Connecting Your Ultra3000
3-5
Single-Phase Power Wired to Single-Phase Drives
The following examples illustrate grounded single-phase power wired
to single-phase Ultra3000 drives when phase-to-phase voltage is
within drive specifications.
Figure 3.4
Single-Phase Grounded Power Configurations
Transformer Secondary
L1
TB1
L1
L2
L2/N
L1
L1
230V ac
Output
AC Line
Filter
L2
L2
Ultra3000
Single-Phase
TB1 Terminals
E
Bonded cabinet ground bus
Ground grid or
Power distribution ground
Transformer Secondary
L1
115V ac
Output
L1
L1
TB1
L1
L2/N
L2/N
AC Line
Filter
L2/N
L2 (Neutral)
Ultra3000
Single-Phase
TB1 Terminals
E
Bonded cabinet ground bus
Ground grid or
Power distribution ground
Note: Reducing transformer output will reduce motor speed.
Note: Feeder and branch short circuit protection is not illustrated.
Isolation Transformer in Grounded Power Configurations
When using an isolation transformer, attach a chassis ground wire to
the neutral connection. This accomplishes the following:
•
Prevents the system from floating and thereby avoids any high
voltages that might otherwise occur (e.g., through static).
•
Provides a solid earth path for fault conditions.
ATTENTION
!
If the supply transformer is an auto transformer (not
recommended), a chassis earth ground should not be
added.
A chassis earth ground should already be included
elsewhere in the system, and adding another would
create a short.
Publication 2098-IN003E-EN-P — April 2004