50
INSTALLATION
6-6. Leveling Sensor Installation
■ Correctly install plate or sensor at each floor.
If it is incorrectly installed, level errors can occur.
■ Distance between Plate and Sensor(30mm) can be found under the [Lift Data] → [Stop Length]
value located in the Inverter.
■ Sensor distance should be adjusted if you change [Stop Length] Data in Inverter.
■ Once installation is completed, PLC input of DZ Relay and movement LU or LD should be
checked.
DZ
200
LD
140
Level
P
L
A
T
E
LU
6-7. Serial Board Installation
■ COP and Hall Boards are serial communication and have transmit-receive functions.
■ Set address of each floor as shown in manual.
■ Address should not be duplicated.
■ Power Jack should be plugged in and out when you change address. Boards recognize
address only at initial operation.
■ LED1 indicates board movement state and blinks once every second.
■ RXA is communication data receive state indicator and may blink irregularly.