NO
Start Timer
TIME > 30
SEC
YES
CC Output = Off
NO
YES
CON > 0
TIME > 120
SEC
Blink Code On Status LED
Report Alarm Fault
Hard Lockout
ALR Output = On/Pulse
NO
YES
INITIAL NO
POWER UP
YES
Start
Anti Short Cycle
Start
Random Start Up
NO
T > ASC OR
RS SEC
YES
CC Output = On
LEGEND:
HPC - HIGH PRESSURE CUTOUT
LPC - LOW PRESSURE CUTOUT
FRZ - FREEZE PROTECTION CONDITION
CON - CONDENSATE OVERFLOW CONDITION
CC - COMPRESSOR COIL
ASC - ANTI SHORT CYCLE
RS - RANDDOM START
Figure # 11
8 733 920 846 (2013/11)
Subject to change without prior notice
SM CS Series Heat Pump