Module: Disturbance Recorder Module: Disturbance Recorder Disturb rec The disturbance recorder works with 32 samples per cycle. The disturbance recorder can be started by one of eight start events (selection from the »assignment list«/OR-Logic). The disturbance record contains the measuring values inclusively pre-trigger-time. By means of Smart view/Datavisualizer (option) the oscillographic curves of the analogue (current, voltage) and digital channels/traces can be shown and evaluated in a graphical form. The disturbance recorder has a storage capacity of 120s. The disturbance recorder is able to record up to 10 s (adjustable) per record. The amount of records depends on the file size of each record. The disturbance recorder can be parameterized in the menu »Device Parameter/Recorder/Disturb rec«. Determine the max. recording time to register a disturbance event. The max. total length of a recording is 10s (inclusive pre-trigger and post-trigger time). To trigger the disturbance recorder, up to 8 signals can be selected from the »assignment list«. The trigger events are OR-linked. If a disturbance record is written, a new disturbance record cannot be triggered until all trigger signals, which have triggered the previous disturbance record, are gone. Recording is only done for the time the assigned event exists (event controlled), plus the time for the pre- and post-trigger, but not longer than 10s. The time for forward run and tracking of the disturbance recorder is shown in percent of the total recording length. Example The disturbance recorder is started by the general activation facility. After the fault has been cancelled (+ follow-up time), the recording process is stopped (but after 10s at the latest). The parameter »Auto Delete« defines how the device shall react if there is no saving place available. In case »Auto Delete« is »active«, the first recorded disturbance will be overwritten according to the FIFO principle. If the parameter is set to »inactive«, recording of the disturbance events will be stopped until the storage location is released manually. Start: 1 Trigger >1 Start: 2 Trigger Start: 3 Trigger Start: 4 Trigger >1 Start: 5 Trigger Recording Start: 6 Trigger Start: 7 Trigger Start: 8 Trigger Man Trigger Page 184 EN MRA4 04/09
Related documents
Instruction Manual
MRA4 HighPROTEC - DSF Technologies
Eton 4000 Plus Instruction manual
SonicWALL TZ 170 10 Node with Comprehensive Gateway Security
GCP-30 Series Genset Control
SonicWALL TZ 170 10 Node
USER`S MANUAL HOOK 3
FAMICO e-Platform User Manual for Counselors
INGEPAC PL70FV User Manual
User`s Manual - EV Charger News
Powerbook 2005
USER`S MANUAL TAKOO 3