Download PTQ AFC User Manual - ProSoft Technology
Transcript
PTQ-AFC ♦ Modicon Quantum Platform Liquid and Gas Flow Computer for Hydrocarbon Products Quick Start User Manual A waived authorization means that password entry is not required for this action even if a non-zero password has been configured. Authorization waivers are configured separately for each port, so, for example, a SCADA system connected to port 2 can be allowed to read measurement results without having to supply a password while an operator connecting AFC Manager to port 1 still must enter the correct password. The backplane is always given both waivers, so the PLC never has to supply a password. To set a hard password in AFC Manager: 1 2 3 Open the Site Configuration Dialog box Click in the Site Options field. This action opens the Site Options dialog box Select (check) option 4, Hard Passwords When this option is selected, any authorization granted using Hard Passwords times out after two minutes of inactivity, and the user will be required to re-enter the password to continue. ProSoft Technology, Inc. June 23, 2011 Page 131 of 259