SCU224 5.1Various: Pump is overheated, but no heat is being transferred from collector to the tank, feed flow and return flow are equally warm, possibly also bubble in the tubes Pump starts for a short moment, switches-on/off repeatedly Air in the system? Is the temperature difference at the controller too small? no yes Exhaust the system; increase system pressure to the minimum pressures listed in the Vitosol Startup and service manual. Switch the pump on and off for a short time Is the collector circuit blocked at the dirt trap? no Wrong placing of the collector sensor? no yes Clean the dirt trap yes yes Activate option tube collector special function Change ∆T on and ∆T off accordingly. no o.k. Mount the collector sensor at solar feed flow (warmest collector output); use the sensor well of the respective collector. Pump starts up very late and stops working soon. The temperature difference between tank and collector increases enormously during operation; the collector circuit cannot dissipate the heat. Switch-on-temperature difference ∆Ton too large? Collector circuit pump defect ? no yes no Change ∆T on and ∆Toff accordingly. Repair / Replace Heat exchanger calcified? Collector sensor unfavour able placed (e.g. contact sensor instead of sensor well. yes yes no yes Decalification If necessary activate tube collector function. o.k. Heat exchanger plugged? no yes Heat exchanger too small? yes New calculation of the dimension. | 22 © 08284 SCU224.monus.indd Cleaning