Chapter 9. – Modules
The maximum number of variables, for each type, is listed in the table below.
Max N°
AC 20
AC 30
Integers
1000
500
Floats
1000
500
String
400
300
Net Size
1500
1500
Some module types have a maximum number of instances allowed in the strategy.
The table below, list these limit values that cannot be exceeded.
Module
Maximum N° of
instances
PID, IMC
4
SDV, SPM
4
MV
4
HCMV
2
TRP
4
2TP
4
4TP
2
SELP
4
1BP, 2BP, 4BP, TRP, 2TP,
4TP, ALP, ADP, 4ADP, SELP,
4WAD
12 as total
LAN (transmit)
30
LAN (receive)
30
RTC
1
PRG
4
FI
1
AI
8
AO
8
DI
32
DO
32
CAIO
4
CDIO
4
In a strategy the maximum number of trend pens is 8. Therefore, if you have already
put in your strategy two modules of type 4TP, ( Four traces trend panel) you have
reached the maximum number of traces. Therefore, you cannot add any further
Trend Panel of type 2TP and TRP, even if you have exceed the maximum limit for
these types of modules. and even if you still can add 10 more display panel.
Furthermore, beyond the trend limits and the maximum number of 12 modules, you
have another important limit on the display panels; you cannot have more that 9
display modules of the same type in the strategy.
81