Point Type 31: Linear Meter Setup
Parm
#
Name
Access
Data Type
Length
Range
Default
4
Calibration Pressure
R/W
FL
4
Any floating point
number
0.0
If the meter type is volume:
Not used.
If the meter type is mass:
Calibration pressure of the mass meter
from which the correction for the
pressure effect on the mass flow
accuracy is determined. Units are PSIG
or kPa(g).
5
Press Effect Coeff
R/W
FL
4
Any floating point
number
0.0
If the meter type is volume:
Not used.
If the meter type is mass:
Pressure effect coefficient for the mass
meter. Units are %/PSIG or %/kPa(g).
The correction for pressure effect on
mass flow accuracy requires the
pressure effect coefficient to be a
negative number as indicated in the
sensor product data sheet.
6
Accumulator TLP
R/W
TLP
3
Any valid TLP
0,0,0
Revised Aug-15
Description of functionality and meaning
of values
Accumulator Input for this program.
Configuring this parameter triggers the
Linear Meter program to read the parameter
specified by Accumulator TLP and use its
value, along with the specified rate, to
calculate accumulated totals.
NOTE: The Linear Meter Program assumes
that the accumulator is in the
correct units for the meter run in
which it is used.