Download Multifunction Programmable Controller User Manual AC
Transcript
Chapter 9. – Modules Tag This parameter indicates the name of the instance, as assigned by default (module mnemonic) or entered by the user. Ref Temp. Reference Temperature in °C. Analog value in engineering units. Ref Press. Reference Pressure in the same units of the PIN analog input Analog value, in engineering units with allowed range from -9999 to 99999. Abs. Press. Absolute atmospheric pressure, relative to vacuum. It is used to convert the PIN and Ref. Press values to absolute values. Analog value in engineering unit. Compensation Mode It allows to select the type of compensation you want to use. No Compensation The flow measure is returned on FOUT uncompensated, with the same vale at QIN. SEL = 0; OUT = QIN Temperature The flow is compensated only by the temperature measurement: TR + 273.14 TIN + 273.14 SEL = 1; OUT = QIN * Pressure The flow is compensated only by pressure measurement: PIN + PABS SEL = 2; OUT = QIN * PR + PABS Both The flow is fully compensated, in order to provide a true mass flow measure: TR + 273.14 PIN + PABS * SEL = 3; OUT = QIN * TIN + 273.14 PR + PABS Output FOUT Corrected flow measure, calculated from the raw flow or differential pressure measurement (QIN), according to the selected compensation formula. Analog value in engineering units. 131