PowerFlex® 700S Drives - Phase II Control (Frame Sizes 9-13)
Frame 12 Size Drives
400 and 480 Volt AC Input Wiring for Frame 12 Drives
Frame 12 size drives utilize two parallel power structures, and therefore have two
sets of AC input power terminals. You must supply power to both sets of input
terminals. There are several methods for accomplishing this. Each of these methods
is shown below.
Important: Parallel wiring must have the same cable dimensions, type and routing.
Non-symmetrical wiring may cause unequal loading between the
converters and reduce the drive’s ability to deliver current to the motor.
Figure 9 Frame 12 AC Wiring Example: Two Fuses per Phase
AC Input Power Wiring, Fuses, and
Disconnect Device Provided by
Customer
AC Input Power Terminals
Inside Drive
L1
L2
1L1 1L2 1L3
L3
2L1 2L2 2L3
Figure 10 Frame 12 AC Wiring Example: One Fuse per Phase
L1
1L1 1L2 1L3
L2
L3
2L1 2L2 2L3