Download IPC5000 Universal Programmable Controller User Manual
Transcript
Reference [FIX control timer function] What is FIX TIMER? For normal fix control, the temperature setting is maintained before operation with that temperature setting is stopped. However, if the timer is set, operation will continue for the defined period of time and stopped. (Useful for the case that temperature should be maintained for a certain period of time.) When the timer is set for the previous fix control setting (FIX SET) screen as shown in the (4) of the following Figure, normal fix control operation will be activated if you set the button to OFF. Or, if you set to ON, fix control timer operation will continue as long as the time set at the right side. Current value: 25℃ (Example 1) Operation example when timer is on and 99 hours 59 minutes are set. Set point: 50°C END 50°C 50°C 25°C 99hours 59minutes RAMP The initial rising or declining time will be counted from the time point when WAIT is released, if WAIT is set. If the RAMP is set, the time count will start when the set point reaches to the target value (50°C). <Figure 5.6.3 > Control operation by FIX TIMER setting - 53 -