ExP Protection Module – External Protection
Device Planning Parameters of the Module External Protection
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
[Device planning]
use
Global Protection Parameters of the Module External Protection
Parameter
Description
Setting range
ExBlo1
External blocking of
the module, if
blocking is activated
(allowed) within a
parameter set and if
the state of the
assigned signal is
true.
1..n, Assignment List -
External blocking of
the module, if
blocking is activated
(allowed) within a
parameter set and if
the state of the
assigned signal is
true.
1..n, Assignment List -
ExBlo2
ExBlo TripCmd
Alarm
Default
Menu path
[Protection Para
/Global Prot Para
/ExP
/ExP[1]]
[Protection Para
/Global Prot Para
/ExP
/ExP[1]]
External blocking of 1..n, Assignment List the Trip Command
of the module/the
stage, if blocking is
activated (allowed)
within a parameter
set and if the state of
the assigned signal
is true.
[Protection Para
Assignment for
External Alarm
[Protection Para
1..n, Assignment List -
/Global Prot Para
/ExP
/ExP[1]]
/Global Prot Para
/ExP
/ExP[1]]
Trip
External trip of the
1..n, Assignment List CB if the state of the
assigned signal is
true.
[Protection Para
/Global Prot Para
/ExP
/ExP[1]]
EN MRA4 04/09