Download Viessmann SCU224 Technical data
Transcript
SCU224 Maximum temperature limitation MX3O / MX3F: Maximum temperature limitation Adjustment range: 30.0 ... 200.0 °F [0.0 ... 95.0 °C] in steps of 1 °Ra [0.5 K] Factory setting: MX3O: 140.0 °F [60.0 °C] MX3F: 136.0 °F [58.0 °C] Minimum temperature limitation MN3O / MN3F: Minimum temperature limitation Adjustment range: 30.0 ...190.0 °F [0.0 ... 90.0 °C] in steps of 1 °Ra [0.5 K] Factory setting (Arr = 2 only): MN3O: 40.0 °F [5.0 °C] MN3F: 50.0 °F [10.0 °C] Minimum and maximum temperature limits can be set for the heat exchange function. The maximum temperature limitation uses sensor 4 as reference sensor. The maximum temperature limitation function provides a maximum temperature setting, usually to reduce scald risk in a storage tank. If MX3O is exceeded, relay 2 is switched off until the temperature at sensor 4 falls below MX3F. The minimum temperature limitation uses sensor 3 as reference sensor. The minimum temperature limitation function provides a minimum temperature setting for the heat source in system layout 2. If the temperature at sensor 3 falls below MN3O, relay 2 is switched off until the temperature at sensor 3 exceeds MN3F. © Viessmann 5443203 Both switch-on and switch-off temperature differences DT3O and DT3F are valid for the maximum and minimum temperature limitation. 11 |