7.0. Connection details to Toshiba T Series PLC’s
13-Pin Screw Terminal Block
8-Pin Screw Terminal
25-Pin D-Type Male
1
1
1
13
14
TIU100, TIU110
TIU Type
TIU050, 101, 102, 103,
111, 112, 113, 201,
202, 203
13- 8- 25Pin Pin Pin
TIU300, 301, 302, 303, 304,
310, 311, 312, 313, 314,
320, 321, 322, 323, 324
RS232 Connection
Signal Name
+5V
TX 485/422+
TX 485/422RX 485/422+
RX 485/422TX RS232
Signal GND
RX RS232
Frame Gnd
RTS RS232
CTS RS232
RTS 485/422+
RTS 485/422CTS 485/422CTS 485/422+
1
2
3
4
5
6
7
8
13
-
1
2
3
4
5
6
7
8
-
12
13
24
25
2
7
3
1
4
5
14
17
18
19
25
Twisted Shielded Pair
Toshiba
T1
8-Pin
Mini-Din
5V DC
GND
5V DC
RTS
0V
TX
CTS
RX
1
2
3
4
5
6
7
8
Do not connect to unlisted pins.
Recommended cable : Beldon 9503, twisted multipair, screened.
Connect the screens together at the shield / Earth pin of the PLC