SOTF-Protection Module: Switch Onto Fault
SOTF-Protection Module: Switch Onto Fault
SOTF
In case that a faulty line is energized (e.g. when an earthing switch is while maintenance in the ON-Position) an
instantaneous tripping required.
This protection module can initiate a high speed trip of the overcurrent protection modules.
This module can be started via a digital input that indicates that the circuit breaker is manually closed.
This Module issues a Signal only (This Module is not armed, does not issue
a trip command).
In order to take influence on the tripping settings of the overcurrent
protection in case of switching onto a fault, you have to assign the signal
„SOTF.EFFEKTIVE“ onto an Adaptive Parameter Set. Please refer to chapter
Parameter / Adaptive Parameter Sets. Within the Adaptive Parameter Set
you have to modify the tripping characteristic of the overcurrent protection
according to your needs.