Download York Heat Pump YCAL0014SC

Transcript
Unit Controls
RETURN CHILLED LIQUID CONTROL
(DUAL SYSTEM 4 AND 6 COMP UNITS ONLY)
Return chilled liquid control is based on staging the compressors to match the cooling load. The chiller will be
fully loaded when the return water temperature is equal
to the Cooling Setpoint plus the Range Setpoint. The
chiller will be totally unloaded (all compressors off) when
the return water temperature is equal to the Cooling
Setpoint. At return water temperatures between the
Cooling Setpoint, and Cooling Setpoint plus Range
Setpoint, compressor loading and unloading will be determined by the formulas in Table 37 or Table 38.
determining the separation between segments. Note
also that the Cooling Setpoint is the point at which all
compressors are off, and Cooling Setpoint plus Range
Setpoint is the point all compressors are on. Specifically, if the return water temperature is 55°F (12.8°C),
then all compressors will be on, providing full capacity.
At nominal gpm, this would provide approximately 45°F
(7.2°C) leaving water temperature out of the evaporator.
Normal loading will occur at intervals of 60 seconds according to the temperatures determined by the formulas. Unloading will occur at a rate of 30 seconds according the temperatures determined in the formulas.
If the return water temperature drops to 53.3°F (11.8°C),
one compressor would cycle off leaving five compressors running. The compressors would continue to cycle
off approximately every 1.7°F (.94°C), with the exception of hot gas bypass. Notice that the hot gas bypass
would be available when the return water temperature
dropped to 46.25°F (7.9°C). At this point one compressor would be running.
The return chilled liquid setpoint is programmable from
40°F to 70°F (4.4°C to 21.1°C) in water chilling mode
and from 10°F to 70°F (-12.2°C to 21.1°C) in glycol chilling mode. In both modes, the cooling range can be from
4°F to 20°F (2.2° to 11.1°C).
Should the return water temperature rise from this point
to 46.7°F (8.2°C), the hot gas bypass would shut off,
still leaving one compressor running. As the load increased, the compressors would stage on every 1.7°F
(.94°C).
As an example of compressor staging (refer to Table
36 and Table 37), a chiller with six compressors using a
Cooling Setpoint programmed for 45°F (7.20°C) and a
Range Setpoint of 10°F (5.56°C). Using the formulas in
Table 37, the control range will be split up into six (seven
including hot gas) segments, with the Control Range
Also notice that Tables 37 and 38 not only provide the
formulas for the loading (ON POINT) and unloading
(OFF POINT) of the system, the “STEP” is also shown
in the tables. The “STEP” is that sequence in the capacity control scheme that can be viewed under the
OPER DATA key. Please refer to the section on the DISPLAY/PRINT keys for specific information on the OPER
DATA key.
88
YORK INTERNATIONAL