Industrial Control & Instrumentation
Din rail isolator & transmitter
din20
l
l
l
din20-bas: Thermocouples, Pt100, 4..20ma, 0..10V process inputs.
din20-vac: True RMS AC/DC Volt, Amper input.
din20-tac: Tachometer 0.01 Hz.. 50KHz pulse input.
l
4 alarms associated to 2 output solid state relays.
l
l
Isolated 4/20ma and 0/10V outputs.
RS485 modbus RTU serial communications.
General description
The din20 din rail isolators are based on Arian id20 digital panel indicators, having the
same funtionalities except for not having a display and enhaced isolation characteristics. Composed by 3 sub-models (din20-bas, din20-vac, din20-tac) they cover a broad
range of input types.
Isolation
Complete galvanical isolation between: power supply, input, analog output, solid state
relays and RS485 communications.
Inputs
The din20-bas includes thermocouples, Pt100, 4...20mA, 0...10V and 0...50mV
process inputs.
The din20-vac is a AC true RMS volt and amper input instrument, (also bipolar DC)
with several scales. May be used with shunts, current transformers or direct measurement of AC/DC voltages up to 600V.
The din20-tac is a tachometer or rate meter, only accepts pulse inputs e.g.. NPN, PNP
and Mechanical Switch. Frecuency measurement is done counting the input pulses
and simultaneously measuring the time among them. This method allows precise and
quick readings especially at low frequencies where the measurement is obtained
mainly from the period (time) among pulses. Simplifies input programming not having
to define "time windows" on which the count is carried out.
Alarms
Possess two output solid state relays, each one corresponds to 2 programmable
alarms (high and low). Alarms can be absolute or relative to a general set point.
Analog output
Isolated analog outputs 0/10Volt, 4/20mA active or loop powered.
Programming
Set up and configuration is done by the Arian RPS software running on a PC. Computer connection is made to the RS485 port (using the ISO485 interface) or to the
internal connector with the RPS interface.
Since funtionalities are exactly equivalent with the id20 panel meters, detailed configuration is found on the id20 user manual.
BRO-DIN20-E-03-2009, http://www.arian.cl
1
TECHNICAL SPECIFICATIONS
INPUTS
din20-bas
Resolution 16 bit a/d, CMRR 100 dB min., 400 VAC. Min.
Input break protection TC with preset action.
Thermocouples (100 ohm max.):
Centigrade Degrees or Fahrenheit
J
(-60, 760) °C
k
(-100, 1372) °C.
T
(-86, 400) °C.
R
-1 mV, 1767 °C.
S
-1 mV, 1764 °C.
B
-1 mV, 1815 °C.
N
(-139, 1298) °C.
E
(-176, 750) °C.
Platinel
(0, 1394) °C.
C
(0, 2314) °C.
D
(0, 2314) °C.
G
(0, 2313) °C.
PT100 ( -136, 450 ) °C
DIN43760, alpha=0.0385
4...20 mA, 0...20 mA, 0...5 V, 1..5 V, 0..10 V, 0..50 mV, scalable for engineering units.
din20-vac:
Resolution:
Dc:
Ac:
Scales:
din20-tac:
Pulse inputs: NPN, PNP, Mechanical switch, TTL, High voltage (500 V).
Provides feeding for input sensor, +5, -7.5 Vdc, 30mA max.
Frequency range 0.01Hz ... 50KHz
ALARM RELAYS
Two solid state bipolar ( for DC or AC use ) relays outputs for alarms 400 VDC max and 200mA
max.
This must be used with external larger power relays unless are conected to low power loads such as
PLC or DCS inputs.
Normally open or normally close software configured.
Independent alarm outputs, each one with high and/or low alarm, with absolute or relative set point.
RS485
Modbus RTU protocol serial communications, half duplex (RS485 not RS422)
Opto isolated up to 5kV
18 bit a/d, CMRR 100 dB min., 400 VAC. Min.
Bipolar simetrical input (positive/negative voltages/ currents)
True RMS.
5 Ampers, 60mV, 2V, 6V, 20V, 60V, 200V, 600V
ANALOG OUT
Loop powered:
4... 20 mA, loop powered,
Voltage drop 4.5V max., Operating voltage 30V max.
Opto isolated (5kV).
Active loop:
0-10V and 4..20mA Active loop, driving up to 14 volts onto loads (700 ohms max. load)
Opto isolated (5kV).
POWER SUPPLY:
Low noise switching power supply.
5kV min. isolation from analog input.
20Vdc... 28Vdc, 3 W max.
CONSTRUCTION:
Reinforced polyester
Total Dimension:
Weight:
Operation temperature:
BRO-DIN20-E-03-2009, http://www.arian.cl
121 x 98 x 23 mm.
200 grams.
0 ... 50 °C.
2
PROGRAMMING
Set up configuration is done with the RPS (remote programming ) software provided on
http://www.arian.cl/downloads/arianrps.zip and running on windows PC.
Connection can be done from the RS485 lines using the ISO485 interface to the PC RS232 comm port .
Also may be done using the RPS interface cable plugged to the internal connector, taking care of the “UP”
direction for the connector, as seen on the figure.
Remove the four top cover screws for accessing the RPS connector and other internal jumpers needed for
setting the input and output type.
UP
RPS Connector
The RPS software will recognize the device and load the proper driver for reading and writing configuration
parameters.
Since the din20 is functionally equivalent to the ind20 panel meters, you may refer to the id20 user manual
for further references.
BRO-DIN20-E-03-2009, http://www.arian.cl
3
Analog output and solid state relay outputs
Power
Supply
+20... +28 Vdc, 100mA max
+V/I -V/I
Analog
Out
+0/10Vdc
A
RS485
17
Gnd
16
-420A option
0/10V and 4/20mA
active outputs.
24V Gnd
18
-420L option
4/20mA loop powered
pasive output.
15
14
+
Gnd
-4/20mA
13
R load
700 ohms max
+4/20mA
12
4.5V min.,
30V max
Modbus RTU
B
11
10
8
7
200mA max
SSR Rele
Outputs
O2 O1 Com
9
200mA max
Out 2 0.2A / 250Vac max
Out 1 0.2A / 250Vac max
Common
6
4
400Vdc max, 250Vac max
_
BEU / AZUL
+
INPUT
Gnd V+
5
V
GRN / VERDE
Gnd
-4/20mA
Gnd
TC
0/10V
0/60mV
+4/20mA
PT 100
3
BRN / CAFE
2
1
fig-din20-1
Input connections
CAUTION: Set internal jumpers
4
-7.5V
INPUT
3
2
1
+5 V
S1
HV
_
Mechanical
switch
BEU / AZUL
V
LV
3
V
+
BLK / NEGRO
Low voltage
input pulse
Inductive proximity
switch NPN, PNP
High voltage
input pulse
_
_
V
+ 60mV, 2V
V
+ 5 Amp
+ Caution:
Set internal jumper
2
6V, 20V, 60V, 200V, 600V
HV
1
INPUT
4
Gnd V+
5
din20 -BAS
_
+
BRN / CAFE
_
INPUT
4
Gnd 5A
5
din20 -VAC
Gnd -7.5V +5V S1 HV
5
din20 -TAC
Gnd
GRN / VERDE
_
BEU / AZUL
+
Gnd
Gnd
-4/20mA
TC
0/10V 0/60mV
+4/20mA
PT 100
3
BRN / CAFE
2
1
fig-din20-2
BRO-DIN20-E-03-2009, http://www.arian.cl
4
Input configuration jumpers
din20-BAS
Thermocouples, Pt-100, 0-50mV
4-20mA, 0-20mA
0-10V, 0-5V, 1-5V
din20-TAC
TTL
Low Voltage
PNP
NPN
Mechanical
Switch
din20-VAC
5 Amp.
60mV
2V
6V
20V
60V
200V
600V
din20_03
BRO-DIN20-E-03-2009, http://www.arian.cl
5
4/20mA and 0/10V active output configuration jumper
4 / 20mA
0 / 10V
din20_04
PART CODES:
din20-BAS : thermocouples, pt100, 0-10V, 4-20ma, ...
-TAC :rate meter
-VAC :amperimeter, voltimeter DC and AC true RMS.
Optional
-420L
-420A
-RS485
4..20mA pasive loop analog output.
4..20mA active, includes 0..10Vdc analog output.
modbus RTU serial communications
Example: din20-BAS-420A-RS485
MORE INFORMATION:
ARIAN S. A.
El Comendador 2340, Providencia
Santiago, Chile
Fono/Fax 56-2-4218333
[email protected]
www.arian.cl
C Copyright ARIAN S.A. 2009.
BRO-DIN20-E-03-2009, http://www.arian.cl
6